8
Table2 – ARI COOLING RATING TABLES
UNIT
NOM.
CAPACITY
(TONS)
NETCOOLING
CAPACITY
(KBTU/ H R)
TOTAL
POWER(KW) SEER EER IPLV IEER
04 334.6 3.1 13.0 11.0 N/A N/A
05 445.0 4.0 13.0 11.0 N/A N/A
06 559.0 5.5 13.0 10.8 N/A N/A
07 670.0 6.4 N/A 11.0 N/A 11.4
LEGEND
ARI --- Air---Conditioning& Refrigeration Institute
ASHRAE --- American Society of Heating, Refrigerating
andA ir Conditioning,Inc.
EER --- Energy Efficiency Ratio
IEER --- IntegratedEnergy Efficiency Ratio
SEER --- SeasonalEnergy Efficiency Ratio
IPLV --- IntegratedPartLoad Value
Thisproduct h as been designed and manufactu red to
meetEnergy Star®cri teria for energyeff iciency.
However,proper refrigeran t charge and proper air flow
arecritical to achieve rated capacity and efficiency.
Installationofthis product shouldfollow all
manufacturer’srefrigerantcharging and air flow
instructions.Failureto confirm proper charge and
airflow may reduce energy efficien cy and shorten
equipmentlife.
NOTES
1. Rated and certified under ARI Standard 210/240 ---06or
360/360---04,as appropriate.
2. Ratings are based on:
Cooling Standard: 80_F(27_C) db, 67_F(19_C) wb
indoor air temp and 95_F(35_C)db outd oor air temp.
IPLVSt andard:80_F(27_C)db, 67_F(19_C)wb indoor
air temp and 80_F(27_C)db outdoor air temp .
IEER Standard: Procedure described in ARI Standard
340/360.
3. All 558J units comply with ASHRAE 90.1 2001, 2004
Energy Standard for minimum SEER and EER
requirements.
4. Where appropriate, 558J units comply with US Energy
Policy Act (2005). Refer to state and local codes orv isit
the following website: http://bcap---energy. org to
determine if compliance with this standard pertains to
your state, territory,or mun icipality.
558J