Briggs & Stratton Automatic Transfer Switch manual Power Wiring Interconnections, Connection

Models: Automatic Transfer Switch

1 40
Download 40 pages 12.05 Kb
Page 7
Image 7

Power Wiring Interconnections

All wiring must be the proper size, properly supported and protected by conduit.

Complete the following connections between the transfer switch, main distribution panel, utility power and generator. The 100 Amp transfer switch (Model 071022) is depicted below and the 200 Amp transfer switch (Model 071023) is depicted on the next page.

warning

Low voltage wire cannot be installed in same conduit as power voltage wiring.

Failure to follow above warning could cause personal injury, damage and/or malfunction of equipment.

1.Ensure utility power is turned OFF. Connect utility Service conductors to line side of transfer switch service disconnect circuit breaker.

2.Connect utility service Neutral conductor to the transfer switch “NEUTRAL” terminal.

Model 071022

To Utility Meter

 

 

 

 

 

 

Utility

Connection

Load

Connection

Ground

Terminal

To Generator

3.Connect main breaker panel feeder conductors to transfer switch terminals marked “LOAD

CONNECTION”.

4.Connect main breaker panel Neutral conductor to transfer switch “NEUTRAL” terminal.

5.Connect main breaker panel Ground conductor to the transfer switch “GND” terminal.

NOTE: Assure grounding electrode conductor is connected and bonded per applicable federal, state and local codes, standards and regulations.

6.Connect generator feeder conductors from the generator control panel to line side of transfer switch “GENERATOR” breaker.

7.Connect Neutral conductor from the generator control panel to the transfer switch “NEUTRAL” terminal.

8.Connect generator Ground conductor from the control panel to the transfer switch “GND” terminal.

NOTE: Assure generator equipment grounding conductor is connected per applicable federal, state and local codes, standards and regulations.

Generator

Connection

Supervisory

Contacts

Neutral

Terminal

 

Main Distribution Panel

Neutral

 

Bus

Main

Ground Bus

7

Page 7
Image 7
Briggs & Stratton Automatic Transfer Switch manual Power Wiring Interconnections, Connection