![](/images/new-backgrounds/1048002/4800213x1.webp)
5000 |
| |
4500 |
| |
4000 | LEAK IN | |
3500 | ||
SYSTEM | ||
3000 | ||
|
Connect Ground and Power Wires
Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 8.
DISCONNECT
PER N. E. C. AND/OR
LOCAL CODES
2500 |
|
|
|
|
|
|
|
MICRONS2000 |
|
|
|
|
| VACUUM TIGHT | |
1500 |
|
|
|
|
| ||
|
|
|
|
| TOO WET | ||
1000 |
|
|
|
|
| ||
|
|
|
|
| TIGHT | ||
500 |
|
|
|
|
| ||
|
|
|
|
| DRY SYSTEM | ||
|
|
|
|
|
| ||
0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 |
|
|
| MINUTES |
|
|
| |
|
|
|
|
|
|
| A95424 |
FIELD POWER
WIRING
FIELD GROUND
WIRING
CONTACTOR |
GROUND
LUG
A91056
Fig. 7 - Deep Vacuum Graph
Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
Step 8 — Make Electrical Connections
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not supply power to unit with compressor terminal box cover removed.
Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section
Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.
Fig. 8 - Line Power Connections
Connect Control Wiring
Connect to Evolution connections. Only two wires (AB) to Evolution capable indoor unit (furnace or fan coil) is required. Typical 4 wire (ABCD) may be connected (see Fig. 18).
IMPORTANT: This system requires the power supply to the outdoor unit, and the indoor unit, for the UI to communicate with the outdoor unit.
General Information
Use No. 18 AWG or larger
All wiring must be NEC Class 1 and must be separated from incoming power leads.
Use furnace transformer, fan coil transformer, or accessory transformer for control power requirement of system accessories external to the OD unit. The outdoor unit has its own transformer power.
Final Wiring Check
IMPORTANT: Check factory wiring and field wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.
Step 9 — Compressor Crankcase Heater
This compressor has an internal crankcase heater. Furnish power to the unit a minimum of 24 hr before starting the unit for the first time.
To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.
Power is not required to the indoor unit or User Interface for proper operation of heater. Crankcase heater will however be intelligently energized as needed between operations, and otherwise even when the UI and indoor unit is not installed, as long as there is power to the outdoor unit even if the indoor unit and UI are not yet installed.
Airflow Setup for Evolution Control Furnace or FE Fan Coil (communicating)
This system can only be installed with Evolution indoor and user interface (UI)
Due to using a communicating control with the fan coil or the furnace, dip switch adjustments are not necessary. The outdoor unit configuration and the indoor airflows are determined by communicating control setup.
7