CONDENSER ONLY RATINGS* Continued

SST

 

 

 

CONDENSER ENTERING AIR TEMPERATURES °F

 

 

 

 

 

 

 

 

 

 

 

°F

 

55

65

75

85

95

105

115

125

 

 

 

 

 

 

 

 

 

 

552AN048-F

 

TCG

43.2

40.8

38.5

36.2

33.8

31.4

28.9

26.2

30

SDT

77.6

87.0

96.5

106.

115.

125.

134.

143.

 

KW

2.18

2.48

2.82

3.20

3.61

4.08

4.58

5.14

 

 

 

 

 

 

 

 

 

 

 

TCG

47.2

44.7

42.2

39.6

37.0

34.4

31.6

28.7

35

SDT

79.4

88.7

98.2

108.

117.

126.

136.

145.

 

KW

2.23

2.53

2.86

3.25

3.66

4.12

4.63

5.19

 

 

 

 

 

 

 

 

 

 

 

TCG

51.5

48.8

46.0

43.3

40.4

37.6

34.5

31.3

40

SDT

81.4

90.6

99.9

109.

119.

128.

137.

146.

 

KW

2.28

2.58

2.92

3.30

3.72

4.18

4.68

5.23

 

 

 

 

 

 

 

 

 

 

 

TCG

56.0

53.1

50.1

47.1

44.0

40.9

37.6

34.0

45

SDT

83.5

92.6

102.

111.

120.

130.

139.

147.

 

KW

2.34

2.64

2.97

3.35

3.78

4.24

4.74

5.29

 

 

 

 

 

 

 

 

 

 

 

TCG

60.8

57.7

54.4

51.2

47.8

44.4

40.8

36.9

50

SDT

85.7

94.7

104.

113.

122.

131.

140.

149.

 

KW

2.40

2.70

3.04

3.42

3.84

4.30

4.80

5.34

 

 

 

 

 

 

 

 

 

 

 

TCG

65.8

62.5

59.1

55.5

51.8

48.0

44.2

39.9

55

SDT

88.1

96.9

106.

115.

124.

133.

142.

150.

 

KW

2.47

2.77

3.11

3.49

3.91

4.38

4.87

5.40

 

 

 

 

 

 

 

 

 

 

552AN060-F

 

TCG

53.4

50.5

47.6

44.7

41.8

38.8

35.7

32.5

30

SDT

77.9

87.5

97.1

107.

116.

126.

135.

144.

 

KW

2.79

3.18

3.61

4.10

4.64

5.23

5.88

6.60

 

 

 

 

 

 

 

 

 

 

 

TCG

58.4

55.2

52.1

48.9

45.7

42.5

39.1

35.5

35

SDT

79.8

89.2

98.8

108.

118.

127.

137.

146.

 

KW

2.85

3.24

3.67

4.16

4.71

5.30

5.95

6.66

 

 

 

 

 

 

 

 

 

 

 

TCG

63.7

60.3

56.9

53.4

49.9

46.4

42.7

38.7

40

SDT

81.8

91.1

101.

110.

120.

129.

138.

147.

 

KW

2.92

3.30

3.74

4.23

4.78

5.37

6.02

6.72

 

 

 

 

 

 

 

 

 

 

 

TCG

69.3

65.6

62.0

58.2

54.4

50.5

46.4

42.1

45

SDT

83.9

93.1

102.

112.

121.

131.

140.

149.

 

KW

2.99

3.37

3.81

4.30

4.85

5.45

6.10

6.80

 

 

 

 

 

 

 

 

 

 

 

TCG

75.2

71.3

67.3

63.3

59.1

54.8

50.4

45.6

50

SDT

86.1

95.3

105.

114.

123.

132.

141.

150.

 

KW

3.06

3.45

3.89

4.38

4.93

5.54

6.18

6.88

 

 

 

 

 

 

 

 

 

 

 

TCG

81.4

77.2

72.9

68.5

64.0

59.3

54.5

49.2

55

SDT

88.5

97.5

107.

116.

125.

134.

143.

152.

 

KW

3.15

3.54

3.98

4.47

5.02

5.63

6.28

6.96

 

 

 

 

 

 

 

 

 

 

*ARI listing applies only to systems shown in Ratings and Performance table. kW — Outdoor Unit Kilowatts only.

SDT — Saturated Temperature Leaving Compressor (°F) SST — Saturated Temperature Entering Compressor (°F) TCG — Gross Cooling Capacity (1000 Btuh).

SYSTEM DESIGN SUMMARY

1.Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.

2.Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C).

3.Maximum outdoor operating air temperature is 125°F (51.7°C).

4.For reliable operation, unit should be level in all horizontal planes.

5.Maximum elevation of indoor coil above or below base of outdoor unit without additional consideration is: Indoor coil above = 20 ft, indoor coil below = 20 ft. Consult Application Guidelines and Service Manual—Air Conditioners and Heat Pumps Using Puron® Refrigerant prior to application if elevations are exceeded.

6.For interconnecting refrigerant tube lengths greater than 50 ft and/or 20 ft vertical differential, consult the Application Guideline and Service Manual—Air Conditioners and Heat Pumps Using Puron® Refrigerant Application Guideline and Service Manual—Air Con- ditioners and Heat Pumps Using Puron® Refrigerant available from equipment distributor.

7.If any refrigerant tubing is buried, provide a 6 in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in. may be buried without further consideration. Do not bury lines over 36 in.

8.Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.

9.Do not apply capillary tube indoor coils to these units.

10.Factory-supplied filter drier must be installed. This must be replaced each time the refrigeration system is opened for service.

11.Do not deviate from factory specified TXV’s and Liquid Line Solenoids.

—35—

Page 35
Image 35
Bryant 552A warranty System Design Summary