Bryant 581B RLA LRA FLA MCA Mocp, FAN Motor Disconnect SIZE†, With Outlet, Nec, Rla

Models: 581B

1 52
Download 52 pages 16.87 Kb
Page 11
Image 11

Table 2A — Electrical Data — Standard Motor Units Without Electrical Convenience Outlet

UNIT

 

NOMINAL VOLTAGE

VOLTAGE

COMPRESSOR

OFM

IFM

COMBUSTION

POWER

MINIMUM UNIT

 

RANGE

 

(each)

 

(each)

FAN MOTOR

SUPPLY*

DISCONNECT SIZE†

581B

 

(V-Ph-Hz)

 

 

 

 

Min

Max

Qty

RLA

LRA

FLA

FLA

FLA

MCA

MOCP**

FLA

LRA

 

 

 

 

208/230-1-60

187

254

 

16.0

88.0

0.7

4.9

.60

25.6/25.6

30/30

25/25

101/101

036

208/230-3-60

187

254

1

10.3

77.0

0.7

4.9

.60

18.5/18.5

25/25

18/18

90/90

(3 Tons)

460-3-60

414

508

5.1

39.0

0.4

2.2

.30

9.0

20

9

46

 

 

575-3-60

518

632

 

4.2

31.0

0.4

2.2

.30

7.3

20

7

37

048

 

208/230-1-60

187

254

 

23.7

126.0

0.7

4.9

.60

35.2/35.2

45/45

34/34

139/139

208/230-3-60

187

254

1

13.5

93.0

0.7

4.9

.60

22.5/22.5

30/30

22/22

106/106

(4 Tons)

460-3-60

414

508

6.4

46.5

0.4

2.2

.30

10.6

20

10

54

 

 

575-3-60

518

632

 

6.4

40.0

0.4

2.2

.30

10.1

20

10

46

060

 

208/230-1-60

187

254

 

28.8

169.0

1.5

8.8

.60

46.3/46.3

60/60

45/45

216/216

208/230-3-60

187

254

1

17.3

123.0

1.5

5.8

.60

28.9/28.9

35/35

28/28

168/168

(5 Tons)

460-3-60

414

508

9.0

62.0

0.8

2.6

.30

14.7

20

14

84

 

 

575-3-60

518

632

 

7.1

50.0

0.8

2.6

.30

11.6

20

12

68

072

 

208/230-3-60

187

254

 

20.5

156.0

1.4

5.8

.60

32.8/32.8

40/40

32/32

200/200

460-3-60

414

508

1

9.6

75.0

0.6

2.6

.30

15.2

20

15

97

(6 Tons)

575-3-60

518

632

 

7.7

56.0

0.6

2.6

.30

12.2

20

12

74

 

 

Table 2B — Electrical Data — Standard Motor Units With Electrical Convenience Outlet

 

 

VOLTAGE

COMPRESSOR

OFM

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

NOMINAL VOLTAGE

IFM

SUPPLY

RANGE

 

(each)

 

(each)

FAN MOTOR

DISCONNECT SIZE†

581B

(V-Ph-Hz)

 

 

 

WITH OUTLET*

 

 

 

 

 

 

 

 

 

 

 

 

Min

Max

Qty

RLA

LRA

FLA

FLA

FLA

MCA

MOCP**

FLA

LRA

 

208/230-1-60

187

254

 

16.0

88.0

0.7

4.9

.60

31.6/31.6

35/35

30/30

106/106

036

208/230-3-60

187

254

1

10.3

77.0

0.7

4.9

.60

24.5/24.5

30/30

24/24

95/95

(3 Tons)

460-3-60

414

508

5.1

39.0

0.4

2.2

.30

11.7

20

11

48

 

 

575-3-60

518

632

 

4.2

31.0

0.4

2.2

.30

9.5

20

9

38

 

208/230-1-60

187

254

 

23.7

126.0

0.7

4.9

.60

41.2/41.2

50/50

39/39

144/144

048

208/230-3-60

187

254

1

13.5

93.0

0.7

4.9

.60

28.5/28.5

35/35

27/27

111/111

(4 Tons)

460-3-60

414

508

6.4

46.5

0.4

2.2

.30

13.3

20

13

56

 

 

575-3-60

518

632

 

6.4

40.0

0.4

2.2

.30

12.2

20

12

47

 

208/230-1-60

187

254

 

28.8

169.0

1.5

8.8

.60

52.3/52.3

60/60

50/50

221/221

060

208/230-3-60

187

254

1

17.3

123.0

1.5

5.8

.60

34.9/34.9

40/40

34/34

173/173

(5 Tons)

460-3-60

414

508

9.0

62.0

0.8

2.6

.30

17.4

20

17

87

 

 

575-3-60

518

632

 

7.1

50.0

0.8

2.6

.30

13.8

20

13

70

072

208/230-3-60

187

254

 

20.5

156.0

1.4

5.8

.60

38.8/38.8

45/45

37/37

205/205

460-3-60

414

508

1

9.6

75.0

0.6

2.6

.30

17.9

20

17

99

(6 Tons)

575-3-60

518

632

 

7.7

56.0

0.6

2.6

.30

14.3

20

14

75

 

 

 

LEGEND

FLA

Full Load Amps

HACR — Heating, Air Conditioning and

 

Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP

Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

UL

Underwriters’ Laboratories

*The values listed in this table do not include power exhaust. See table at right for power exhaust requirements.

†Used to determine minimum disconnect per NEC. **Fuse or HACR circuit breaker.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The UL, Canada units may be fuse or circuit breaker.

2.Electrical data based on 95 F ambient outdoor-air temperature ± 10% voltage.

3.Unbalanced 3-Phase Supply Voltage

Never operate a motor where phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent voltage imbalance.

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3 = 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

POWER EXHAUST ELECTRICAL DATA

POWER EXHAUST

MCA

MCA

MCA

MOCP

(for separate

PART NO.

(230 v)

(460 v)

(575 v)

power source)

 

 

 

 

CRPWREXH021A01

N/A

0.9

N/A

15

CRPWREXH022A01

3.3

N/A

1.32

15

CRPWREXH023A01

N/A

1.8

N/A

15

CRPWREXH028A01

1.7

N/A

0.68

15

CRPWREXH029A01

N/A

1.0

N/A

15

CRPWREXH030A01

1.6

N/A

0.64

15

N/A — Not available

NOTE: If a single power source is to be used, size wire to include power exhaust MCA and MOCP.

Check MCA and MOCP when power exhaust is powered through the unit. Deter- mine the new MCA including the power exhaust using the following formula:

MCA New = MCA unit only + MCA of Power Exhaust

For example, using a 581B072 unit with MCA = 32.8 and MOCP = 40, with CRPWREXH030A01 power exhaust.

MCA New = 32.8 amps + 1.6 amps = 34.4 amps

If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 40 amps and the MCA New is below 40; therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

11

Page 11
Image 11
Bryant 581B RLA LRA FLA MCA Mocp, FAN Motor Disconnect SIZE†, With Outlet, Nec, Rla, Power Exhaust MCA Mocp

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.