MATCHED SYSTEM
A98599
System Design
1.Intended for outdoor installation with
2.Minimum outdoor operating air temperature is 55°F (12.8°C).
3.
4.Maximum outdoor operating air temperature is 125°F (51.7°C).
5.For reliable operation, unit should be level in all horizontal planes.
6.Maximum elevation of indoor coil above or below base of outdoor unit is; Indoor coil above = 50 ft, indoor coil below = 150 ft.
7.For interconnecting refrigerant tube lengths greater than 50 ft, consult Application Guideline and Service
8.If any refrigerant tubing is buried, provide a minimum
9.Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
10.Use with hard
11.Do not apply capillary tube indoor coils to these units
12.Factory supplied filter drier must be installed.