DETAILED COOLING CAPACITIES* continued
| EVAPORATOR |
|
|
|
|
| CONDENSER ENTERING AIR TEMPERATURES °F |
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| AIR |
| 75 |
|
| 85 |
|
| 95 |
|
| 105 |
|
|
| 115 |
|
| 125 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Capacity | Total | Capacity | Total | Capacity | Total | Capacity | Total |
| Capacity | Total | Capacity |
| Total | ||||||
|
|
| MBtuh† | MBtuh† | MBtuh† | MBtuh† |
| MBtuh† | MBtuh† |
| ||||||||||||
|
|
| System | System | System | System |
| System | System | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| CFM | EWB | Total | Sens‡ | KW** | Total | Sens‡ | KW** | Total | Sens‡ | Kw** | Total | Sens‡ | Kw** |
| Total | Sens‡ | Kw** | Total | Sens‡ |
| KW** |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 72 | 39.76 | 21.24 | 1.94 | 36.67 | 20.07 | 2.10 | 33.65 | 18.94 | 2.25 | 30.65 | 17.85 | 2.39 |
| 27.67 | 16.78 | 2.54 | 24.69 | 15.73 |
| 2.67 |
| 1050 | 67 | 35.45 | 25.93 | 1.92 | 32.63 | 24.76 | 2.07 | 29.85 | 23.64 | 2.21 | 27.10 | 22.54 | 2.35 |
| 24.38 | 21.45 | 2.48 | 21.68 | 20.35 |
| 2.61 |
| 63†† | 32.40 | 24.81 | 1.91 | 29.77 | 23.65 | 2.05 | 27.16 | 22.51 | 2.18 | 24.60 | 21.41 | 2.31 |
| 22.09 | 20.32 | 2.43 | 19.61 | 19.16 |
| 2.55 | |
|
| 62 | 31.56 | 30.45 | 1.91 | 29.05 | 29.05 | 2.04 | 27.06 | 27.06 | 2.18 | 25.10 | 25.10 | 2.32 |
| 23.15 | 23.15 | 2.46 | 21.12 | 21.12 |
| 2.59 |
|
| 57 | 30.98 | 30.98 | 1.90 | 29.02 | 29.02 | 2.04 | 27.07 | 27.07 | 2.18 | 25.11 | 25.11 | 2.32 |
| 23.15 | 23.15 | 2.46 | 21.12 | 21.12 |
| 2.59 |
|
| 72 | 41.34 | 23.37 | 2.04 | 38.00 | 22.15 | 2.21 | 34.69 | 20.96 | 2.36 | 31.46 | 19.81 | 2.51 |
| 28.27 | 18.69 | 2.65 | 25.12 | 17.61 |
| 2.79 |
| 1350 | 67 | 36.86 | 29.31 | 2.03 | 33.78 | 28.08 | 2.18 | 30.73 | 26.86 | 2.33 | 27.79 | 25.63 | 2.46 |
| 24.94 | 24.33 | 2.60 | 22.40 | 22.40 |
| 2.73 |
| 63†† | 33.67 | 27.97 | 2.02 | 30.76 | 26.72 | 2.16 | 27.94 | 25.47 | 2.30 | 25.23 | 24.21 | 2.42 |
| 22.66 | 22.66 | 2.56 | 20.48 | 20.48 |
| 2.69 | |
|
| 62 | 33.52 | 33.52 | 2.02 | 31.28 | 31.28 | 2.17 | 29.08 | 29.08 | 2.31 | 26.87 | 26.87 | 2.45 |
| 24.66 | 24.66 | 2.59 | 22.41 | 22.41 |
| 2.73 |
|
| 57 | 33.53 | 33.53 | 2.02 | 31.29 | 31.29 | 2.17 | 29.09 | 29.09 | 2.31 | 26.88 | 26.88 | 2.45 |
| 24.66 | 24.66 | 2.59 | 22.41 | 22.41 |
| 2.74 |
|
| 72 | 42.29 | 25.25 | 2.15 | 38.72 | 23.97 | 2.31 | 35.25 | 22.74 | 2.47 | 31.87 | 21.55 | 2.62 |
| 28.54 | 20.40 | 2.77 | 25.27 | 19.28 |
| 2.90 |
| 1650 | 67 | 37.66 | 32.34 | 2.14 | 34.38 | 30.98 | 2.29 | 31.22 | 29.58 | 2.44 | 28.19 | 28.19 | 2.57 |
| 25.69 | 25.69 | 2.72 | 23.23 | 23.23 |
| 2.86 |
| 63†† | 34.36 | 30.74 | 2.12 | 31.32 | 29.34 | 2.27 | 28.41 | 27.85 | 2.41 | 25.82 | 25.82 | 2.54 |
| 23.50 | 23.50 | 2.68 | 21.16 | 21.16 |
| 2.81 | |
|
| 62 | 35.35 | 35.35 | 2.13 | 32.94 | 32.94 | 2.28 | 30.50 | 30.50 | 2.43 | 28.09 | 28.09 | 2.57 |
| 25.70 | 25.70 | 2.72 | 23.23 | 23.23 |
| 2.86 |
|
| 57 | 35.36 | 35.36 | 2.13 | 32.95 | 32.95 | 2.28 | 30.51 | 30.51 | 2.43 | 28.10 | 28.10 | 2.57 |
| 25.70 | 25.70 | 2.72 | 23.24 | 23.24 |
| 2.86 |
|
| 72 | 42.84 | 26.94 | 2.25 | 39.14 | 25.63 | 2.42 | 35.54 | 24.36 | 2.58 | 32.05 | 23.15 | 2.73 |
| 28.63 | 21.98 | 2.87 | 25.24 | 20.80 |
| 3.01 |
| 1950 | 67 | 38.12 | 34.99 | 2.24 | 34.77 | 33.42 | 2.40 | 31.61 | 31.61 | 2.55 | 28.99 | 28.99 | 2.69 |
| 26.40 | 26.40 | 2.84 | 23.80 | 23.80 |
| 2.98 |
| 63†† | 34.80 | 33.11 | 2.23 | 31.66 | 31.65 | 2.38 | 29.03 | 29.03 | 2.52 | 26.55 | 26.55 | 2.66 |
| 24.09 | 24.09 | 2.80 | 21.61 | 21.61 |
| 2.94 | |
|
| 62 | 36.78 | 36.78 | 2.24 | 34.15 | 34.15 | 2.39 | 31.56 | 31.56 | 2.55 | 29.00 | 29.00 | 2.69 |
| 26.41 | 26.41 | 2.84 | 23.81 | 23.81 |
| 2.98 |
|
| 57 | 36.79 | 36.79 | 2.24 | 34.16 | 34.16 | 2.39 | 31.57 | 31.57 | 2.55 | 29.01 | 29.01 | 2.69 |
| 26.42 | 26.42 | 2.84 | 23.81 | 23.81 |
| 2.98 |
|
| 72 | 43.19 | 28.56 | 2.35 | 39.39 | 27.23 | 2.52 | 35.69 | 25.94 | 2.68 | 32.11 | 24.70 | 2.83 |
| 28.60 | 23.49 | 2.98 | 25.12 | 22.18 |
| 3.12 |
| 2250 | 67 | 38.48 | 37.30 | 2.34 | 35.16 | 35.16 | 2.50 | 32.40 | 32.40 | 2.66 | 29.66 | 29.66 | 2.81 |
| 26.94 | 26.94 | 2.96 | 24.21 | 24.21 |
| 3.10 |
| 63†† | 35.14 | 35.14 | 2.33 | 32.36 | 32.36 | 2.49 | 29.70 | 29.70 | 2.63 | 27.10 | 27.10 | 2.77 |
| 24.52 | 24.52 | 2.92 | 21.88 | 21.88 |
| 3.05 | |
|
| 62 | 37.91 | 37.91 | 2.34 | 35.14 | 35.14 | 2.50 | 32.41 | 32.41 | 2.66 | 29.68 | 29.68 | 2.81 |
| 26.96 | 26.96 | 2.96 | 24.22 | 24.22 |
| 3.10 |
|
| 57 | 37.93 | 37.93 | 2.34 | 35.15 | 35.15 | 2.50 | 32.43 | 32.43 | 2.66 | 29.68 | 29.68 | 2.81 |
| 26.96 | 26.96 | 2.96 | 24.23 | 24.23 |
| 3.10 |
Multipliers for Determining the Performance With Other Indoor Sections
| Indoor |
| Low Speed | Indoor |
| Low Speed |
| ||
|
|
|
|
|
|
|
| ||
| Section | Size | Capacity | Power | Section | Size | Capacity | Power |
|
|
|
|
|
|
|
|
|
|
|
| CK5A/CK5BA | 060 | 1.00 | 1.08 | CK5PA | 060 | 0.99 | 1.04 |
|
| CK5A/CK5BT | 060 | 1.00 | 1.08 | CK5PT | 060 | 0.99 | 1.04 |
|
| CK5A/CK5BX | 060 | 1.00 | 1.08 | CK5PX | 060 | 1.00 | 1.04 |
|
| CK5PA | 060 | 1.00 | 1.08 | COILS + 355MAV060120 VARIABLE SPEED FURNACE |
| |||
| CK5PT | 060 | 1.00 | 1.08 | CC5A/CD5AA | 060 | 0.98 | 1.04 |
|
| CK5PX | 060 | 1.00 | 1.08 | CC5A/CD5AW | 060 | 0.98 | 1.04 |
|
| COILS + 355MAV060100 VARIABLE SPEED FURNACE | CE3AA | 060 | 0.99 | 1.04 |
| |||
| CC5A/CD5AA | 060 | 0.97 | 1.05 | CK3BA | 060 | 0.99 | 1.04 |
|
| CC5A/CD5AW | 060 | 0.98 | 1.03 | CK5A/CK5BA | 060 | 0.99 | 1.04 |
|
| CE3AA | 060 | 0.99 | 1.04 | CK5A/CK5BT | 060 | 0.99 | 1.04 |
|
| CK3BA | 060 | 0.99 | 1.04 | CK5A/CK5BX | 060 | 1.00 | 1.04 |
|
| CK5A/CK5BA | 060 | 0.99 | 1.04 | CK5PA | 060 | 0.99 | 1.04 |
|
| CK5A/CK5BT | 060 | 0.99 | 1.04 | CK5PT | 060 | 0.99 | 1.04 |
|
| CK5A/CK5BX | 060 | 1.00 | 1.04 | CK5PX | 060 | 1.00 | 1.04 |
|
*Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard
†Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh (245 kw) per 1,000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245°kw) per 1,000 CFM (480 L/S) of indoor coil air per degree above 80°F (27°C). When the required data falls between the published data, interpolation may be performed.
** Unit kw is total of indoor and outdoor unit kilowatts.
††At TVA conditions