Bryan Water-PakTM Indirect Water Heater Systems
Water-Pak Selection
1.Select Heater Model based on "Heater Specifications" table below.
2.Select storage capacity from "Storage Tank Specifications" tables, horizontal or vertical tank depending on space considerations.
Selection Procedure Example
A requirement of 800 gph at 100° rise. Storage capacity 1000 gallons. Fuel, gas. Tank lining, cement.
1.From "Heater Specifications" table, select Model No. CLM-
2.From the "Storage Tank Specifications" tables, suppose you select the 1045 gallon horizontal tank.
3.Then the setting shown in diagram "AH" (horizontal tank) would be appropriate.
Specify:
3.Choose appropriate "Setting" from "Heater, Tank Setting" diagrams on previous page.
Indirect | Fuel | Storage | Setting | Tank Lining | Tank |
Heater | Section |
| Insulated | ||
Model | Size |
| PVC | ||
| (gals.) |
|
| Jacket |
Indirect Heater Specifications
Heater | Model |
| Heater Capacity |
| |||
Output |
| Gallons Per Hour* |
| ||||
Series | Number | BTU/HR | |||||
|
| ||||||
DR SERIES | 280,000 | 559 | 420 | 336 | — | ||
(Forced Draft) | 360,000 | 720 | 540 | 432 | — | ||
F SERIES | 520,000 | 1,039 | 780 | 624 | — | ||
(Atmospheric) | 680,000 | 1,359 | 1,020 | 816 | — | ||
CLM SERIES | 960,000 | 1,920 | 1,440 | 1,152 | 960 | ||
(Forced Draft) | 1,200,000 | 2,400 | 1,800 | 1,440 | 1,200 | ||
& | 1,440,000 | 2,880 | 2,160 | 1,728 | 1,440 | ||
(Atmospheric) | |||||||
1,680,000 | 3,660 | 2,520 | 2,016 | 1,680 | |||
| |||||||
| 1,920,000 | 3,840 | 2,880 | 2,304 | 1,920 | ||
| 2,160,000 | 4,320 | 3,240 | 2,592 | 2,160 | ||
| 2,400,000 | 4,800 | 3,600 | 2,880 | 2,400 | ||
K SERIES | 2,800,000 | 5,600 | 4,200 | 3,360 | 2,800 | ||
(Atmospheric) | 3,200,000 | 6,400 | 4,800 | 3,840 | 3,200 | ||
| 3,600,000 | 7,200 | 5,400 | 4,320 | 3,600 | ||
| 4,000,000 | 8,000 | 6,000 | 4,800 | 4,000 | ||
| 4,400,000 | 8,800 | 6,600 | 5,280 | 4,400 | ||
| 4,800,000 | 9,600 | 7,200 | 5,760 | 4,800 | ||
| 5,200,000 | 10,400 | 7,800 | 6,240 | 5,200 | ||
AB SERIES | 720,000 | 1,440 | 1,080 | 864 | 720 | ||
(Forced Draft) | 960,000 | 1,920 | 1,440 | 1,152 | 960 | ||
| 1,200,000 | 2,400 | 1,800 | 1,440 | 1,200 | ||
| 1,680,000 | 3,360 | 2,520 | 2,016 | 1,680 | ||
| 2,000,000 | 4,000 | 3,000 | 2,400 | 1,999 | ||
| 2,400,000 | 4,800 | 3,600 | 2,880 | 2,400 | ||
RV SERIES | 2,800,000 | 5,600 | 4,200 | 3,360 | 2,800 | ||
(Forced Draft) | 3,200,000 | 6,400 | 4,800 | 3,840 | 3,200 | ||
| 3,600,000 | 7,200 | 5,400 | 4,320 | 3,600 | ||
| 4,000,000 | 8,000 | 6,000 | 4,800 | 4,000 | ||
| 4,400,000 | 8,800 | 6,600 | 4,280 | 4,400 | ||
| 4,800,000 | 9,600 | 7,200 | 5,760 | 4,800 | ||
| 5,600,000 | 11,200 | 8,400 | 6,720 | 5,600 | ||
| 6,400,000 | 12,800 | 9,600 | 7,680 | 6,400 | ||
|
|
|
|
|
|
|
† These units are equipped with two heat exchangers as standard and require a copper header to be field supplied.
*Note 1: Contact factory for ratings at other conditions.
Note 2: Heater is not intended to provide the temperature increases shown above instantly, but will raise the temperature of the gallons listed to final storage temperature within one hour.
Note 3: Select adequate storage tank capacity to handle peak demand. Keep in mind that, typically, only 75% of tank capacity is usable storage.
Storage Tank Specifications
Tank | Tank | Approximate |
Capacity | Dia × Length | Weight |
gallons | in (cm) | lbs (Kg) |
| Horizontal Tanks |
|
36×96 (91.4×243.8) | 2,000 (907) | |
42×96 (106.7×243.8) | 2,200 (998) | |
42×144 (106.7×365.8) | 3,000 (1,361) | |
48×144 (121.9×365.8) | 3,800 (1,724) | |
54×168 (137.2×426.7) | 5,600 (2,540) | |
60×192 (152.4×487.7) | 6,900 (3,130) | |
72×168 (182.9×426.7) | 8,100 (3,674) | |
72×216 (182.9×548.6) | 10,100 (4,581) | |
|
|
|
| Vertical Tanks |
|
36×84 (91.40×213.4) | 1,700 (771) | |
42×96 (106.7×243.8) | 2,200 (998) | |
48×96 (121.9×243.8) | 2,700 (1,225) | |
54×96 (137.2×243.8) | 3,100 (1,406) | |
60×96 (152.4×243.8) | 4,000 (1,814) | |
72×96 (182.9×243.8) | 5,300 (2,404) | |
84×96 (213.4×243.8) | 7,000 (3,175) | |
|
|
|