Bryant 764A Ð Physical Data, Ð Condensate Connection Details, A Ð Condensate Trap Using Tubing

Models: 764A

1 24
Download 24 pages 6.94 Kb
Page 6
Image 6
Table 1 Ð Physical Data

Table 1 Ð Physical Data

UNIT 564A AND 764A

024

030

 

036

 

042

048

060

OPERATING WEIGHT (lb)

222

236

 

250

 

297

310

350

COMPRESSOR TYPE

 

 

 

Reciprocating

 

 

REFRIGERANT

 

 

 

 

R-22

 

 

Charge (lb)

2.8

3.9

 

4.7

 

4.4

6.1

7.5

REFRIGERANT METERING DEVICE

 

 

 

Acutrol™ System

 

 

CONDENSER COIL

 

 

Copper Tubes, Aluminum Plate Fins

 

Rows...Fins/in.

1...17

1...17

 

2...17

 

1...17

2...17

2...17

Total Face Area (sq ft)

6.7

7.9

 

6.2

 

11.1

8.6

10.7

CONDENSER-FAN MOTOR

 

 

 

 

Propeller

 

 

Cfm

1600

2000

 

2000

 

2600

2600

2800

Nominal Rpm

825

1100

 

1100

 

1100

1100

1100

Motor Hp

1¤8

1¤4

 

1¤4

 

1¤4

1¤4

1¤4

Diameter (in.)

20

20

 

20

 

20

20

20

EVAPORATOR COIL

 

 

Copper Tubes, Aluminum Plate Fins

 

Rows...Fins/in.

2...15

3...15

 

3...15

 

3...15

3...15

4...15

Total Face Area (sq ft)

2.8

2.8

 

3.1

 

3.9

4.3

4.9

EVAPORATOR-FAN MOTOR

 

 

 

Direct Drive

 

 

Blower Motor Size (in.)

10 x 8

10 x 8

 

10 x 8

 

10 x 9

10 x 9

10 x 10

Nominal Cfm

800

1000

 

1200

 

1400

1600

2000

Rpm Range

550-1000

550-1000

 

800-1050

 

800-1050

1000-1100

950-1100

Number of Speeds

3

3

 

3

 

3

2

3*

Factory Speed Setting

Low

Med

 

Low

 

Med

Low

Low

Motor Hp

1¤4

1¤4

 

1¤2

 

1¤2

3¤4

1

CONNECTING DUCT SIZES

 

 

 

Round

 

 

 

Square

Supply Air (in.)

 

 

14

 

 

 

13.9 x 13.9

Return Air (in.)

 

 

14

 

 

 

13.9 x 27.8

FIELD-SUPPLIED RETURN AIR FILTER²

 

 

 

 

 

 

 

 

Throwaway (in.)

24 x 24

24 x 24

 

24 x 24

 

24 x 24

24 x 30

24 x 30

*460-v motors are 2-speed only.

²Required ®lter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute) rated air¯ow at a velocity of 300 ft/min for throwaway type or 450 ft/min for high capacity type. Recommended ®lters are 1-in. thick.

CONDENSATE DRAIN HOLE

Fig. 7 Ð Condensate Connection Details

Fig. 8A Ð Condensate Trap (Using Tubing)

Fig. 8B Ð Condensate Trap (Using PVC Piping)

If the installation requires draining the condensate water away from the unit, install a ®eld-supplied 2-in. trap using 3¤4-in. OD tubing or piping to ensure proper drainage. See Fig. 8A and 8B. Make sure that the outlet of the trap is at least one in. lower than the unit drain pan condensate con- nection to prevent the pan from over¯owing. Connect a drain tube using a minimum of 3¤4-in. PVC, 3¤4-in. CPVC, or 3¤4-in. copper pipe (all ®eld-supplied). Do not undersize the tube. Pitch the drain tube downward at a slope of at least 1 inch in every 10 ft of horizontal run. Be sure to check the drain tube for leaks. Prime trap at the beginning of cooling season start-up. Allowable glues for condensate trap connection are: Stand- ard ABS, CPVC, or PVC cement.

B. Field-Duct Connections

NOTE: The design and installation of the duct system must be in accordance with the standards of NFPA for the instal- lation of nonresidence-type air conditioning and ventilating systems, NFPA 90A or residence-type, NFPA 90B, and/or local codes and ordinances.

Units have duct ¯anges on the supply- and return-air open- ings on the side of the unit. See Fig. 2-4 for connection sizes and locations.

Ð6Ð

Page 6
Image 6
Bryant 764A Ð Physical Data, Ð Condensate Connection Details, A Ð Condensate Trap Using Tubing, B. Field-DuctConnections