Bryant 265A warranty Detailed Cooling Capacities Continued, Evaporator

Models: 265A

1 32
Download 32 pages 6.91 Kb
Page 24
Image 24
Manual background

DETAILED COOLING CAPACITIES CONTINUED

EVAPORATOR

 

 

 

 

 

 

 

CONDENSER ENTERING AIR TEMPERATURES deg F

 

 

 

 

 

 

 

AIR

 

75

 

 

85

 

 

 

95

 

 

105

 

 

115

 

 

125

 

 

 

 

Capacity

Total

Capacity

 

Total

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

CFM

 

EWB

MBtuh†

Sys-

MBtuh†

 

Sys-

MBtuh†

Sys-

MBtuh†

Sys-

MBtuh†

Sys-

MBtuh†

Sys-

 

 

 

tem

 

 

 

tem

 

 

tem

 

 

tem

 

 

tem

 

 

tem

 

 

 

Total

Sens

KW*

Total

Sens

 

KW*

Total

Sens

KW*

Total

Sens

KW*

Total

Sens

KW*

Total

Sens

KW*

 

 

 

*

 

*

*

*

*

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

265ANA060

---B Outdoor

Section

With FX4CNF060 Indoor Section

 

 

 

 

 

 

 

 

 

72

71.33

36.68

4.31

67.94

35.37

 

4.75

64.29

33.97

5.23

60.48

32.53

5.76

56.36

31.00

6.34

51.80

29.32

6.95

 

 

67

65.68

45.79

4.24

62.55

44.44

 

4.68

59.19

43.00

5.17

55.69

41.53

5.70

51.91

39.96

6.27

47.75

38.25

6.89

1750

 

63

61.47

44.48

4.19

58.52

43.11

 

4.63

55.39

41.68

5.12

52.12

40.20

5.65

48.60

38.63

6.22

44.75

36.92

6.84

 

 

62

60.32

54.79

4.18

57.45

53.36

 

4.62

54.41

51.84

5.11

51.27

50.21

5.64

48.05

48.05

6.22

44.86

44.86

6.84

 

 

57

58.31

58.31

4.16

55.99

55.99

 

4.61

53.53

53.53

5.10

50.90

50.90

5.63

48.05

48.05

6.22

44.86

44.86

6.84

 

 

72

72.40

38.30

4.40

68.88

36.98

 

4.84

65.09

35.56

5.33

61.15

34.10

5.86

56.89

32.55

6.43

52.19

30.86

7.04

 

 

67

66.76

48.55

4.34

63.50

47.18

 

4.78

60.00

45.72

5.26

56.37

44.22

5.79

52.46

42.62

6.36

48.17

40.87

6.98

2000

 

63

62.55

47.09

4.29

59.48

45.70

 

4.73

56.22

44.24

5.21

52.82

42.73

5.74

49.18

41.12

6.31

45.20

39.37

6.93

 

 

62

61.49

58.54

4.28

58.54

57.01

 

4.72

55.41

55.41

5.20

52.57

52.57

5.74

49.53

49.53

6.32

46.13

46.13

6.95

 

 

57

60.49

60.49

4.27

58.02

58.02

 

4.71

55.37

55.37

5.20

52.58

52.58

5.74

49.53

49.53

6.32

46.13

46.13

6.95

 

 

72

73.17

39.84

4.49

69.54

38.50

 

4.93

65.65

37.08

5.42

61.60

35.61

5.94

57.24

34.04

6.51

52.42

32.34

7.12

 

 

67

67.52

51.19

4.43

64.16

49.81

 

4.87

60.56

48.32

5.35

56.83

46.79

5.88

52.83

45.15

6.45

48.44

43.34

7.07

2250

 

63

63.34

49.57

4.38

60.17

48.16

 

4.82

56.81

46.67

5.30

53.32

45.13

5.83

49.59

43.48

6.40

45.51

41.66

7.02

 

 

62

62.50

61.84

4.37

59.65

59.65

 

4.81

56.86

56.86

5.31

53.91

53.91

5.84

50.70

50.70

6.42

47.12

47.12

7.05

 

 

57

62.26

62.26

4.37

59.66

59.66

 

4.81

56.86

56.86

5.31

53.92

53.92

5.84

50.71

50.71

6.42

47.12

47.12

7.05

265A

Cooling Indoor Model

Capacity

Power

Furnace Model

*FX4CN(B,F)060

1.00

1.00

 

FE4ANB006

0.99

0.99

 

FV4BNB006

0.99

0.99

 

FY4ANB060

0.99

1.06

 

CAP**6021A**

0.97

0.99

 

CAP**6024A**

0.98

1.03

 

CNPH*6024A**

0.98

1.03

 

CNPV*6024A**

0.98

1.03

 

CSPH*6012A**

0.98

1.02

 

Cooling Indoor Model

Capacity

Power

Furnace Model

CAP**6021A**

0.97

0.99

315(A,J)AV060110

CNPH*6024A**

0.98

1.00

315(A,J)AV060110

CSPH*6012A**

0.98

1.00

315(A,J)AV060110

CAP**6024A**

0.98

1.00

315(A,J)AV066135

CNPH*6024A**

0.98

1.00

315(A,J)AV066135

CNPV*6024A**

0.98

1.00

315(A,J)AV066135

CSPH*6012A**

0.98

1.00

315(A,J)AV066135

CAP**6024A**

0.98

1.01

315(A,J)AV066155

CNPH*6024A**

0.98

1.00

315(A,J)AV066155

CNPV*6024A**

0.98

1.00

315(A,J)AV066155

CSPH*6012A**

0.98

1.01

315(A,J)AV066155

NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.

*Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240---94. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

{Total and sensible capacities are net capacities. Blower motor heat has been subtracted.

}Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F (27_C), deduct 835 Btuh

(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F (27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F (27_C).

** System kw is total of indoor and outdoor unit kilowatts.

{{At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb. EWB — Entering Wet Bulb

24