Troubleshooting
Problem |
| Cause |
| Correction | |
|
|
|
|
| |
Automatic transfer switch does not | 1. | Generator breaker open. | 1. | Reset generator circuit breaker. | |
2. | Generator voltage not acceptable. | 2. | Refer to generator manual. | ||
transfer to generator | 3. | Generator disconnect circuit breaker | 3. | Reset generator disconnect circuit | |
|
| open. |
| breaker. | |
|
|
|
|
| |
Automatic transfer switch does not | 1. | Utility disconnect circuit breaker | 1. | Reset utility disconnect circuit | |
| open. |
| breaker. | ||
transfer to utility | 2. | Utility voltage not acceptable. | 2. | Wait for utility voltage to return to | |
|
|
|
| normal. | |
|
|
|
|
| |
Generator is still running after switch | Engine cool down period. | Engine should stop after 1 minute. | |||
transfers to utility power | |||||
|
|
|
| ||
|
|
|
|
| |
Generator or supervised loads (air | 1. | NC contacts not operating correctly. | 1. | Check NC contacts for proper | |
conditioner, etc.) are operating |
|
|
| operation and/or check control | |
improperly when generator is supplying |
|
|
| wiring to external load. | |
power | 2. | Too much load on generator. | 2. | Decrease load to generator. | |
|
|
|
|
| |
Generator is still running after utility | 1. | Minimum engine run time has not | 1. | Wait five minutes for transfer switch | |
| elapsed. |
| to retransfer to utility power. | ||
power is restored | 2. | Fuse(s) in transfer switch is | 2. | Check fuse(s) and replace if | |
|
| defective. |
| necessary | |
|
|
|
|
|