
DETAILED COOLING CAPACITIES CONTINUED
| EVAPORATOR | 
 | 
 | 
 | 
 | 
 | 
 | 
 | CONDENSER ENTERING AIR TEMPERATURES deg F | 
 | 
 | 
 | 
 | 
 | 
 | |||||||
| 
 | AIR | 
 | 75 | 
 | 
 | 85 | 
 | 
 | 
 | 95 | 
 | 
 | 105 | 
 | 
 | 115 | 
 | 
 | 125 | 
 | |
| 
 | 
 | 
 | Capacity | Total | Capacity | 
 | Total | Capacity | Total | Capacity | Total | Capacity | Total | Capacity | Total | ||||||
| CFM | 
 | EWB | MBtuh† | Sys- | MBtuh† | 
 | Sys- | MBtuh† | Sys- | MBtuh† | Sys- | MBtuh† | Sys- | MBtuh† | Sys- | ||||||
| 
 | 
 | 
 | tem | 
 | 
 | 
 | tem | 
 | 
 | tem | 
 | 
 | tem | 
 | 
 | tem | 
 | 
 | tem | ||
| 
 | 
 | 
 | Total | Sens | KW* | Total | Sens | 
 | KW* | Total | Sens | KW* | Total | Sens | KW* | Total | Sens | KW* | Total | Sens | KW* | 
| 
 | 
 | 
 | ‡ | * | ‡ | 
 | * | ‡ | * | ‡ | * | ‡ | * | ‡ | * | ||||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||||||||||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 265ANA060 | Section | With FX4CNF060 Indoor Section | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |||
| 
 | 
 | 72 | 71.33 | 36.68 | 4.31 | 67.94 | 35.37 | 
 | 4.75 | 64.29 | 33.97 | 5.23 | 60.48 | 32.53 | 5.76 | 56.36 | 31.00 | 6.34 | 51.80 | 29.32 | 6.95 | 
| 
 | 
 | 67 | 65.68 | 45.79 | 4.24 | 62.55 | 44.44 | 
 | 4.68 | 59.19 | 43.00 | 5.17 | 55.69 | 41.53 | 5.70 | 51.91 | 39.96 | 6.27 | 47.75 | 38.25 | 6.89 | 
| 1750 | 
 | 63 | 61.47 | 44.48 | 4.19 | 58.52 | 43.11 | 
 | 4.63 | 55.39 | 41.68 | 5.12 | 52.12 | 40.20 | 5.65 | 48.60 | 38.63 | 6.22 | 44.75 | 36.92 | 6.84 | 
| 
 | 
 | 62 | 60.32 | 54.79 | 4.18 | 57.45 | 53.36 | 
 | 4.62 | 54.41 | 51.84 | 5.11 | 51.27 | 50.21 | 5.64 | 48.05 | 48.05 | 6.22 | 44.86 | 44.86 | 6.84 | 
| 
 | 
 | 57 | 58.31 | 58.31 | 4.16 | 55.99 | 55.99 | 
 | 4.61 | 53.53 | 53.53 | 5.10 | 50.90 | 50.90 | 5.63 | 48.05 | 48.05 | 6.22 | 44.86 | 44.86 | 6.84 | 
| 
 | 
 | 72 | 72.40 | 38.30 | 4.40 | 68.88 | 36.98 | 
 | 4.84 | 65.09 | 35.56 | 5.33 | 61.15 | 34.10 | 5.86 | 56.89 | 32.55 | 6.43 | 52.19 | 30.86 | 7.04 | 
| 
 | 
 | 67 | 66.76 | 48.55 | 4.34 | 63.50 | 47.18 | 
 | 4.78 | 60.00 | 45.72 | 5.26 | 56.37 | 44.22 | 5.79 | 52.46 | 42.62 | 6.36 | 48.17 | 40.87 | 6.98 | 
| 2000 | 
 | 63 | 62.55 | 47.09 | 4.29 | 59.48 | 45.70 | 
 | 4.73 | 56.22 | 44.24 | 5.21 | 52.82 | 42.73 | 5.74 | 49.18 | 41.12 | 6.31 | 45.20 | 39.37 | 6.93 | 
| 
 | 
 | 62 | 61.49 | 58.54 | 4.28 | 58.54 | 57.01 | 
 | 4.72 | 55.41 | 55.41 | 5.20 | 52.57 | 52.57 | 5.74 | 49.53 | 49.53 | 6.32 | 46.13 | 46.13 | 6.95 | 
| 
 | 
 | 57 | 60.49 | 60.49 | 4.27 | 58.02 | 58.02 | 
 | 4.71 | 55.37 | 55.37 | 5.20 | 52.58 | 52.58 | 5.74 | 49.53 | 49.53 | 6.32 | 46.13 | 46.13 | 6.95 | 
| 
 | 
 | 72 | 73.17 | 39.84 | 4.49 | 69.54 | 38.50 | 
 | 4.93 | 65.65 | 37.08 | 5.42 | 61.60 | 35.61 | 5.94 | 57.24 | 34.04 | 6.51 | 52.42 | 32.34 | 7.12 | 
| 
 | 
 | 67 | 67.52 | 51.19 | 4.43 | 64.16 | 49.81 | 
 | 4.87 | 60.56 | 48.32 | 5.35 | 56.83 | 46.79 | 5.88 | 52.83 | 45.15 | 6.45 | 48.44 | 43.34 | 7.07 | 
| 2250 | 
 | 63 | 63.34 | 49.57 | 4.38 | 60.17 | 48.16 | 
 | 4.82 | 56.81 | 46.67 | 5.30 | 53.32 | 45.13 | 5.83 | 49.59 | 43.48 | 6.40 | 45.51 | 41.66 | 7.02 | 
| 
 | 
 | 62 | 62.50 | 61.84 | 4.37 | 59.65 | 59.65 | 
 | 4.81 | 56.86 | 56.86 | 5.31 | 53.91 | 53.91 | 5.84 | 50.70 | 50.70 | 6.42 | 47.12 | 47.12 | 7.05 | 
| 
 | 
 | 57 | 62.26 | 62.26 | 4.37 | 59.66 | 59.66 | 
 | 4.81 | 56.86 | 56.86 | 5.31 | 53.92 | 53.92 | 5.84 | 50.71 | 50.71 | 6.42 | 47.12 | 47.12 | 7.05 | 
265A
| Cooling Indoor Model | Capacity | Power | Furnace Model | 
| *FX4CN(B,F)060 | 1.00 | 1.00 | 
 | 
| FE4ANB006 | 0.99 | 0.99 | 
 | 
| FV4BNB006 | 0.99 | 0.99 | 
 | 
| FY4ANB060 | 0.99 | 1.06 | 
 | 
| CAP**6021A** | 0.97 | 0.99 | 
 | 
| CAP**6024A** | 0.98 | 1.03 | 
 | 
| CNPH*6024A** | 0.98 | 1.03 | 
 | 
| CNPV*6024A** | 0.98 | 1.03 | 
 | 
| CSPH*6012A** | 0.98 | 1.02 | 
 | 
| Cooling Indoor Model | Capacity | Power | Furnace Model | 
| CAP**6021A** | 0.97 | 0.99 | 315(A,J)AV060110 | 
| CNPH*6024A** | 0.98 | 1.00 | 315(A,J)AV060110 | 
| CSPH*6012A** | 0.98 | 1.00 | 315(A,J)AV060110 | 
| CAP**6024A** | 0.98 | 1.00 | 315(A,J)AV066135 | 
| CNPH*6024A** | 0.98 | 1.00 | 315(A,J)AV066135 | 
| CNPV*6024A** | 0.98 | 1.00 | 315(A,J)AV066135 | 
| CSPH*6012A** | 0.98 | 1.00 | 315(A,J)AV066135 | 
| CAP**6024A** | 0.98 | 1.01 | 315(A,J)AV066155 | 
| CNPH*6024A** | 0.98 | 1.00 | 315(A,J)AV066155 | 
| CNPV*6024A** | 0.98 | 1.00 | 315(A,J)AV066155 | 
| CSPH*6012A** | 0.98 | 1.01 | 315(A,J)AV066155 | 
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
*Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 
{Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
}Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F (27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F (27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F (27_C).
** System kw is total of indoor and outdoor unit kilowatts.
{{At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb. EWB — Entering Wet Bulb
24
