Bryant 113A warranty Vapor Line Sizing And Cooling Capacity Loss, Physical Data

Models: 113A

1 38
Download 38 pages 62.83 Kb
Page 3
Image 3
PHYSICAL DATA

PHYSICAL DATA

UNIT SIZE---VOLTAGE, SERIES

018---D

024---D

030---E

 

036---E

 

042---C

048---E

060---F

 

 

 

 

 

 

 

 

 

 

Operating Weight lb (kg)

107

110

111

 

141

 

190

186

190

(48.5)

(49.9)

(50.3)

 

(64.0)

 

(86.2)

(84.4)

(86.2)

 

 

 

Shipping Weight lb (kg)

130

134

136

 

170

 

218

224

226

(59.0)

(60.8)

(61.7)

 

(77.1)

 

(98.9)

(101.6)

(102.5)

 

 

 

Compressor Type

 

 

 

 

Scroll

 

 

 

 

REFRIGERANT

 

 

 

Puron(R--- 410A)

 

 

 

Control

 

 

TXV (PuronHard Shutoff)

 

 

Charge lb (kg)

3.50

3.80

4.1

 

5.34

 

5.84

7.00

8.19

(1.60)

(1.72)

(1.86)

 

(2.42)

 

(2.65)

(3.18)

(3.71)

 

 

 

COND FAN

 

 

Propeller

Type, Direct

Drive

 

 

Air Discharge

 

 

 

 

Vertical

 

 

 

Air Qty (CFM)

1792

2218

2218

 

2954

 

3167

3644

3129

Motor HP

1/12

1/10

1/10

 

1/4

 

1/5

1/4

1/4

Motor RPM

1100

1100

1100

 

1100

 

1100

1100

800

COND COIL

 

 

 

 

 

 

 

 

 

Face Area (Sq ft)

8.4

8.4

9.80

 

13.13

 

17.25

19.40

12.93

Fins per In.

20

25

25

 

25

 

25

25

20

Rows

1

1

1

 

1

 

1

1

2

Circuits

3

3

3

 

3

 

4

5

5

VALVE CONNECT. (In. ID)

 

 

 

 

 

 

 

 

 

Vapor

3/4

3/4

3/4

 

7/8

 

7/8

7/8

1--- 1/8

Liquid

 

 

 

 

3/8

 

 

 

 

REFRIGERANT TUBES (In. OD)

 

 

 

 

 

 

 

 

 

Rated Vapor*

3/4

3/4

7/8

 

7/8

 

1--- 1/8

1--- 1/8

1--- 1/8

Liquid

 

 

 

 

3/8

 

 

 

 

*Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset. Note: See unit Installation Instruction for proper installation.

113A

VAPOR LINE SIZING AND COOLING CAPACITY LOSS

LONG LINE APPLICATION: An application is considered ”Long line” when the total equivalent tubing length exceeds 80 ft. (24.38

m)or when there is more than 20 ft. (6.09 m) vertical separation between indoor and outdoor units. These applications require additional accessories and system modifications for reliable system operation. The maximum allowable total equivalent length is up to 250 ft. (76.2 m). The maximum vertical separation 200 ft. (60.96

m)when outdoor unit is above indoor unit, and up to 80 ft. (24.38

m)when the outdoor unit is below the indoor unit. Refer to Accessory Usage Guideline below for required accessories. See Longline Application Guideline for required piping and system modifications. Also, refer to the table below for the vapor tube diameters based on the total length to minimize the cooling capacity loss.

 

 

 

 

 

 

 

 

Cooling Capacity Loss (%)

 

 

 

 

Unit

 

Maximum

Vapor Line

 

 

 

Total Equivalent Line Length ft. (m)

 

 

 

 

 

Liquid Line

Standard

 

 

 

 

 

 

 

 

Nominal

 

Diameters

 

Long Line Application Requires Accessories

 

 

 

Diameters

Application

 

 

 

Size (Btuh)

 

(In. OD)

 

 

 

 

 

 

 

 

 

(In. OD)

 

 

 

 

 

 

 

 

 

 

 

 

 

26---50

51---80

81---100

101---125

126---150

151---175

176---200

201---225

226---250

 

 

 

 

 

 

 

 

 

 

(7.9---15.2)

(15.5---24.4)

(24.7---30.5)

(30.8---38.1)

(38.4---45.7)

(46.0---53.3)

(53.6---61.0)

(61.3---68.6)

(68.9---76.2)

 

18000

 

3/8

1/2

1

2

3

5

6

7

8

9

11

 

1 Stage

 

5/8

0

1

1

1

2

2

2

3

3

 

Puron AC

 

 

3/4

0

0

0

0

1

1

1

1

1

 

24000

 

3/8

5/8

0

1

2

2

3

3

4

5

5

 

1 Stage

 

3/4

0

0

1

1

1

1

1

2

2

 

Puron AC

 

 

7/8

0

0

0

0

0

1

1

1

1

 

30000

 

3/8

5/8

1

2

3

3

4

5

6

7

8

 

1 Stage

 

3/4

0

0

1

1

1

2

2

2

3

 

Puron AC

 

 

7/8

0

0

0

0

1

1

1

1

1

 

36000

 

3/8

5/8

1

2

4

5

6

8

9

10

12

 

1 Stage

 

3/4

0

1

1

2

2

3

3

4

4

 

Puron AC

 

 

7/8

0

0

0

1

1

1

1

2

2

 

42000

 

3/8

3/4

0

1

2

2

3

4

4

5

6

 

1 Stage

 

7/8

0

0

1

1

1

2

2

2

3

 

Puron AC

 

 

1 1/8

0

0

0

0

0

0

0

0

0

 

48000

 

3/8

3/4

0

1

2

3

4

5

5

6

7

 

1 Stage

 

7/8

0

0

1

1

2

2

2

3

3

 

Puron AC

 

 

1 1/8

0

0

0

0

0

0

0

1

1

 

60000

 

3/8

3/4

1

2

4

5

6

7

9

10

11

 

1 Stage

 

7/8

0

1

2

2

3

4

4

5

5

 

Puron AC

 

 

1 1/8

0

0

0

1

1

1

1

1

1

 

 

 

 

 

Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines

 

 

 

Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit

See Long Line Applica-

 

tion Guidelines

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Page 3
Image 3
Bryant 113A warranty Vapor Line Sizing And Cooling Capacity Loss, Physical Data

FAQ

What is the maximum allowable total equivalent length for long line applications?

The maximum allowable total equivalent length for long line applications is up to 250 ft (76.2 m).

What type of refrigerant does the Bryant 113A model use?

The Bryant 113A model uses Puron R-410A refrigerant.

What are the motor HP and RPM for the cond fan?

The cond fan motor HP ranges from 1/12 to 1/4, and the RPM is 1100.