Make Piping Connections
!WARNING
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
If ANY refrigerant tubing is buried, provide a 6 in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. (914.4 mm) may be buried without further special consideration. Do not bury lines longer than 36 in. (914.4 mm).
Outdoor units may be connected to indoor section using accessory tubing package or
Outdoor Unit Connected to Factory-Approved Indoor
Unit
Outdoor unit contains correct system refrigerant charge for operation with
NOTE: If the indoor furnace coil width is more than the furnace casing width, refer to the indoor coil Installation Instructions for transition requirements.
Table 1 – Refrigerant Connections and Recommended Liquid
and Vapor Tube Diameters (in.)
| LIQUID | RATED VAPOR* | |
UNIT SIZE | Connection | Connection | Tube |
| & Max. Tube | Diameter | Diameter |
| Diameter | ||
|
|
| |
024 | 3/8 | 3/4 | 3/4 |
036 | 3/8 | 7/8 | 7/8 |
048 | 3/8 | 7/8 | |
060 | 3/8 | 7/8 |
*Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length linesets.
Notes:
1.Do not apply capillary tube or fixed orifice indoor coils to these units.
2.For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 20 ft. (6.1 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length), refer to the Residential Piping and Longline Guide
286B / 289B
Table 2 – Accessory Usage
| REQUIRED FOR |
| REQUIRED FOR SEA | |
| REQUIRED FOR LONG LINE | |||
ACCESSORY | COAST APPLICATIONS | |||
APPLICATIONS | APPLICATIONS* | |||
| (Within 2 miles/3.22 km) | |||
| (Below 55°F/12.8_C) |
| ||
|
|
| ||
Compressor Start Assist | No | Yes | No | |
|
|
|
| |
Crankcase Heater | Standard | Standard | Standard | |
|
|
|
| |
Evaporator Freeze Protection | Standard with Evolutiont Control | No | No | |
(Low Ambient not allowed with non | ||||
| communicating thermostat) |
|
| |
No | Yes | No | ||
|
|
|
| |
Standard with Evolution Control | No | No | ||
(Low ambient not allowed with non | ||||
| communicating thermostat) |
|
| |
Puron Refrigerant Balance Port | Yes{ | Yes{ | Yes{ | |
|
|
| ||
Support Feet | Recommended | No | Recommended |
*For tubing set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 20 ft. (6.10 m) vertical differential (total equivalent length), refer to the Long Line
{Required on all indoor units. Standard on all new Puron refrigerant fan coils and furnace coils.
3