Bryan electric hot water or steam boilers...
For commercial, institutional and industrial applications
Electric Element Bundle | ||
Each element | Spacing disc for | Removable |
replaceable with | support and | threaded fittings |
hand tools. Incoloy | proper circulation | for ease of |
sheathed, 75 | around individual | individual element |
watts/sq in | elements | replacement |
150 lb ANSI flange |
|
|
Efficiency
Bryan Electric Boilers are nearly 95% efficient at all load levels. Varying loads do not effect the efficiency since the resistive type heating elements are immersed and de- signed to heat the water directly. With a modulating step control only the elements that are required to heat the water to the desired temperature/pressure will be ener- gized in order to encourage a balanced load during operation.
Replaceable Hairpins
Each element hairpin is field replaceable with no welding, soldering, or brazing required. Each hairpin, as standard for all Bryan Electric Boilers, is Incoloy sheathed and industrial size 0.430″ diameter. Elements are designed for 75 watts/sq. inch for long life (optional 50 W/D available). Elements are individually installed in a standard ANSI 150 lb. blind flange.
Bryan Series BE electric hot water** or steam boilers are compact, completely packaged and wired units with automatic controls featuring long life Incoloy sheathed elements. Applications include hot water heating, steam heating, process heating, and supplemental heat for heat pump type equipment.
All Bryan Boilers are built in accordance with the requirements of the ASME boiler and pressure vessel code and are UL listed. Water boilers are 150 psig MAWP and steam boilers either 15 psig or 150 psig. Higher pressures are available.
Steam Disengaging Area
Steam release area is near the middle of the horizontal vessel for maximum steam disengaging area for dry steam and stable water level.
Water Boiler Design
Vessel is designed for proper circulation around individual elements to maximize heat transfer. High velocities, i.e. heat pump applications, are handled with very little pressure drop when using a horizontal tank for the pressure vessel. Supply and return nozzle sizes can be made larger to accommodate the flow requirements.
Bryan BE Series Boiler Specifications
Model | Input | Nominal Output | Steam Output* |
| Approximate Total Load Amps |
| Shipping | |||||
KW | MBH | BHP | lbs/hr (kg/hr) | 208V | 240V | 380V | 480V |
| 575V | Wt. lbs (kg) | ||
|
| |||||||||||
30 | 98 | 3 | 104 (47) | 84 | 73 | 47 | 37 |
| 31 | 800 | (365) | |
45 | 147 | 4.5 | 155 (70) | 126 | 109 | 69 | 55 |
| 46 | 825 | (375) | |
60 | 196 | 6 | 207 (93) | 168 | 146 | 92 | 73 |
| 61 | 850 | (390) | |
75 | 245 | 7.5 | 259 (117) | 209 | 182 | 115 | 91 |
| 76 | 875 | (400) | |
90 | 294 | 9 | 311 (141) | 251 | 218 | 138 | 109 |
| 91 | 1000 (455) | ||
105 | 343 | 10.5 | 362 (164) | 293 | 254 | 161 | 127 |
| 107 | 1050 (480) | ||
120 | 393 | 12 | 414 (187) | 334 | 290 | 184 | 146 |
| 122 | 1100 (500) | ||
135 | 441 | 13.5 | 466 (211) | 376 | 326 | 206 | 164 |
| 137 | 1300 (590) | ||
150 | 491 | 15 | 518 (234) | 418 | 362 | 229 | 182 |
| 152 | 1325 (600) | ||
165 | 539 | 16.5 | 569 (258) | 460 | 398 | 252 | 200 |
| 167 | 1350 (615) | ||
180 | 589 | 18 | 621 (281) | 501 | 435 | 275 | 218 |
| 182 | 1400 (635) | ||
195 | 637 | 19.5 | 673 (305) | 543 | 471 | 298 | 236 |
| 197 | 1450 (660) | ||
210 | 687 | `21 | 725 (328) | 585 | 507 | 320 | 254 |
| 212 | 1950 (885) | ||
240 | 786 | 24 | 828 (375) | 668 | 579 | 366 | 290 |
| 242 | 2000 (910) | ||
270 | 884 | 27 | 932 (422) | 751 | 651 | 412 | 326 |
| 272 | 2450 | (1115) | |
300 | 982 | 30 | 1035 (469) | 835 | 724 | 457 | 362 |
| 303 | 2500 | (1135) | |
330 | 1081 | 33 | 1139 (516) | 918 | 796 | 503 | 398 |
| 333 | 2550 | (1160) | |
360 | 1179 | 36 | 1242 (563) | 1001 | 868 | 549 | 435 |
| 363 | 2600 | (1180) | |
390 | 1277 | 39 | 1346 (610) | 1085 | 940 | 594 | 471 |
| 393 | 2650 | (1205) | |
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTES: * Lbs. steam per hour from and at 212°F. ** Not intended for use as a principal heating source for living space of any individual residence.