113A
DETAILED COOLING CAPACITIES# CONTINUED
EVAPORATOR AIR |
|
|
|
|
|
|
| CONDENSER ENTERING AIR TEMPERATURES ° F (° C) |
|
|
|
|
|
|
| ||||||
|
|
| 75 (23.9) |
|
| 85 (29.4) |
|
| 95 (35) |
|
| 105 (40.6) |
|
|
| 115 (46.1) |
|
| 125 (51.7) |
| |
CFM | EWB | Capacity MBtuh | Total | Capacity MBtuh | Total | Capacity MBtuh | Total | Capacity MBtuh |
| Total | Capacity MBtuh | Total | Capacity MBtuh | Total | |||||||
|
| Sys. |
|
| Sys. |
|
|
| Sys. |
|
|
| Sys. |
|
| Sys. |
|
| Sys. | ||
° F (° C) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| Total | Sens‡ | KW** | Total | Sens‡ | KW** | Total |
| Sens‡ | KW** | Total | Sens‡ |
| KW** | Total | Sens‡ | KW** | Total | Sens‡ | KW** | |
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| 113A*A060 Outdoor Section With CAR**6034A** Indoor Section |
|
|
|
|
|
|
| |||||||
| 72 (22.2) | 67.80 | 34.89 | 4.35 | 64.83 | 33.80 | 4.80 | 61.64 |
| 32.64 | 5.29 | 58.24 | 31.43 |
| 5.83 | 54.52 | 30.11 | 6.41 | 50.31 | 28.65 | 7.04 |
| 67 (19.4) | 62.53 | 43.30 | 4.28 | 59.78 | 42.18 | 4.73 | 56.82 |
| 41.00 | 5.22 | 53.69 | 39.76 |
| 5.76 | 50.29 | 38.43 | 6.35 | 46.47 | 36.96 | 6.99 |
1750 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
63 (17.2)†† | 58.72 | 42.13 | 4.23 | 56.15 | 41.01 | 4.68 | 53.37 |
| 39.81 | 5.17 | 50.43 | 38.56 |
| 5.71 | 47.26 | 37.23 | 6.31 | 43.72 | 35.76 | 6.95 | |
| 62 (16.7) | 57.74 | 51.63 | 4.22 | 55.26 | 50.49 | 4.66 | 52.60 |
| 49.24 | 5.16 | 49.85 | 49.43 |
| 5.71 | 47.17 | 47.17 | 6.31 | 44.20 | 44.20 | 6.96 |
| 57 (13.9) | 56.44 | 56.44 | 4.20 | 54.39 | 54.39 | 4.65 | 52.16 |
| 52.16 | 5.15 | 49.79 | 49.79 |
| 5.71 | 47.18 | 47.18 | 6.31 | 44.20 | 44.20 | 6.96 |
| 72 (22.2) | 68.70 | 36.53 | 4.46 | 65.64 | 35.43 | 4.91 | 62.33 |
| 34.26 | 5.40 | 58.81 | 33.03 |
| 5.94 | 54.97 | 31.69 | 6.52 | 50.63 | 30.21 | 7.14 |
| 67 (19.4) | 63.42 | 45.98 | 4.39 | 60.56 | 44.86 | 4.83 | 57.50 |
| 43.66 | 5.33 | 54.27 | 42.41 |
| 5.87 | 50.76 | 41.06 | 6.46 | 46.84 | 39.55 | 7.09 |
2000 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
63 (17.2)†† | 59.63 | 44.67 | 4.34 | 56.94 | 43.52 | 4.78 | 54.07 |
| 42.32 | 5.28 | 51.04 | 41.05 |
| 5.82 | 47.76 | 39.69 | 6.41 | 44.11 | 38.17 | 7.06 | |
| 62 (16.7) | 58.86 | 55.26 | 4.33 | 56.34 | 55.78 | 4.78 | 53.88 |
| 53.88 | 5.28 | 51.35 | 51.35 |
| 5.83 | 48.55 | 48.55 | 6.42 | 45.37 | 45.37 | 7.07 |
| 57 (13.9) | 58.44 | 58.44 | 4.32 | 56.26 | 56.26 | 4.78 | 53.88 |
| 53.88 | 5.28 | 51.35 | 51.35 |
| 5.83 | 48.56 | 48.56 | 6.42 | 45.38 | 45.38 | 7.07 |
| 72 (22.2) | 69.36 | 38.09 | 4.57 | 66.19 | 36.98 | 5.01 | 62.79 |
| 35.79 | 5.50 | 59.18 | 34.55 |
| 6.04 | 55.24 | 33.21 | 6.62 | 50.79 | 31.71 | 7.24 |
| 67 (19.4) | 64.04 | 48.55 | 4.49 | 61.12 | 47.42 | 4.94 | 57.98 |
| 46.21 | 5.43 | 54.67 | 44.94 |
| 5.97 | 51.08 | 43.55 | 6.56 | 47.07 | 41.97 | 7.19 |
2250 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
63 (17.2)†† | 60.27 | 47.08 | 4.44 | 57.52 | 45.93 | 4.89 | 54.56 |
| 44.70 | 5.38 | 51.46 | 43.41 |
| 5.92 | 48.11 | 42.01 | 6.51 | 44.39 | 40.42 | 7.16 | |
| 62 (16.7) | 60.07 | 60.07 | 4.44 | 57.75 | 57.75 | 4.89 | 55.24 |
| 55.24 | 5.39 | 52.57 | 52.57 |
| 5.94 | 49.63 | 49.63 | 6.54 | 46.28 | 46.28 | 7.18 |
| 57 (13.9) | 60.07 | 60.07 | 4.44 | 57.75 | 57.75 | 4.89 | 55.25 |
| 55.25 | 5.39 | 52.58 | 52.58 |
| 5.94 | 49.64 | 49.64 | 6.54 | 46.28 | 46.28 | 7.18 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
34
COOLING INDOOR | CAPACITY | POWER | FURNACE MODEL | |
MODEL | ||||
|
|
| ||
*CAP**6024A** | 1.00 | 1.00 |
| |
CAP**6021A** | 0.98 | 0.98 |
| |
CNPH*6024A** | 0.99 | 0.99 |
| |
CNPV*6024A** | 0.99 | 0.99 |
| |
CSPH*6012A** | 1.00 | 1.00 |
| |
FV4BNB006 | 0.99 | 0.97 |
| |
FX4CN(B,F)060 | 1.01 | 1.01 |
| |
FY4ANB060 | 0.98 | 0.98 |
| |
CAP**6021A** | 0.97 | 0.97 | 315(A,J)AV060110 | |
CSPH*6012A** | 0.98 | 0.98 | 315(A,J)AV060110 | |
CAP**6024A** | 0.98 | 0.98 | 315(A,J)AV066135 | |
CNPH*6024A** | 0.97 | 0.96 | 315(A,J)AV066135 | |
CNPV*6024A** | 0.97 | 0.97 | 315(A,J)AV066135 |
* Tested combination.
COOLING INDOOR | CAPACITY | POWER | FURNACE MODEL | |
MODEL | ||||
|
|
| ||
CSPH*6012A** | 0.98 | 0.97 | 315(A,J)AV066135 | |
CAP**6024A** | 0.98 | 0.97 | 315(A,J)AV066155 | |
CNPH*6024A** | 0.98 | 0.97 | 315(A,J)AV066155 | |
CNPV*6024A** | 0.98 | 0.97 | 315(A,J)AV066155 | |
CSPH*6012A** | 0.98 | 0.97 | 315(A,J)AV066155 | |
CAP**6021A** | 0.98 | 0.98 | 353AAV060100 | |
CNPH*6024A** | 0.98 | 0.98 | 353AAV060100 | |
CSPH*6012A** | 0.98 | 0.98 | 353AAV060100 | |
CAP**6024A** | 0.98 | 0.98 | 353AAV060120 | |
CNPH*6024A** | 0.98 | 0.98 | 353AAV060120 | |
CNPV*6024A** | 0.98 | 0.98 | 353AAV060120 | |
CSPH*6012A** | 0.98 | 0.98 | 353AAV060120 | |
CAP**6021A** | 0.97 | 1.01 | 355(A,C)AV060080 |
COOLING INDOOR | CAPACITY | POWER | FURNACE MODEL | |
MODEL | ||||
|
|
| ||
CAP**6021A** | 0.97 | 0.99 | 355(A,C)AV060100 | |
CAP**6024A** | 0.98 | 0.98 | 355(A,C)AV060120 | |
CAP**6021A** | 0.97 | 0.97 | 313*AV048090 | |
CNPH*6024A** | 0.97 | 0.97 | 313*AV048090 | |
CSPH*6012A** | 0.97 | 0.97 | 313*AV048090 | |
CAP**6021A** | 0.97 | 0.96 | 313*AV060110 | |
CNPH*6024A** | 0.98 | 0.97 | 313*AV060110 | |
CSPH*6012A** | 0.98 | 0.97 | 313*AV060110 | |
CAP**6024A** | 0.97 | 0.97 | 313*AV060135 | |
CNPH*6024A** | 0.97 | 0.97 | 313*AV060135 | |
CNPV*6024A** | 0.97 | 0.97 | 313*AV060135 | |
CSPH*6012A** | 0.97 | 0.97 | 313*AV060135 |
{Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
}Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F (27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F (27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F (27_C).
#Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard
** System kw is total of indoor and outdoor unit kilowatts.
{{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice. EWB — Entering Wet Bulb
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.