II.DUCT MOUNTING (LOW VOLTAGE)

1.Locate humidistat at least 8 in. upstream of humidifier in return-air duct. If mounting near elbow area, keep device 6 in. upstream of elbow so element will be affected by normal airflow. (See Fig. 20.)

2.Remove protective backing from template furnished with each control and apply self-adhesive side on return air duct at selected location. Following instructions on template and in Fig. 21, drill 2 mounting holes and six 1/4-in. diameter sensing holes in duct. Sensing holes allow return air to reach nylon sensing element and operate humidistat.

NOTE: If desired, cut square hole in duct as indicated on template as an alternative to holes.

3.Remove protective backing from foam gasket provided with control and apply to template.

4.Run low-voltage wire from humidifier to template. Lay wire over 1 side of foam gasket. Wire can enter humidistat case from any direction.

IMPORTANT: Do not position wire directly under standoff projections at back of case. If wire is under these projections, case will not seat tightly against gasket causing air leakage and possible improper operation.

5.Remove knob, faceplate, and switch assembly from case by following steps listed below.

a.Remove knob by pulling away from casing. (See Fig. 18.)

b.Lift off faceplate, starting at right side. Left end of faceplate protrudes under lip on casing. (See Fig. 18.)

c.Remove switch by removing 2 screws in back of casing. Pressing tab on case. Lift out control. (See Fig. 19.)

6.Make connections to screw terminals on switch assembly. Re-install switch into casing Ð secure with 2 short screws.

7.While holding wire in place. Mount humidistat case hori- zontally on duct using 2 mounting screws provided. Tighten firmly so that gasket seals space around wires and between case and duct. (See Fig. 21.)

8.Replace faceplate and knob.

III. WIRING

All wiring must comply with local codes and ordinances.

IV. ADJUSTMENT

Recommended humidistat setting should only be used as a guide. After adjustment of setting, allow at least 5 hr for equilibrium to be reached. Condensation on single pane windows or woodwork indicates excessive moisture. Condensation must not be allowed to continue for extended periods of time, or moisture damage can result. Lower humidistat setting in small steps until condensation disappears. However, if air is too dry, raise the setting.

ALTERNATE LOCATIONS

RETURN AIR

RETURN AIR

5 IN. MIN.

BEST LOCATION

15 IN. MIN.

RETURN AIR DUCT

A97104

Fig. 20ÐAlternate Location Duct Mount Installation

Ð11Ð

Page 11
Image 11
Bryant HUM-56-1 manual II. Duct Mounting LOW Voltage, III. Wiring, IV. Adjustment

HUM-56-1 specifications

The Bryant HUM-56-1 is a cutting-edge heating, ventilation, and air conditioning (HVAC) unit that has garnered attention in both residential and commercial sectors for its advanced features and efficient performance. Designed to provide optimal climate control, the HUM-56-1 incorporates several innovative technologies that set it apart from traditional HVAC systems.

One of the standout features of the Bryant HUM-56-1 is its high-efficiency design. The unit boasts an impressive Seasonal Energy Efficiency Ratio (SEER) rating, which indicates its ability to deliver maximum cooling with minimal energy consumption. This efficiency translates into lower utility bills and a reduced carbon footprint, making it an environmentally conscious choice for homeowners and businesses alike.

The HUM-56-1 employs advanced smart technology, including Wi-Fi connectivity and compatibility with smart home systems. This allows users to monitor and control their HVAC system remotely via mobile devices, providing convenience and flexibility. The unit also features programmable settings that enable users to customize their indoor climate according to their schedules, further enhancing energy savings and comfort.

Another key characteristic of the HUM-56-1 is its quiet operation. Equipped with sound-dampening features, the unit minimizes noise levels, ensuring a peaceful indoor environment. This is particularly beneficial for residential applications where noise disruption can impact daily life.

In terms of air quality management, the HUM-56-1 is designed to optimize indoor air quality. The unit is compatible with advanced filtration systems that remove allergens and pollutants from the air, making it an excellent choice for allergy sufferers. Additionally, the system’s ventilation capabilities ensure fresh air circulation, promoting a healthier living space.

Durability is a crucial aspect of the Bryant HUM-56-1. Constructed with high-quality materials, the unit is built to withstand various environmental conditions, ensuring longevity and reliable performance. Bryant also backs the HUM-56-1 with a comprehensive warranty, highlighting their commitment to quality and customer satisfaction.

Overall, the Bryant HUM-56-1 stands out in the HVAC market due to its efficiency, smart technology integration, quiet operation, enhanced air quality features, and durable construction. These characteristics make it a preferred choice for those seeking a reliable and effective climate control solution. Whether for residential or commercial use, the HUM-56-1 is poised to deliver outstanding performance and comfort all year round.