DETAILED COOLING CAPACITIES* Continued

EVAP

 

 

 

 

 

 

 

 

 

CONDENSER ENTERING AIR TEMPERATURES °F

 

 

 

 

 

 

 

 

AIR

 

 

75

 

 

 

85

 

 

 

95

 

 

 

105

 

 

 

 

115

 

 

 

 

125

 

 

 

 

 

 

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

 

Capacity

Total

 

Capacity

 

Total

 

 

 

 

MBtuh†

MBtuh†

MBtuh†

MBtuh†

 

MBtuh†

 

 

MBtuh†

 

 

 

 

 

Sys

Sys

Sys

Sys

 

Sys

 

 

 

Sys

CFM

 

EWB

 

Total

Sens‡

kW**

Total

 

Sens‡

kW**

Total

Sens‡

kW**

Total

 

Sens‡

kW**

 

Total

Sens‡

kW**

 

Total

Sens‡

 

kW**

 

 

 

 

 

552AN060-F Outdoor Section With CK5A/CK5BA060 Indoor Section

 

 

 

 

 

 

 

 

72

 

66.5

32.5

4.51

 

64.0

 

31.7

5.03

61.2

30.7

5.60

57.9

 

29.6

6.25

 

54.3

 

28.3

6.97

 

50.2

27.0

 

7.76

1600

 

67

 

62.4

41.9

4.44

 

59.6

 

40.8

4.95

56.4

39.5

5.50

53.0

 

38.2

6.13

 

49.5

 

36.9

6.83

 

43.3

34.5

 

7.53

 

63††

 

55.7

39.9

4.33

 

52.2

 

38.3

4.81

48.5

36.7

5.34

46.5

 

35.9

5.97

 

43.7

 

34.7

6.66

 

38.4

32.5

 

7.35

 

 

62

 

54.4

49.4

4.31

 

51.0

 

47.8

4.79

47.5

46.1

5.32

45.7

 

45.1

5.95

 

43.7

 

43.7

6.66

 

39.9

39.9

 

7.41

 

 

57

 

51.3

51.3

4.25

 

48.4

 

48.4

4.74

47.0

47.0

5.30

45.4

 

45.4

5.94

 

43.4

 

43.4

6.65

 

39.6

39.6

 

7.40

 

 

72

 

67.2

33.5

4.60

 

64.8

 

32.7

5.12

61.9

31.8

5.70

58.6

 

30.8

6.35

 

54.6

 

29.4

7.03

 

50.5

28.1

 

7.82

1800

 

67

 

62.9

43.6

4.52

 

60.1

 

42.6

5.02

57.0

41.5

5.59

53.7

 

40.3

6.22

 

50.1

 

39.1

6.92

 

44.0

36.7

 

7.64

 

63††

 

58.6

42.9

4.46

 

55.0

 

41.3

4.94

51.2

39.7

5.47

49.2

 

38.8

6.11

 

44.4

 

36.8

6.76

 

39.2

34.7

 

7.47

 

 

62

 

57.5

53.4

4.44

 

54.0

 

51.7

4.92

50.6

50.0

5.46

48.8

 

48.8

6.10

 

45.6

 

45.6

6.79

 

41.6

41.6

 

7.55

 

 

57

 

54.7

54.7

4.39

 

51.8

 

51.8

4.88

50.2

50.2

5.45

48.5

 

48.5

6.10

 

45.6

 

45.6

6.79

 

41.6

41.6

 

7.55

 

 

72

 

67.6

34.3

4.68

 

65.3

 

33.7

5.21

62.4

32.9

5.79

58.6

 

31.6

6.42

 

55.0

 

30.5

7.13

 

50.9

29.2

 

7.92

2000

 

67

 

63.6

45.4

4.61

 

60.7

 

44.5

5.12

57.6

43.5

5.68

54.3

 

42.4

6.32

 

50.7

 

41.2

7.02

 

44.4

38.8

 

7.74

 

63††

 

60.3

45.2

4.56

 

57.2

 

43.9

5.06

53.8

42.5

5.60

50.5

 

41.1

6.23

 

45.1

 

38.9

6.86

 

39.9

36.7

 

7.57

 

 

62

 

59.7

57.0

4.55

 

56.7

 

55.4

5.05

53.4

53.4

5.60

51.2

 

51.2

6.24

 

47.2

 

47.2

6.92

 

43.1

43.1

 

7.69

 

 

57

 

57.8

57.8

4.52

 

55.1

 

55.1

5.02

53.2

53.2

5.59

51.2

 

51.2

6.24

 

47.4

 

47.4

6.92

 

43.3

43.3

 

7.69

 

 

 

 

 

 

 

 

Multipliers for Determining the Performance With Other Indoor Sections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

 

 

 

Cooling

 

 

 

Indoor

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

Section

 

Size

 

Capacity

 

 

Power

 

Section

 

Size

 

Capacity

 

 

 

Power

 

CC5A/CD5AA

060

 

 

0.96

 

 

0.99

 

 

CK5PA

 

060

 

1.02

 

 

 

0.99

 

 

CC5A/CD5AW

060

 

 

1.02

 

 

1.02

 

 

CK5PT

 

060

 

1.02

 

 

 

0.99

 

 

 

 

CD5PX

 

060

 

 

1.03

 

 

1.02

 

 

CK5PX

 

060

 

1.02

 

 

 

0.97

 

 

 

 

CE3AA

 

060

 

 

1.00

 

 

1.00

 

 

COILS + 315(A,J)AV066135 VARIABLE SPEED FURNACE

 

 

 

CK3BA

 

060

 

 

1.00

 

 

1.00

 

CC5A/CD5AA

060

 

0.98

 

 

 

0.98

 

 

CK5A/CK5BA

060

 

 

1.00

 

 

1.00

 

CC5A/CD5AW

060

 

1.02

 

 

 

0.99

 

 

CK5A/CK5BT

060

 

 

1.00

 

 

1.00

 

 

CE3AA

 

060

 

1.02

 

 

 

0.98

 

 

CK5A/CK5BX

060

 

 

1.02

 

 

1.00

 

 

CK3BA

 

060

 

1.02

 

 

 

0.99

 

 

 

 

CK5PA

 

060

 

 

1.00

 

 

1.00

 

CK5A/CK5BA

060

 

1.02

 

 

 

0.99

 

 

 

 

CK5PT

 

060

 

 

1.00

 

 

1.00

 

CK5A/CK5BT

060

 

1.02

 

 

 

0.99

 

 

 

 

CK5PX

 

060

 

 

1.02

 

 

1.00

 

CK5A/CK5BX

060

 

1.02

 

 

 

0.97

 

 

F(A,B)4(A,B)N(F,B,C)

060

 

 

1.00

 

 

1.03

 

 

CK5PA

 

060

 

1.02

 

 

 

0.99

 

 

FB4(A,B)NB

070

 

 

1.02

 

 

1.01

 

 

CK5PT

 

060

 

1.02

 

 

 

0.99

 

 

FC4(B,C)N(F,B)

060

 

 

1.00

 

 

1.04

 

 

CK5PX

 

060

 

1.02

 

 

 

0.97

 

 

FC4(B,C)NB

070

 

 

1.02

 

 

1.02

 

 

COILS + 315(A,J)AV066155 VARIABLE SPEED FURNACE

 

 

FG3AAA

 

060

 

 

0.98

 

 

0.99

 

CC5A/CD5AA

060

 

0.98

 

 

 

0.97

 

 

FK4(C,D)NB

006

 

 

1.02

 

 

0.97

 

CC5A/CD5AW

 

 

 

 

060

 

 

 

1.00

 

 

FV4(A,B)NB

006

 

 

1.02

 

 

0.97

 

 

CD5PX

 

060

 

1.03

 

 

 

0.98

 

 

FX4(A,B)NB

060

 

 

0.98

 

 

0.99

 

 

CE3AA

 

060

 

1.02

 

 

 

0.97

 

 

 

 

COILS + 315(A,J)AV066110 VARIABLE SPEED FURNACE

 

 

CK3BA

 

060

 

1.02

 

 

 

0.98

 

 

CC5A/CD5AA

060

 

 

0.98

 

 

0.98

 

CK5A/CK5BA

060

 

1.02

 

 

 

0.98

 

 

 

 

CD5PX

 

060

 

 

1.03

 

 

0.99

 

CK5A/CK5BT

060

 

1.02

 

 

 

0.98

 

 

 

 

CE3AA

 

060

 

 

1.02

 

 

0.98

 

CK5A/CK5BX

060

 

1.02

 

 

 

0.97

 

 

 

 

CK3BA

 

060

 

 

1.02

 

 

0.99

 

 

CK5PA

 

060

 

1.02

 

 

 

0.98

 

 

CK5A/CK5BA

060

 

 

1.02

 

 

0.99

 

 

CK5PT

 

060

 

1.02

 

 

 

0.98

 

 

CK5A/CK5BT

060

 

 

1.02

 

 

0.99

 

 

CK5PX

 

060

 

1.02

 

 

 

0.97

 

 

CK5A/CK5BX

060

 

 

1.02

 

 

0.97

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.

*Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

Total and sensible capacities are net capacities. Blower motor heat has been subtracted.

Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh

(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80°F (27°C).

** Total unit kW is total of indoor and outdoor unit kilowatts.

††At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.

—32—

Page 32
Image 32
Bryant warranty 552AN060-F Outdoor Section With CK5A/CK5BA060 Indoor Section