Table 33 — Heating Service Analysis

PROBLEM

CAUSE

REMEDY

Burners Will Not

Misaligned spark electrodes.

Check flame ignition and sensor electrode positioning. Adjust as needed.

Ignite

 

 

No gas at main burners.

Check gas line for air purge as necessary. After purging gas line of

 

 

 

air, allow gas to dissipate for at least 5 minutes before attempting

 

 

to relight unit.

 

 

Check gas valve.

 

Water in gas line.

Drain water and install drip leg to trap water.

 

No power to unit.

Check power supply, fuses, wiring, and circuit breaker.

 

No 24 v power supply to control circuit.

Check transformer. Transformers with internal overcurrent protection

 

 

require a cool-down period before resetting. Check 24-v circuit breaker;

 

 

reset if necessary.

 

Miswired or loose connections.

Check all wiring and wirenut connections.

 

Burned-out heat anticipator in thermostat.

Replace thermostat.

 

Broken thermostat wires.

Run continuity check. Replace wires, if necessary.

Inadequate Heating

Dirty air filter.

Clean or replace filter as necessary.

 

Gas input to unit too low.

Check gas pressure at manifold. Clock gas meter for input. If too low,

 

 

increase manifold pressure or replace with correct orifices.

 

Unit undersized for application.

Replace with proper unit or add additional unit.

 

Restricted airflow.

Clean filter, replace filter, or remove any restrictions.

 

Blower speed too low.

Use high speed tap, increase fan speed, or install optional blower, as suit-

 

 

able for individual units, Adjust pulley.

 

Limit switch cycles main burners.

Check rotation of blower, thermostat heat anticipator settings,

 

 

and temperature rise of unit. Adjust as needed.

 

Too much outdoor air.

Adjust minimum position.

 

 

Check economizer operation.

Poor Flame

Incomplete combustion (lack of

Check all screws around flue outlets and burner compartment.

Characteristics

combustion air) results in:

Tighten as necessary.

 

Aldehyde odors, CO (carbon monoxide),

Cracked heat exchanger. Replace heat exchanger.

 

sooting flame, or floating flame.

 

 

Overfired unit — reduce input, change orifices, or adjust gas line or mani-

 

 

 

 

fold pressure.

 

 

Check vent for restriction. Clean as necessary.

 

 

Check orifice to burner alignment.

Burners Will Not

Unit is locked into Heating mode for a

Wait until mandatory one-minute time period has elapsed or reset power to

Turn Off

one minute minimum.

unit.

Table 34 — Perfect Humidity™ Adaptive Dehumidification System Subcooling Mode Service Analysis

PROBLEM

CAUSE

 

REMEDY

Subcooling Mode (Liquid Reheat)

No power to control transformer from

Check power source and evaporator-fan relay. Ensure all

Will Not Energize.

evaporator-fan motor.

wire connections are tight.

 

No power from control transformer to liquid line

1.

Fuse open; check fuse. Ensure continuity of wiring.

 

solenoid valve.

2.

Low-pressure switch open. Cycle unit off and allow low-

 

 

 

pressure switch to reset. Replace switch if it will not

 

 

 

close.

 

 

3. Transformer bad; check transformer.

 

Liquid line solenoid valve will not operate.

1.

Solenoid coil defective; replace.

 

 

2.

Solenoid valve stuck open; replace.

 

Liquid line solenoid valve will not open.

Valve is stuck closed; replace valve.

Low System Capacity.

Low refrigerant charge or frosted evaporator coil.

1.

Check charge amount. Charge per Fig. 52-55.

 

 

2.

Evaporator coil frosted; check and replace low-

 

 

 

pressure switch if necessary.

Loss of Compressor Superheat

Thermostatic expansion valve (TXV).

1.

Check TXV bulb mounting, and secure tightly to suction

Conditions with Subcooling/Reheat

 

 

line.

Dehumidification Coil Energized.

 

2.

Replace TXV if stuck open or closed.

Table 35 — Perfect Humidity Dehumidification System Hot Gas Reheat Mode Service Analysis

PROBLEM

CAUSE

 

REMEDY

Reheat Mode Will Not Energize.

No power to control transformer from

Check power source and evaporator-fan relay. Ensure all

 

evaporator-fan motor.

wire connections are tight.

 

No power from control transformer to hot gas

1.

Fuse open; check fuse. Ensure continuity of wiring.

 

line solenoid valve.

2.

Low-pressure switch open. Cycle unit off and allow low-

 

 

 

pressure switch to reset. Replace switch if it will not

 

 

 

close.

 

 

3. Transformer bad; check transformer.

 

Hot gas line solenoid valve will not operate.

1.

Solenoid coil defective; replace.

 

 

2.

Solenoid valve stuck closed; replace.

 

Low refrigerant charge or frosted evaporator coil.

1.

Check charge amount. Charge per Fig. 52-55.

 

 

2.

Evaporator coil frosted; check and replace low-

 

 

 

pressure switch if necessary.

Loss of Compressor Superheat

Thermostatic expansion valve (TXV).

1.

Check TXV bulb mounting, and secure tightly to suction

Conditions with Subcooling/Reheat

 

 

line.

Dehumidification Coil Energized.

 

2.

Replace TXV if stuck open or closed.

Excessive Superheat.

Liquid line solenoid valve will not operate.

Valve is stuck; replace valve.

 

Hot gas line solenoid valve will not close.

Valve is stuck; replace valve.

46

Page 46
Image 46
Bryant 581B installation instructions Heating Service Analysis, Problem Cause Remedy

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.