Bryant 558J manual 1494, Medium Static Option High Static Option, 1485, 1512, 1489

Models: 558J

1 55
Download 55 pages 58.4 Kb
Page 28
Image 28

558J

FAN PERFORMANCE (cont.)

Table 19 – 558J*05

3 PHASE

 

 

4 TON HORIZONTAL SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

 

 

 

CFM

 

0.2

 

0.4

 

0.6

0.8

 

 

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

Standard Static Option

 

 

Medium Static Option

 

 

1200

643

0.23

762

0.35

860

0.46

944

0.58

1020

0.71

1300

674

0.28

791

0.40

887

0.52

970

0.65

1045

0.78

1400

706

0.33

820

0.45

914

0.59

997

0.72

1071

0.86

1500

738

0.38

849

0.52

942

0.66

1024

0.80

1097

0.95

1600

771

0.44

 

 

971

0.74

1051

0.89

1124

1.04

879

0.59

1700

804

0.51

910

0.66

1000

0.82

1079

0.98

1151

1.14

1800

837

0.59

941

0.75

1029

0.91

1107

1.08

 

 

1178

1.25

1900

871

0.67

972

0.84

1059

1.02

1136

1.19

1206

1.37

2000

906

0.76

1004

0.94

1089

1.12

1165

1.31

1234

1.49

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

 

 

 

CFM

 

1.2

 

1.4

 

1.6

1.8

 

 

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

Medium Static Option

 

 

High Static Option

 

 

1200

1089

0.84

1153

0.98

1212

1.12

1269

1.26

1322

1.41

1300

1114

0.92

1177

1.06

1236

1.21

1292

1.36

1346

1.52

1400

1139

1.01

1202

1.15

1261

1.31

1316

1.47

1369

1.63

1500

1164

1.10

1227

1.25

1285

1.41

1341

1.58

1394

1.75

1600

1190

1.20

1252

1.36

1311

1.53

1366

1.70

1418

1.87

1700

1217

1.31

1278

1.48

1336

1.65

1391

1.83

1443

2.01

1800

1244

1.42

1305

1.60

1362

1.78

1416

1.97

1468

2.15

1900

1271

1.55

1331

1.73

1388

1.92

1442

2.11

 

 

1494

2.31

2000

1298

1.68

1358

1.87

1415

2.07

1468

2.27

---

---

 

 

 

 

 

 

 

 

 

 

 

NOTE: For more information, see General Fan Performance Notes on page 23. Boldface indicates field--- supplied drive is required.

1. Recommend using field--- supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY181 and belt (part no. KR30AE041).

Table 20 – 558J*05

3 PHASE

 

 

 

4 TON VERTICAL SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

 

 

 

CFM

 

0.2

 

0.4

0.6

 

0.8

 

 

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

Standard Static Option

 

 

 

Medium Static Option

 

 

1200

666

0.25

778

0.36

873

 

0.48

956

0.60

1031

0.72

1300

701

0.30

809

0.42

902

 

0.54

983

0.67

1057

0.80

1400

737

0.36

 

 

932

 

0.61

1012

0.75

1085

0.89

842

0.48

1500

774

0.42

875

0.55

962

 

0.69

1041

0.83

1112

0.98

1600

811

0.49

909

0.63

994

 

0.78

1071

0.93

1141

1.08

1700

849

0.57

943

0.72

1026

 

0.87

1101

1.03

 

 

1170

1.19

1800

887

0.65

978

0.81

1059

 

0.98

1133

1.14

1200

1.31

1900

926

0.75

1014

0.92

1092

 

1.09

1164

1.26

1231

1.44

2000

965

0.86

1050

1.03

1127

 

1.21

1197

1.39

1262

1.58

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

 

 

 

CFM

 

1.2

 

1.4

1.6

 

1.8

 

 

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

Medium Static Option

 

 

 

 

High Static Option

 

 

 

1200

1100

0.85

1165

0.98

1225

 

1.12

1282

1.26

1337

1.40

1300

1126

0.94

1189

1.07

1249

 

1.22

1306

1.36

1360

1.51

1400

1152

1.03

1215

1.17

1274

 

1.32

1330

1.48

1384

1.63

1500

 

 

1241

1.28

1300

 

1.44

1355

1.60

1408

1.76

1179

1.13

 

1600

1206

1.24

1268

1.40

1326

 

1.56

1381

1.73

1433

1.90

1700

1235

1.36

1295

1.52

1352

 

1.69

1407

1.87

1459

2.04

1800

1264

1.48

1323

1.66

1380

 

1.84

1434

2.02

 

 

 

1485

2.20

1900

1293

1.62

1352

1.80

1408

 

1.99

1461

2.17

1512

2.37

2000

1324

1.77

1381

1.96

1436

 

2.15

 

 

---

---

 

1489

2.34

NOTE: For more information, see General Fan Performance Notes on page 23. Boldface indicates field--- supplied drive is required.

1. Recommend using field--- supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY181 and belt (part no. KR30AE041).

28

Page 28
Image 28
Bryant 558J manual 1494, Medium Static Option High Static Option, 1485, 1512, 1489