Burnham 81433101R16-1/10 VII. System Start-up, Always Inspect Installation Before Starting Burner

Models: 81433101R16-1/10

1 40
Download 40 pages 18.46 Kb
Page 23
Image 23

VII. System Start-up

WARNING

All boilers equipped with burner swing door have a potential hazard which can cause severe property damage, personal injury or loss of life if ignored. Before opening swing door, turn off service switch to boiler to prevent accidental firing of burner outside the combustion chamber. Be sure to tighten swing door fastener completely when service is completed.

A.ALWAYS INSPECT INSTALLATION BEFORE STARTING BURNER.

B. FILL HEATING SYSTEM WITH WATER. Refer to Section III, G.

C.CHECK CONTROLS, WIRING AND BURNER to be sure that all connections are tight and burner is rigid, that all electrical connections have been completed and fuses installed, and that oil tank is filled and oil lines have been tested.

D. LUBRICATION — Follow instruction on burner and circulator label to lubricate, if oil lubricated. Most motors currently used on residential type burners employ permanently lubricated bearings and thus do not require any field lubrication. Water lubricated circulators do not need field lubrication.

Do not over-lubricate. This can cause as much trouble as no lubrication at all.

E. Adjust control settings with burner service switch turned “ON” and room thermostat set 10° below room temperature.

1.Adjustment and display modes of the L7248/ L7224 Oil Electronic Aquastat Controller.

a.On the L7248/L7224, the overall range of the High Limit is from 180°F to 240°F (82°C to 116°C).

b.Set the High Limit (designated HL) on the

L7248/L7224 Aquastat Control at 180°F. This temperature setting may be varied to suit requirements of installation. Differential is fixed at 15°F.

i.Adjusting Settings:

To discourage unauthorized changing of

Aquastat settings, a procedure to enter the adjustment mode is required. To enter the adjustment mode, press the UP, DOWN, and I buttons (see Figure 18) simultaneously for three (3) seconds. Press the ‘I’ button until the feature requiring adjustment is displayed (press the “I” button again and will display LL (Low Limit on L7224):

Figure 18: L7248 Circuit Board Layout -

Horizontal Mount

·High Limit

·°F -- °C (Toggle)

Then press the UP and/or DOWN buttons to move the set point to the desired value. After 60 seconds without any button inputs, the control will automatically return to the READ mode.

ii.Display:

In the RUN mode, the Aquastat will flash “bt” (boiler temp.) followed by the temperature (i.e., 220), followed by °F or °C.

To read boiler settings, press the ‘I’ key to read the parameter of interest. For example, press I (HL) High Limit is displayed, followed by a three-digit number, i.e., 220, followed by °F or °C.

See Figure 19 for Display Readout

Definitions.

 

 

Display

Text

Description

Shows

bt

Boiler Temperature

 

HL

High Limit

 

err

Error Code

 

fDegrees Fahrenheit

cDegrees Celsius

LLLow Limit

Figure 19: Display Readout Definitions

23

Page 23
Image 23
Burnham 81433101R16-1/10 VII. System Start-up, Always Inspect Installation Before Starting Burner, Adjusting Settings

81433101R16-1/10 specifications

The Burnham 81433101R16-1/10 is a highly regarded component within the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its reliability and performance. This specific part is designed to enhance the efficiency of heating systems, making it an essential component for both residential and commercial applications.

One of the standout features of the Burnham 81433101R16-1/10 is its durable construction. Made with high-quality materials, this product is built to withstand the rigors of continuous operation in various environmental conditions. Its robust design ensures a longer lifespan, reducing the need for frequent replacements and maintenance, which ultimately saves on operational costs.

The Burnham 81433101R16-1/10 incorporates advanced technology to optimize energy usage. This part is engineered for high efficiency, meaning that it works to convert a maximum amount of energy into heat with minimal waste. The integration of cutting-edge technology ensures that users experience significant energy savings, which not only helps in reducing utility bills but also contributes positively to environmental sustainability.

In terms of compatibility, the Burnham 81433101R16-1/10 is designed to work seamlessly with various heating systems. This makes it a versatile choice for technicians and homeowners alike, as it can be easily integrated without extensive modifications. The ease of installation is another appealing characteristic, allowing for quicker setups that minimize downtime.

Furthermore, this component prioritizes safety, featuring built-in mechanisms that help prevent overheating and other potential hazards. This focus on safety reassures users that their heating systems can operate efficiently without compromising the well-being of their households or properties.

The Burnham 81433101R16-1/10 is also known for its user-friendly design. Technicians find that maintenance and inspection processes are straightforward, allowing for easy access to components for troubleshooting or routine checks. This practical feature enhances user satisfaction and simplifies operational management.

Overall, the Burnham 81433101R16-1/10 exemplifies a commitment to quality, efficiency, and safety in HVAC applications. Its combination of durability, advanced technology, and versatile compatibility makes it a valuable choice for anyone looking to enhance their heating system's performance. By opting for the Burnham 81433101R16-1/10, users can enjoy efficient heating solutions that meet their needs for comfort and energy conservation.