•High efficiency furnace vent

3.INSTALLATION (CONT’D)

3.9INSTALLING 2 EXTERIOR HOODS

Choose an appropriate location to install the exterior hoods:

There must be a minimum distance of 6 feet (1.8 m) between the hoods to avoid cross-contamination

There must be a minimum distance of 18 inches (457 mm) from the ground

!WARNING

Make sure the intake hood is at least 6 feet (1.8 m) away (or more, as per applicable building codes or standards) from sources of contamination such as:

High efficiency furnace vent

Any exhaust from a combustion source

Gas meter exhaust, gas barbecue-grill

Garbage bin

Refer to figure below for connecting insulated ducts to the exterior hoods. An “Anti-gust intake hood” should be installed in regions where a lot of snow is expected to fall.

EXHAUST HOOD

18”

(457 MM)

6” Ø

(152 MM)

INTAKE HOOD

6’

18”

(1.8 M)

(457 MM)

6’

(1.8 M)

OPTIONAL

18” (457 MM)

DUCT LOCATION

TAPE AND DUCT TIE

VD0028

- 16 -