558J
Table 12 – STATIC PRESSURE ADDERS (Factory Options and/or Accessories)
CFM | 600 | 800 | 1000 | 1250 | 1500 | 1750 | 2000 | 2250 | 2500 | 2750 | 3000 | |
Vertical Economizer | 0.01 | 0.02 | 0.035 | 0.045 | 0.065 | 0.08 | 0.12 | 0.145 | 0.175 | 0.22 | 0.255 | |
Horizontal Economizer | 0.1 | 0.125 | 0.15 | 0.18 | 0.225 | 0.275 | ||||||
CFM | 600 | 900 | 1200 | 1400 |
| 1600 | 1800 | 2000 | 2200 | 2400 | 2600 | |
1 | Electric Heater Module | 0.03 | 0.05 | 0.07 | 0.09 |
| 0.09 | 0.1 | 0.11 | 0.11 | 0.12 | 0.13 |
2 | Electric Heater Modules | 0.14 | 0.15 | 0.16 | 0.16 |
| 0.16 | 0.17 | 0.17 | 0.17 | 0.18 | 0.18 |
General fan performance notes:
1.Interpolation is permissible. Do not extrapolate.
2.External static pressure is the static pressure difference between the return duct and the supply duct plus the static pressure caused by any FIOPs or accessories.
3.Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories may add static pressure losses, as shown in Table 12. Selection software is available, through your salesperson, to help you select the best motor/drive combination for your application.
4.The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would work, Bryant recommended the lower horsepower option.
5.For information on the electrical properties of Bryant’s motors, please see the Electrical information section of this book.
6.For more information on the performance limits of Bryant’s motors, see the application data section of this book.
24