III. STEP 3 Ð FIELD FABRICATE DUCTWORK

Secure all ducts to building structure. Use ¯exible duct con- nectors between unit and ducts as required. Insulate and weath- erproof all external ductwork, joints, and roof openings with counter ¯ashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be in- sulated and covered with a vapor barrier.

The 559F units with electric heat require a 1-in. clearance for the ®rst 24 in. of ductwork.

Outlet grilles must not lie directly below unit discharge.

NOTE: A 90-degree elbow must be provided in the ductwork to comply with UL (Underwriters' Laboratories) codes for use with electric heat.

WARNING: For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install a 90 degree turn in the return ductwork be- tween the unit and the conditioned space. If a 90 de- gree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent ob- jects from falling into the conditioned space. Due to elec- tric heater, supply duct will require 90 degree elbow.

NOTE: Do not drill in this area, as damage to basepan may result in water leak.

Fig. 6 Ð Air Distribution Ð Thru-the-Bottom

(559F216-300 Shown)

NOTE: Do not drill in this area, as damage to basepan may result in water leak.

Fig. 7 Ð Concentric Duct Air Distribution

(559F216-300 Shown)

IV. STEP 4 Ð MAKE UNIT DUCT CONNECTIONS

Unit is shipped for thru-the-bottom duct connections. Duct- work openings are shown in Fig. 6. Field-fabricated concen- tric ductwork may be connected as shown in Fig. 7 and 8. Attach all ductwork to roof curb and roof curb basepans. Re- fer to installation instructions shipped with accessory roof curb for more information.

V. STEP 5 Ð TRAP CONDENSATE DRAIN

See Fig. 4, 5, and 9 for drain location. Plug is provided in drain hole and must be removed when unit is operating. One 3¤4-in. half coupling is provided inside unit evaporator section for condensate drain connection. An 81¤2 in. x 3¤4-in. diameter nipple and a 2-in. x 3¤4-in. diameter pipe nipple are coupled to standard 3¤4-in. diameter elbows to provide a straight path down through holes in unit base rails (see Fig. 10). A trap at least 4-in. deep must be used.

Shaded area indicates block-off panels.

NOTE: Dimension A, A and B, B are obtained from ®eld-supplied ceil- ing diffuser.

Fig. 8 Ð Concentric Duct Details

3/4" FPT DRAIN

1-3/8"

CONNECTION

DRAIN HOLES

Fig. 9 Ð Condensate Drain Details

(559F180,216 Shown)

Ð7Ð

Page 7
Image 7
Bryant 559F operation manual III. Ð Field Fabricate Ductwork, IV. Ð Make Unit Duct Connections, Trap Condensate Drain

559F specifications

The Bryant 559F is a standout heating and cooling solution, designed with both efficiency and performance in mind. This model is a part of Bryant's legacy of reliability, combining innovative technology with user-friendly features to ensure a comfortable indoor environment throughout the year.

One of the most notable features of the Bryant 559F is its high efficiency rating. With a Seasonal Energy Efficiency Ratio (SEER) that exceeds industry standards, this model is engineered to significantly reduce energy consumption, translating to lower utility bills and a smaller carbon footprint. The system is designed to perform efficiently even in extreme temperatures, making it a reliable choice for households in diverse climates.

Incorporating advanced inverter technology, the Bryant 559F automatically adjusts its output to meet the precise cooling and heating needs of the space, providing consistent comfort while minimizing energy usage. This adaptive capability reduces energy waste, resulting in more efficient operation compared to traditional systems that constantly cycle on and off.

The Bryant 559F also features an integrated Wi-Fi capability, allowing users to control their heating and cooling system remotely via a smartphone app. This modern convenience empowers homeowners to create schedules, adjust settings, and monitor performance from virtually anywhere, enhancing both comfort and energy management.

Another characteristic of the Bryant 559F is its quiet operation. Thanks to sound-dampening features, the system is designed to operate at lower noise levels, providing a peaceful indoor environment. This makes it particularly suitable for residential applications where noise can be a concern, such as bedrooms and home offices.

Additionally, the Bryant 559F is equipped with advanced air filtration and purification systems that help improve indoor air quality. This is particularly beneficial for allergy sufferers or those concerned about pollutants in the air. The system can remove dust, pollen, and other particulates, creating a healthier living space.

Furthermore, the Bryant 559F model is backed by a robust warranty, showcasing Bryant's commitment to quality and customer satisfaction. Overall, the Bryant 559F combines innovative technology, energy efficiency, and user-friendly features to deliver a reliable heating and cooling solution that meets the needs of modern households. Its blend of performance, comfort, and convenience makes it an excellent choice for anyone looking to enhance their indoor climate control solutions.