Model 071023

To Utility Meter

 

 

 

 

 

 

 

 

Utility

Connection

Load

Connection

Ground

Terminal

To Generator

9.Connect generator “UTILITY 240 VAC” terminals to transfer switch “UTILITY 240 VAC” terminals. Use minimum #14 AWG conductors.

10.Tighten all wire connections/fasteners to proper torque. See inside transfer switch enclosure for proper torque values.

Supervisory Control Wiring

Terminal strip on control module in transfer switch has four connections for customer use. There are two sets of “Normally Closed” contacts available. They will be opened when generator power is required. These can be used to lock out large loads when powered by generator. Example: air conditioner, hot water heater, etc..

Generator

Connection

Supervisory

Contacts

Neutral

Terminal

 

Main Distribution Panel

Neutral

 

Bus

Main

Ground Bus

A

Air Conditioner Contactor

24 VAC

A

Contactor

B

Neutral

B

120 VAC

 

1.Terminals on control module are for installer supplied contactors to lock out large loads. Example: air conditioner, electric hot water heater, etc.. Contacts are connected in series with the contactor control circuit.

2.Tighten all wire connections/fasteners to proper torque. See inside transfer switch enclosure for proper torque values.