PHYSICAL DATA
UNIT SIZE SERIES | |||||||
Operating Weight (lb) | 198 | 244 | 280 | 299 | 318 | 325 | 307 |
Shipping Weight (lb) | 232 | 280 | 310 | 335 | 354 | 361 | 344 |
Compressor Type |
|
|
| Scroll |
|
|
|
REFRIGERANT |
|
|
| Puron→ |
|
|
|
Control |
|
| TXV (Puron Hard Shutoff) |
|
| ||
Charge (lb) | 6.13 | 10.4 | 12 | 14.8 | 14.2 | 12.6 | 12.5 |
COND FAN |
|
| Propeller Type, Direct Drive |
|
| ||
Air Discharge |
|
|
| Vertical |
|
|
|
Air Qty (CFM) | 2595 | 2595 | 3265 | 3265 | 3265 | 3673 | 3673 |
Motor HP | 1/10 | 1/10 | 1/5 | 1/5 | 1/5 | 1/4 | 1/4 |
Motor RPM | 800 | 800 | 800 | 800 | 800 | 800 | 800 |
COND COIL |
|
|
|
|
|
|
|
Face Area (Sq ft) | 16.26 | 18.3 | 20.33 | 24.4 | 24.4 | 24.4 | 22.4 |
Fins per In. | 20 | 20 | 20 | 20 | 20 | 20 | 20 |
Rows | 1 | 1 | 1 | 2 | 2 | 2 | 2 |
Circuits | 4 | 5 | 6 | 5 | 7 | 8 | 9 |
VALVE CONNECT. (In. ID) |
|
|
|
|
|
|
|
Vapor | 5/8” | 5/8” | 3/4” | 3/4” | 7/8” | 7/8” | 7/8” |
Liquid |
|
|
| 3/8” |
|
|
|
REFRIGERANT TUBES* (In. OD) |
|
|
|
|
|
|
|
Vapor | 5/8” | 5/8” | 3/4” | 3/4” | 7/8” | 7/8” | |
Liquid |
|
|
| 3/8” |
|
|
|
*For tubing sets between 80 ft. and 200 ft. horizontal or 20 ft. vertical differential (250 ft. Total Equivalent Length), consult the
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
PURON
LONG LINE APPLICATION: An application is considered |
| is above indoor unit, and 80 ft. when the outdoor unit is below | |||||||||||||
”Long line” when the total equivalent tubing length exceeds 80 |
| the indoor unit. Refer to Accessory Usage Guideline below for | |||||||||||||
ft. or when there is more than 20 ft. vertical separation between |
| required accessories. See | |||||||||||||
indoor and outdoor units. These applications require additional | required piping and system modifications. Also, refer to the table | ||||||||||||||
accessories and system modifications for reliable system |
| below for the acceptable vapor tube diameters based on the total | |||||||||||||
operation. The maximum allowable total equivalent length is 250 |
| length to minimize the cooling capacity loss. |
|
| |||||||||||
ft. The maximum vertical separation is 200 ft. when outdoor unit |
|
|
|
|
|
|
|
|
|
| |||||
| Acceptable | Acceptable |
|
| Cooling Capacity Loss (%)Total Equivalent Line Length (ft.) |
|
| ||||||||
Unit Nominal | Liquid Line | Vapor Line |
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard Application |
|
| Long Line Application Requires Accessories |
| |||||||||||
Size (Btuh) | Diameter OD | Diameters |
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| (in.) | OD (in.) | 25 | 50 | 80 | 80+ | 100 | 125 | 150 | 175 | 200 |
| 225 | 250 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
18000 | 3/8 | 1/2 | 1 | 2 | 3 | 3 | 4 |
| 6 | 7 | 8 | 9 |
| 10 | 12 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
5/8 | 0 | 0 | 1 | 1 | 1 |
| 1 | 2 | 2 | 3 |
| 3 | 3 | ||
HP |
|
|
| ||||||||||||
24000 | 3/8 | 5/8 | 0 | 1 | 1 | 1 | 2 |
| 3 | 3 | 4 | 4 |
| 5 | 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
3/4 | 0 | 0 | 0 | 0 | 0 |
| 1 | 1 | 1 | 1 |
| 1 | 2 | ||
HP |
|
|
| ||||||||||||
30000 |
| 5/8 | 1 | 2 | 3 | 3 | 3 |
| 4 | 5 | 6 | 7 |
| 8 | 9 |
3/8 | 3/4 | 0 | 0 | 1 | 1 | 1 |
| 1 | 2 | 2 | 2 |
| 3 | 3 | |
HP |
| 7/8 | 0 | 0 | 0 | 0 | 0 |
| 1 | 1 | 1 | 1 |
| 1 | 1 |
|
|
|
| ||||||||||||
36000 |
| 5/8 | 1 | 2 | 4 | 4 | 5 |
| 6 | 7 | 9 | 10 |
| 11 | 13 |
3/8 | 3/4 | 0 | 0 | 1 | 1 | 1 |
| 2 | 2 | 3 | 3 |
| 4 | 4 | |
HP |
| 7/8 | 0 | 0 | 0 | 0 | 0 |
| 1 | 1 | 1 | 1 |
| 2 | 2 |
|
|
|
| ||||||||||||
42000 | 3/8 | 3/4 | 0 | 1 | 2 | 2 | 2 |
| 3 | 4 | 4 | 5 |
| 6 | 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
7/8 | 0 | 0 | 1 | 1 | 1 |
| 1 | 2 | 2 | 2 |
| 3 | 3 | ||
HP |
|
|
| ||||||||||||
48000 | 3/8 | 3/4 | 0 | 1 | 2 | 2 | 3 |
| 4 | 5 | 5 | 6 |
| 7 | 8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
7/8 | 0 | 0 | 1 | 1 | 1 |
| 2 | 2 | 2 | 3 |
| 3 | 4 | ||
HP |
|
|
| ||||||||||||
60000 |
| 3/4 | 1 | 2 | 4 | 4 | 5 |
| 6 | 7 | 9 | 10 |
| 11 | 12 |
3/8 | 7/8 | 0 | 1 | 2 | 2 | 2 |
| 3 | 4 | 4 | 5 |
| 5 | 6 | |
HP |
| 1 1/8 | 0 | 0 | 0 | 0 | 1 | 1 | 1 | 1 | 1 |
| 1 | 2 | |
|
|
|
Standard Length = 80 ft. or less total equivalent length
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See Long Line Application Guidelines
265A