ELECTRICAL DATA
|
|
|
|
|
|
|
| MIN | MIN | MAX | MAX | MAX | |
|
|
|
|
|
|
|
| WIRE | WIRE | FUSE** | |||
|
| OPER VOLTS* | COMPR | FAN |
| LENGTH | LENGTH | ||||||
UNIT SIZE | V/PH | MCA | SIZE | SIZE | or CKT | ||||||||
|
|
|
|
| (FT)} | (FT)} | |||||||
|
|
|
|
|
|
|
| { | { | BRK | |||
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| AMPS | |
|
| MAX | MIN | LRA | RLA | FLA |
| 60° C | 75° C | 60° C | 75° C | ||
|
|
| 48 | 9 | 0.7 | 12 | 14 | 14 | 66 | 62 | 20 | ||
|
|
| 58.3 | 12.8 | 0.7 | 16.7 | 14 | 14 | 46 | 44 | 25 | ||
|
|
| 73 | 14.1 | 1.1 | 18.7 | 14 | 14 | 41 | 39 | 30 | ||
208/230/1 | 253 | 197 | 79 | 17.9 | 1.1 | 23.4 | 12 | 12 | 55 | 52 | 35 | ||
|
|
| 109 | 21.3 | 1.1 | 27.7 | 10 | 10 | 71 | 68 | 40 | ||
|
|
| 117 | 21.8 | 1.3 | 28.5 | 10 | 10 | 69 | 66 | 40 | ||
|
|
| 134 | 26.4 | 1.3 | 34.3 | 8 | 10 | 91 | 56 | 50 |
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{If wire is applied at ambient greater than 30° C (86° F), consult table
or 75° C (140 or 167° C) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
}Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%. **
FLA | |
LRA | |
MCA | |
RLA |
NOTE: Control circuit is
A-WEIGHTED SOUND LEVEL (dBA)
UNIT SIZE | STANDARD |
| TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment) |
| |||||
RATING | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||
| |||||||||
70 | 57 | 57 | 63 | 62.5 | 61 | 56.5 | 47.5 | ||
69 | 56.5 | 57.5 | 63.5 | 61.5 | 61.5 | 57 | 48.5 | ||
71 | 59.5 | 60 | 65 | 64.5 | 61.5 | 58 | 55.5 | ||
71 | 60 | 62 | 66 | 65 | 63 | 58 | 51.5 | ||
71 | 60.5 | 59.5 | 63 | 64 | 62 | 58.5 | 50.5 | ||
72 | 58.5 | 62.5 | 64.5 | 67 | 65 | 61 | 54.5 | ||
75 | 59 | 61 | 67 | 69.5 | 64 | 59 | 54.5 |
CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)
UNIT | REQUIRED SUBCOOLING (F) |
12 | |
11 | |
11 | |
11 | |
10 | |
10 | |
11 |
265A