ACCESSORY USAGE GUIDELINE
| 
 | 
 | 
 | 
 | |
| 
 | REQUIRED FOR  | REQUIRED FOR | REQUIRED FOR | |
| 
 | LONG LINE | SEA COAST | ||
| ACCESSORY | COOLING APPLICATIONS | |||
| APPLICATIONS* | APPLICATIONS | |||
| 
 | (Below 55° F) | |||
| 
 | (Over 80 Ft.) | (Within 2 miles) | ||
| 
 | 
 | |||
| Crankcase Heater | Yes | Yes | No | |
| Evaporator Freeze Thermostat | Yes | No | No | |
| Accumulator | Standard | Standard | Standard | |
| Compressor Start Assist Capacitor and Relay | Yes | Yes | No | |
| Motor Master→ Control or | Standard | Standard | Standard | |
| 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | |
| Support Feet | Recommended | No | Recommended | |
| Liquid Line Solenoid Valve | No | See  | No | |
| plication Guideline | ||||
| 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | |
| Ball Bearing Fan Motor | Standard | Standard | Standard | 
* For tubing line sets between 80 and 200 ft. and/or 20 ft. vertical differential (250 ft. Total Equivalent Length), refer to 
Accessory Description and Usage (Listed Alphabetically)
| 1.  | 6. Isolation Relay | 
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
Usage Guideline:
Required on all units when MotorMasterr is used.
2. Compressor Start Assist - Capacitor and Relay
Start capacitor and relay gives a ”hard” boost to compressor motor at each start up.
Usage Guideline:
Required for reciprocating compressors in the following applications:
Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil Liquid line solenoid on indoor coil
Required for 
Long line
Low ambient cooling
Suggested for all compressors in areas with a history of low voltage problems.
3. Compressor Start Assist — PTC Type
Solid state electrical device which gives a ”soft” boost to the compressor at each 
Usage Guideline:
Suggested in installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging.
Usage Guideline:
Required in low ambient cooling applications. Required in long line applications.
Suggested in all commercial applications.
5. Evaporator Freeze Thermostat
An SPST 
Usage Guideline:
Required when low ambient kit has been added.
An SPDT relay which switches the 
Usage Guideline:
Required in all heat pumps where low ambient kit has been added.
7. Liquid-Line  Solenoid Valve (LLS)
An electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation. It is to be installed at the outdoor unit to control refrigerant off cycle migration in the heating mode.
Usage Guideline:
An LLS is required in all long line heat pump applications to control refrigerant off cycle migration in the heating mode. See Long Line Guideline.
8. Low-Ambient  Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits. The control will maintain working head pressure at 
Usage Guideline:
A
9.MotorMasterr Low-Ambient  Controller
A
Usage Guideline:
A MotorMasterr Low Ambient Controller or 
Suggested for all commercial applications.
265A
5