Bryant 265A warranty Electrical Data, A-WEIGHTEDSOUND LEVEL dBA

Models: 265A

1 32
Download 32 pages 6.91 Kb
Page 7
Image 7
ELECTRICAL DATA

ELECTRICAL DATA

 

 

 

 

 

 

 

 

MIN

MIN

MAX

MAX

MAX

 

 

 

 

 

 

 

 

WIRE

WIRE

FUSE**

 

 

OPER VOLTS*

COMPR

FAN

 

LENGTH

LENGTH

UNIT SIZE

V/PH

MCA

SIZE

SIZE

or CKT

 

 

 

 

 

(FT)}

(FT)}

 

 

 

 

 

 

 

 

{

{

BRK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AMPS

 

 

MAX

MIN

LRA

RLA

FLA

 

60° C

75° C

60° C

75° C

018---B

 

 

 

48

9

0.7

12

14

14

66

62

20

024---B

 

 

 

58.3

12.8

0.7

16.7

14

14

46

44

25

030---B

 

 

 

73

14.1

1.1

18.7

14

14

41

39

30

036---B

208/230/1

253

197

79

17.9

1.1

23.4

12

12

55

52

35

042---B

 

 

 

109

21.3

1.1

27.7

10

10

71

68

40

048---B

 

 

 

117

21.8

1.3

28.5

10

10

69

66

40

060---B

 

 

 

134

26.4

1.3

34.3

8

10

91

56

50

* Permissible limits of the voltage range at which the unit will operate satisfactorily

{If wire is applied at ambient greater than 30° C (86° F), consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non ---metallic---sheathed cable (NM), trade name ROMEX, shall be that of 60° C (140° F) conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60

or 75° C (140 or 167° C) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

}Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%. ** Time---Delay fuse.

FLA

--- Full Load Amps

LRA

--- Locked Rotor Amps

MCA

--- Minimum Circuit Amps

RLA

--- Rated Load Amps

NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

A-WEIGHTED SOUND LEVEL (dBA)

UNIT SIZE

STANDARD

 

TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)

 

RATING

125

250

500

1000

2000

4000

8000

 

018---B

70

57

57

63

62.5

61

56.5

47.5

024---B

69

56.5

57.5

63.5

61.5

61.5

57

48.5

030---B

71

59.5

60

65

64.5

61.5

58

55.5

036---B

71

60

62

66

65

63

58

51.5

042---B

71

60.5

59.5

63

64

62

58.5

50.5

048---B

72

58.5

62.5

64.5

67

65

61

54.5

060---B

75

59

61

67

69.5

64

59

54.5

CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)

UNIT SIZE---SERIES

REQUIRED SUBCOOLING (F)

018---B

12

024---B

11

030---B

11

036---B

11

042---B

10

048---B

10

060---B

11

265A

7

Page 7
Image 7
Bryant 265A warranty Electrical Data, A-WEIGHTEDSOUND LEVEL dBA, Charging Subcooling Txv-Typeexpansion Device