Bryant 598B warranty Specifications, 024-A, 036-A, 048-A, 060-A,B

Models: 598B

1 40
Download 40 pages 2.5 Kb
Page 4
Image 4
SPECIFICATIONS
Coastal installations.
Windy areas or where debris is normally circulating. Rooftop installations.

SPECIFICATIONS

 

UNIT SIZE-SERIES

024-A

036-A

048-A

060-A, B

 

 

OPERATING WEIGHT (Lb)

171

228

266

311

 

 

ELECTRICAL

 

 

 

 

 

 

Unit Volts—Hertz—Phase

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

 

 

Operating Voltage Range*

187-253

187-253

187-253

187-253

 

 

Compressor— Rated Load Amps

10.6

14.1

19.9

26.3

 

 

 

Locked Rotor Amps

64.0

66.0

96.0

130.0

 

 

Condenser Fan Motor—Full Load Amps

0.5

0.8

1.1

1.1

 

 

Min Unit Ampacity for Wire Sizing

13.8

18.4

26.0

34.0

 

 

Min Wire Size (60°C Copper) AWG†

14

14

10

8

 

 

Min Wire Size (75°C Copper) AWG†

14

14

10

10

 

 

Max Wire Length (60°C) (Ft)‡

57

43

77

91

 

 

Max Wire Length (75°C) (Ft)‡

55

41

73

56

 

 

Max Branch Circuit Fuse Size**

20

30

40

50

 

 

COMPRESSOR AND REFRIGERANT

 

 

 

 

 

 

 

Compressor—

Manufacturer

 

 

Bristol

 

 

 

 

Type

 

Reciprocating

 

 

 

Temperature and Current Protection

 

Internal Overload

 

 

 

Refrigerant—

Type

 

Puron® (R-410A)

 

 

 

 

Amount (Lb)

6.0

8.9

 

11.5

13.1

 

 

Metering Device

 

 

Puron Balance Port Hard Shutoff TXV

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSER COIL AND FAN

 

 

 

 

 

 

 

 

Coil—Face Area (Sq Ft)

 

10.8

18.2

 

18.2

18.2

 

 

Fins per In.—Rows—Circuits

 

25-1-2

25-1-3

 

20-2-5

20-2-5

 

 

Fan Motor—HP and RPM (PSC Type)

1/15 and 825

1/8 and 825

 

1/5 and 825

1/5 and 825

 

 

Volts—Hertz—Phase

 

 

208/230-60-1

 

 

 

Condenser Airflow (CFM)

 

1500

2500

 

3000

3100

 

 

OPTIONAL EQUIPMENT

 

 

 

 

 

 

 

 

Support Feet

 

 

KSASF0101AAA

 

 

 

Coastal Filter

 

 

KAACF0801MED

 

 

 

Bi-Flow Balance Port TXV (Hard Shut-off)

KSATX0201PUR

KSATX0301PUR

 

KSATX0401PUR

KSATX0501PUR

 

 

Thermostat, Auto Changeover,

 

 

 

 

 

 

 

 

Non-Programmable, °F/°C, 1-stage heat/

 

TSTATBBNAC01-B

 

 

 

1-stage cool

 

 

 

 

 

Thermostat, Auto Changeover,

 

 

 

 

 

 

 

 

7-Day Programmable, °F/°C, 2-stage heat/

 

 

 

 

 

 

 

2-stage cool in AC mode, 3-stage heat/

 

TSTATBBP2S01-B

 

 

 

2-stage cool in HP mode

 

 

 

 

 

Thermidistat Control, Programmable/Non-

 

TSTATBBPRH01-B

 

 

 

Programmable Thermostat with Humidity Control

 

 

 

 

Outdoor Air Temperature Sensor

 

 

TSTATXXSEN01-B

 

 

 

Backplate for Non-Programmable Thermostat

 

TSTATXXNBP01

 

 

 

Backplate for Programmable Thermostat

 

TSTATXXPBP01

 

 

 

Thermostat Conversion Kit (4 to 5 wire)—10 Pack

 

TSTATXXCNV10

 

 

* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.

If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated (non-plated), 60 or 75°C

(140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%. ** Time-delay fuse or circuit breaker.

NOTES: 1. Copper wire must be used from service disconnect to unit.

2.All motors and compressors contain internal overload protection.

3.This product may not be used in low-ambient applications below 55°F outdoor ambient.

OPTIONAL EQUIPMENT DESCRIPTION AND USAGE (Listed Alphabetically)

1.Coastal Filter

A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow. SUGGESTED USE:In geographic areas where salt damage could occur.

2.Support Feet

Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base; minimizes corrosion.

SUGGESTED USE:

—4—

Page 4
Image 4
Bryant 598B warranty Specifications, 024-A, 036-A, 048-A, 060-A,B