LEGEND |
|
NEC Ð National Electrical Code | Outdoor Air¯ow |
Power Wiring | Indoor Air¯ow |
Control Wiring |
*Required for electric heater when
Fig. 12 Ð Typical Installation
C. Converting Horizontal Discharge Units to Down¯ow (Vertical) Discharge
WARNING: Before performing service or mainte- nance operations on system, turn off main power to unit. Turn off accessory heater power switch if applicable. Elec- trical shock can cause personal injury.
Units are dedicated
D. Electrical Connections
WARNING: The unit cabinet must have an un- interrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire con- nected to the unit ground in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC, ANSI (American National Standards Institute)/NFPA (latest edition) (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1) and local electrical codes. Failure to adhere to this warning could result in per- sonal injury or death.
CAUTION: Failure to follow these precautions could result in damage to the unit being installed:
1.Make all electrical connections in accordance with NEC ANSI/NFPA (latest edition) and local electrical codes governing such wiring. In Canada, all elec- trical connections must be in accordance with CSA Standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2.Use only copper conductor for connections between
DO NOT USE ALUMINUM WIRE.
3.Be sure that
4.Insulate
5.Do not damage internal components when drilling through any panel to mount electrical hardware, con- duit, etc.
The unit must have a separate electrical service with a ®eld- supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate for maxi- mum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing. See Table 2 for electrical data.
The
CAUTION: Operation of unit on improper line volt- age constitutes abuse and may cause unit damage that could affect warranty.
Routing Power Leads Into Unit
Use only copper wire between disconnect and unit. The high- voltage leads should be in a conduit until they enter the unit; conduit termination at the unit must be watertight. Run the
Connecting Ground Lead to Unit Ground
Refer to Fig. 14 and 15. Connect the ground lead to the chas- sis using the unit ground screw in the control box.
Routing Control Power Wires
Form a
Ð8Ð