Bryant 552A warranty Specifications, Unit Size-Series, 018-F, 024-F/G, 030-F, 036-F/G, Electrical

Models: 552A

1 36
Download 36 pages 60.78 Kb
Page 4
Image 4

SPECIFICATIONS

UNIT SIZE-SERIES

018-F

024-F/G

 

030-F

 

036-F/G

 

 

Operating Weight (Lb)

168

209

 

209

 

212

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL

 

 

 

 

 

 

 

Unit Volts—Hertz—Phase

 

208/230—60—1

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Voltage Range*

 

187—253

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor— Rated Load Amps

10.3

13.5/12.8

 

14.7

 

16.7/15.4

 

 

 

 

 

 

 

 

 

 

 

 

 

Locked Rotor Amps

51.0

61.0/60.0

 

72.5

 

87.5/83.0

 

 

 

 

 

 

 

 

 

 

 

Condenser Fan Motor—Full Load Amps

0.50

0.50/0.80

 

0.80

 

0.8

 

 

 

 

 

 

 

 

 

 

 

Min Unit Ampacity for Wire Sizing

13.4

17.4/16.8

 

19.2

 

21.7/20.1

 

 

 

 

 

 

 

 

 

 

 

Min Wire Size (60°C Copper) AWG†

14

14

 

14

 

12

 

 

 

 

 

 

 

 

 

 

 

Min Wire Size (75°C Copper) AWG†

14

14

 

14

 

12

 

 

 

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (60°C Copper)‡

61

45/46

 

41

 

57/62

 

 

 

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (75°C Copper)‡

58

43/44

 

39

 

54/59

 

 

 

 

 

 

 

 

 

 

 

Max Branch Circuit Fuse or

 

 

 

 

 

 

 

Circuit Breaker Size (Amps)

20

25

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR & REFRIGERANT

 

 

 

 

 

 

 

Compressor— Type

 

Scroll

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature & Current Protection

 

Internal Line Break

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant— Type

 

Puron® (R-410A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amount (Lb)

5.22

5.31/5.20

 

5.19

 

5.43

 

 

 

 

 

 

 

 

 

 

 

CONDENSER COIL & FAN

 

 

 

 

 

 

 

Coil Face Area (Sq Ft)

10.9

12.2/10.9

 

12.2

 

12.2

 

 

 

 

 

 

 

 

 

 

 

Fins per In.—Rows—Circuits

25—1—2

25—1—2

 

25—1—2

 

25—1—2

 

 

 

 

 

 

 

 

 

 

Fan Motor—HP (PSC) & RPM

1/12 & 1100

1/15 & 825/1/10 & 1100

 

1/8 & 825

 

1/8 & 825

 

 

 

 

 

 

 

 

 

 

 

Volts—Hertz—Phase

 

208/230—60—1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condenser Airflow (CFM)

1700

1800/2000

 

2400

 

2400

 

 

 

 

 

 

 

 

 

 

 

OPTIONAL EQUIPMENT

 

 

 

 

 

 

 

Support Feet

 

KSASF0101AAA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KAACF0801MED/

 

 

 

 

 

Coastal Filter

KAACF0701SML

KAACF0701SML

 

 

KAACF0801MED

Time Delay Relay

 

KAATD0101TDR

 

 

 

 

 

 

 

 

 

 

 

 

 

Cycle Protector

 

KSACY0101AAA

 

 

 

 

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

KAACH1201AAA

 

 

 

 

 

 

 

 

 

 

 

 

 

Start Assist—Capacitor/Relay Type

 

KSAHS1501AAA

 

 

 

 

 

 

 

 

 

 

 

 

 

Start Assist—PTC Type

 

KAACS0201PTC

 

 

 

 

 

 

 

 

 

 

 

 

 

TXV (Hard Shutoff)

 

KSATX0201PUR

 

 

KSATX0301PUR

 

 

 

 

 

 

 

 

 

Piston Body

 

KSAPX0101PIS

 

 

 

 

 

 

 

 

 

 

 

 

Filter Drier (Suction Line)

 

KH45LG140 (RCD)

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator Freeze Thermostat††

 

KAAFT0101AAA

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid-Line Solenoid Valve

 

KAALS0201LLS

 

 

 

 

 

 

 

 

 

 

 

 

 

Winter Start Control††

 

KAAWS0101AAA

 

 

 

 

 

 

 

 

 

 

 

 

 

Low-Ambient Pressure Switch

 

KSALA0301410

 

 

 

 

 

 

 

 

 

 

 

 

MotorMaster® Control**

 

32LT660004 (RCD)

 

 

 

 

 

 

 

 

 

 

 

Ball Bearing Fan Motor

HC34GE232

HC38GE231/HC34GE232

 

HC38GE231 (RCD)

 

 

 

 

 

 

 

 

 

 

Thermostat—Auto Changeover,

 

 

 

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

TSTATBBNAC01-B

 

 

 

 

Thermostat—Auto Changeover,

 

 

 

 

 

 

 

7-Day Programmable, °F/°C,

 

 

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

TSTATBBPAC01-B

 

 

 

 

Thermidistat™ Control—

 

 

 

 

 

 

 

Programmable Thermostat with Humidity Control

 

TSTATBBPRH01-B

 

 

 

 

Builder’s Thermostat—Manual Changeover,

 

 

 

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

TSTATBBBAC01-B

 

 

 

 

Outdoor Air Temperature Sensor

 

TSTATXXSEN01-B

 

 

 

 

 

 

 

 

 

 

 

 

 

Backplate for Non-Programmable Thermostat

 

TSTATXXNBP01

 

 

 

 

 

 

 

 

 

 

 

 

 

Backplate for Programmable Thermostat

 

TSTATXXPBP01

 

 

 

 

 

 

 

 

 

 

 

 

 

Backplate for Builder’s Thermostat

 

TSTATXXBBP01

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat Conversion Kit (4 to 5 wire)—10 Pack

 

TSTATXXCNV10

 

 

 

 

See notes on page 5.