PERFORMANCE DATA (cont)

HIGH ALTITUDE COMPENSATION

NATURAL GAS ONLY

ORIFICE CONVERSION Ð 3.5 in. wg MANIFOLD PRESSURE*

ALTITUDE (ft)

INPUT

OUTPUT

ORIFICE

(Btuh)

(Btuh)

NUMBER²

 

 

40,000

32,040

#44

 

60,000

47,040

#38

0-2000

90,000

71,910

#38

 

115,000

93,265

#33

 

130,000

104,390

#31

 

33,290

27,130

#49

 

49,930

40,690

#43

2001-4500

74,900

61,040

#43

 

95,700

78,000

#38

 

108,180

88,170

#36

 

31,310

25,520

#50

 

46,970

38,280

#44

4501-6000

70,450

57,420

#44

 

90,020

73,370

#40

 

101,760

82,930

#37

 

 

 

 

*As the height above sea level increases, there is less oxygen per cubic ft of air. Therefore heat input rate should be reduced at higher altitudes.

²Ori®ces available through your distributor.

LIQUID PROPANE ONLY

ORIFICE CONVERSION Ð 3.5 in. wg MANIFOLD PRESSURE*

ALTITUDE (ft)

INPUT

OUTPUT

ORIFICE

(Btuh)

(Btuh)

NUMBER²

 

 

40,000

33,200

#50

 

57,000

47,310

#46

0-2000

85,500

70,965

#46

 

115,000

95,450

#42

 

127,000

105,410

#41

 

33,290

27,630

#53

 

47,430

39,370

#50

2001-4500

71,150

59,050

#50

 

95,700

79,430

#45

 

105,690

87,720

#44

 

31,310

25,990

NOT TO BE USED

 

ABOVE 4500 FT

 

 

 

4501-6000

44,620

37,030

#51

66,930

55,550

#51

 

 

90,020

74,720

#47

 

99,140

82,510

#45

 

 

 

 

*As the height above sea level increases, there is less oxygen per cubic ft of air. Therefore, heat input rate should be reduced at higher altitudes.