Bryant H3A Make Electrical Connections, Compressor Crankcase Heater, Start-Up, Final Wiring Check

Models: H3A

1 6
Download 6 pages 11.76 Kb
Page 4
Image 4
Table 2 – Accessory Usage

Table 2 – Accessory Usage

 

REQUIRED FOR LOW--- AMBIENT

REQUIRED FOR LONG LINE

REQUIRED FOR

 

SEA COAST

ACCESSORY

COOLING APPLICATIONS

APPLICATIONS*

APPLICATIONS

 

(Below 55°F/12.8_C)

 

 

(Within 2 miles/3.22 km)

 

 

 

Ball Bearing Fan Motor

Yes{

No

No

Compressor Start Assist Capacitor and Relay

Yes

Yes

No

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Hard Shut--- Off TXV

Yes

Yes

Yes

Liquid Line Solenoid Valve

No

No

No

Motor Master® or Low---ambient Pressure Switch

Yes

No

No

Support Feet

Recommended

No

Recommended

Winter Start Control

Yes

No

No

*For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 35 ft. (10.7 m) vertical differential, refer to Residential Split---System Longline Application Guideline.

{Additional requirement for Low---Ambient Controller (full modulation feature) MotorMasterr Control.

113A / 114A / 116B

Make Electrical Connections

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.

NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits.

NOTE: Use copper wire only between disconnect switch and unit.

NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 5.

Use No. 18 AWG color-coded, insulated (35_C minimum) wire. If thermostat is located more than 100 ft. (30.48 m) from unit, as measured along the control voltage wires, use No. 16 AWG color-coded wire to avoid excessive voltage drop.

All wiring must be NEC Class 1 and must be separated from incoming power leads.

Use furnace transformer, fan coil transformer, or accessory transformer for control power, 24v/40va minimum.

NOTE: Use of available 24v accessories may exceed the minimum 40va power requirement. Determine total transformer loading and increase the transformer capacity or split the load with an accessory transformer as required.

Final Wiring Check

IMPORTANT: Check factory wiring and field wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.

A crankcase heater is required if refrigerant tubing is longer than 80 ft. (24.38 m). Refer to the Application Guideline and Service Manual Longline Section-Residential Split-System Air Conditioners and Heat Pumps.

Install Electrical Accessories

Refer to the individual instructions packaged with kits or accessories when installing.

Start-Up

!CAUTION

UNIT OPERATION AND SAFETY HAZARD

DISCONNECT

PER N.E.C. AND/OR LOCAL CODES

FIELD POWER

WIRING

3 PHASE ONLY

FIELD GROUND

WIRING

CONTACTOR

BLUE

GROUND

LUG

A94025

Failure to follow this caution may result in personal injury, equipment damage or improper operation.

S Do not overcharge system with refrigerant.

S Do not operate unit in a vacuum or at negative pressure. S Compressor dome temperatures may be hot.

!CAUTION

PERSONAL INJURY HAZARD

Fig. 5 - Line Connections

Connect Control Wiring

Route 24-v control wires through control wiring grommet and connect leads to control wiring (See Fig. 7). Refer to Installation Instructions packaged with thermostat.

Failure to follow this caution may result in personal injury.

Wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following:

S Front seating service valves are equipped with Schrader valves.

4

Page 4
Image 4
Bryant H3A Make Electrical Connections, Compressor Crankcase Heater, Install Electrical Accessories, Start-Up