OPERATION
Connecting Electrical Loads
•Let engine stabilize and warm up for a few minutes after starting.
•Plug in and turn on the desired 120 and/or 240 Volt AC, single phase, 60 Hz electrical loads.
•DO NOT connect 240 Volt loads to the 120 Volt duplex receptacles.
•DO NOT connect
•DO NOT connect 50 Hz loads to the generator.
•DO NOT OVERLOAD THE GENERATOR. See “Don’t Overload Generator”.
CAUTION
Exceeding generator’s wattage/amperage capacity can damage generator and/or electrical devices connected to it.
•See “Don’t Overload Generator”.
•Start generator and let engine stabilize before connecting electrical loads.
•Connect electrical loads in OFF position, then turn ON for operation.
•Turn electrical loads OFF and disconnect from generator before stopping generator.
Stopping the Engine
1.Turn OFF and unplug all electrical loads from generator panel receptacles. NEVER start or stop engine with electrical devices plugged in and turned ON.
2.Let engine run at
3.Move on/off switch to “Off” position.
CAUTION
Backfire, fire or engine damage could occur.
•DO NOT stop engine by moving choke lever to “Choke” position.
4.Move fuel valve to “Off” position.
RECEPTACLES
CAUTION
Receptacles may be marked with rating value greater than generator output capacity.
•NEVER attempt to power a device requiring more amperage than generator or receptacle can supply.
•DO NOT overload the generator. See “Don’t Overload Generator”.
120 Volt AC, 20 Amp, Duplex Receptacles
Each duplex receptacle (Figure 7) is protected against overload by a
Figure 7 — 120 Volt, 20 Amp Duplex Receptacles
Use each receptacle to operate 120 Volt AC,
GENERATOR ADAPTER CORD SET
The generator comes with a 25’ generator adapter cord set designed to provide two sets of 120 Volt, 20 Amp outlets from one 120 Volt, 20 Amp duplex receptacle (Figure 8).The generator adapter cord set provides a convenient supply of emergency power so that your generator can be operated safely outside.
Figure 8 — Generator Adapter Cord Set
The maximum load on each outlet is 20 Amps.The maximum total load on both black wire outlets or white stripe wire outlets is 20 Amps.
NOTE: Follow all safety precautions when connecting any extension cord or device to the generator.
10