PERFORMANCE DATA (cont)

NET COOLING CAPACITIES (cont)

 

583A--048

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

Evaporator Air Ð Cfm/BF

 

 

 

 

 

 

 

 

1400/0.050

 

 

1600/0.085

 

 

1800/0.119

 

 

 

Air Ent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator Air Ð Ewb (F)

 

 

 

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

62

 

67

72

62

67

72

62

67

72

 

 

 

TC

 

45.2

 

49.7

54.7

46.4

50.9

56.0

47.5

51.9

57.1

 

85

 

SHC

 

41.4

 

34.6

27.6

44.6

37.2

29.2

47.5

39.6

30.8

 

 

 

kW

 

4.04

 

4.08

4.12

4.05

4.09

4.13

4.06

4.10

4.14

 

 

 

TC

 

43.5

 

47.8

52.5

44.6

48.0

53.7

45.7

49.8

54.6

 

95

 

SHC

 

40.4

 

33.7

26.7

43.4

34.9

28.3

45.7

38.6

29.8

 

 

 

kW

 

4.45

 

4.50

4.55

4.46

4.62

4.56

4.47

4.53

4.58

 

 

 

TC

 

41.3

 

45.4

49.8

42.3

46.4

50.9

43.4

47.2

51.7

 

105

 

SHC

 

39.0

 

32.5

25.6

41.6

34.9

27.1

43.4

37.2

28.6

 

 

 

kW

 

4.91

 

4.95

5.00

4.93

4.97

5.02

4.93

4.98

5.03

 

 

 

TC

 

37.6

 

42.4

46.4

39.0

43.3

47.5

40.6

44.0

48.3

 

115

 

SHC

 

35.4

 

30.9

24.1

38.3

32.9

25.6

40.6

35.0

27.0

 

 

 

kW

 

5.39

 

5.46

5.51

5.41

5.48

5.43

5.44

5.49

5.55

 

 

 

TC

 

33.9

 

36.1

42.5

35.8

37.8

43.4

37.4

38.8

44.1

 

125

 

SHC

 

27.8

 

25.5

22.1

33.7

28.0

23.4

37.4

30.1

24.6

 

 

 

kW

 

6.30

 

5.94

6.05

6.18

5.97

6.06

6.15

5.98

6.08

 

 

 

 

 

 

 

 

 

 

 

 

 

583A--060

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

Evaporator Air Ð Cfm/BF

 

 

 

 

 

 

 

 

1750/0.082

 

 

2000/0.130

 

 

2250/0.162

 

 

 

Air Ent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator Air Ð Ewb (F)

 

 

 

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

62

 

67

72

62

67

72

62

67

72

 

 

 

TC

 

55.2

 

60.9

66.4

56.1

61.5

66.4

56.6

61.6

66.9

 

85

 

SHC

 

49.9

 

42.1

33.8

53.2

44.3

33.9

55.9

46.3

35.3

 

 

 

kW

 

4.92

 

4.97

5.00

5.14

5.23

5.28

5.41

5.55

5.59

 

 

 

TC

 

52.2

 

58.0

63.7

53.2

58.5

64.1

53.9

58.4

64.0

 

95

 

SHC

 

48.2

 

41.0

32.7

51.8

43.2

33.6

53.9

44.8

34.2

 

 

 

kW

 

5.39

 

5.57

5.50

5.64

5.75

5.77

5.90

6.03

6.09

 

 

 

TC

 

49.1

 

54.4

60.4

49.9

54.9

60.7

50.9

55.0

60.5

 

105

 

SHC

 

47.3

 

39.4

31.5

49.9

41.6

32.4

50.9

43.5

33.0

 

 

 

kW

 

5.87

 

5.98

6.02

6.13

6.22

6.30

6.34

6.57

6.62

 

 

 

TC

 

45.9

 

50.2

55.2

46.8

50.3

55.5

47.3

50.2

55.3

 

115

 

SHC

 

45.3

 

37.4

29.4

46.8

39.4

29.8

47.3

41.0

30.8

 

 

 

kW

 

6.39

 

6.48

6.54

6.57

6.75

6.81

6.85

7.07

7.14

 

 

 

TC

 

42.5

 

46.5

50.6

43.7

46.9

50.6

44.9

46.2

50.2

 

125

 

SHC

 

42.5

 

36.1

27.3

43.7

38.4

28.2

44.9

39.5

28.6

 

 

 

kW

 

7.03

 

7.13

7.13

7.22

7.38

7.40

7.51

7.67

7.72

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

BF

Ð Bypass Factor

 

 

 

 

 

 

 

 

 

 

Ewb

Ð Entering Wet-Bulb

 

 

 

 

 

 

 

 

 

 

kW

Ð Total Unit Power Input

 

 

 

 

 

 

 

 

SHC Ð Sensible Heat Capacity (1000 Btuh)

 

 

 

 

 

 

 

TC

Ð Total Capacity (1000 Btuh) (net)

 

 

 

 

 

 

 

 

NOTES:

1.Ratings are net; they account for the effects of the evaporator-fan motor power and heat.

2.Direct interpolation is permissible. Do not extrapolate.

3.The following formulas may be used:

t ldb = t edb

sensible capacity (Btuh)

1.10 x cfm

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)

hlwb = hewb

total capacity (Btuh)

4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

4.The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.

Correction Factor = 1.10 x (1 − BF) x (edb − 80).

14

Page 14
Image 14
Bryant manual 583A--048