Bryant installation instructions Ð Base Unit Dimensions Ð 564A/764A024-036

Models: 764A

1 24
Download 24 pages 6.94 Kb
Page 2
Image 2
Fig. 2 Ð Base Unit Dimensions Ð 564A/764A024-036

UNIT

ELECTRICAL

UNIT

CENTER OF GRAVITY mm [in.]

WEIGHT

564A/764A

CHARACTERISTICS

 

 

 

 

 

Lb

Kg

X

Y

Z

 

 

024

208/230-1-60

222

101

355.6 [14.00]

508.0 [20.00]

241.3 [9.50]

030

208/230-1-60

236

107

355.6 [14.00]

508.0 [20.00]

241.3 [9.50]

036

208/230-1-60, 208/230-3-60

250

114

355.6 [14.00]

508.0 [20.00]

241.3 [9.50]

 

 

 

 

 

 

 

LEGEND

NEC Ð National Electrical Code

REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL, mm [in.]

Top of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

Duct Side of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 0

Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . 0

Bottom of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

NEC REQUIRED CLEARANCES, mm [in.]

 

Between Units, Power Entry Side . . .

. . . . 1066.8

[42.00]

Unit and Ungrounded Surfaces,

 

 

Power Entry Side

. . . . 914.0

[36.00]

Unit and Block or Concrete Walls and Other

 

Grounded Surfaces, Power Entry Side

. . . . 1066.8 [42.00]

REQUIRED CLEARANCES FOR SERVICING, mm [in.]

Condenser Coil Access Side . . . . . . . . . . . . 762.0 [30.00]

Power Entry Side

(Except for NEC Requirements) . . . . . . . . . 762.0 [30.00]

Unit Top . . . . . . . . . . . . . . . . . . . . . . . . 914.0 [36.00]

Side Opposite Ducts . . . . . . . . . . . . . . . . . 762.0 [30.00]

NOTES:

1.Clearances must be maintained to prevent recirculation of air from condenser-fan discharge. With the exception of the condenser coil (914 mm [36 in.]), a removable fence or bar- ricade requires no clearance.

2. Dimensions are in millimeters. Dimensions in [ ] are in inches.

Fig. 2 Ð Base Unit Dimensions Ð 564A/764A024-036

Ð2Ð

Page 2
Image 2
Bryant installation instructions Ð Base Unit Dimensions Ð 564A/764A024-036