Burnham RSA Remove GUN Assembly, Verify OIL Burner Settings Before Starting, Start OIL Burner

Models: RSA

1 52
Download 52 pages 34.98 Kb
Page 34
Image 34

H.REMOVE GUN ASSEMBLY

1.Check nozzle size, head size, gun setting, and positioning of electrodes. This information is shown in Figure 25 and Tables 7 and 7A for Beckett burner, Figure 25A and Table 7B for Carlin EZ-1HP burner.

2.Reinstall gun assembly.

I.VERIFY OIL BURNER SETTINGS BEFORE STARTING

1.BURNER AIR BAND AND AIR SHUTTER SETTINGS, see Tables 7 and 7A for Beckett burner, Table 7B for Carlin EZ-1HP burner.

2.OPEN ALL OIL LINE VALVES.

3.Attach a plastic hose to fuel pump vent fitting and provide a container to catch the oil.

4.REMOVE GAUGE PORT PLUG from fuel pump and install pressure gauge.

J.START OIL BURNER

1.Open vent fitting on fuel pump.

2.TURN ‘ON’ BURNER service switch and allow burner to run until oil flows from vent fitting in a SOLID stream without air bubbles for approximately 10 seconds.

3.Close vent fitting and burner flame should start immediately after pre-purge is complete. Pre-purge prevents burner flame until 10 seconds has elapsed after initial power is applied to burner. During pre-purge, the motor and ignitor will operate but the oil valve will remain closed. Refer to Oil Primary Control Instructions for more details.

4.For Carlin burner, refer to “Installation and

Operating Instructions for Packaged Heating/ Burner Units, Carlin Elite Oil Burner” (Form CCT-569A)for instructions for Bleeding the Pump and Starting the Burner.

K.ADJUST OIL PRESSURE

1.Locate oil pressure adjusting screw and turn screw until Pressure Gauge reads the correct pump pressure required for the specific boiler. Refer to

Tables 7 & 7A for Beckett burners or Table 7B for Carlin burner (set pump pressure to 150 for Carlin EZ-1HP Burner).

2.DO NOT REMOVE PRESSURE GAUGE until later.

L.OTHER ADJUSTMENTS

Beckett Burner

1.ADJUST THE AIR BAND AND/OR AIR SHUTTER.

a.Adjust air supply by loosening lock screws and moving the air shutter and if necessary the air band. Refer to Tables 7 and 7A preliminary settings.

2. ADJUST DRAFT REGULATOR for a draft of

-

.02” (water gauge) over the fire after chimney has

 

reached operating temperature and while burner is

 

running.

 

3.READJUST AIR BANDS on burner for a light orange colored flame while draft over the fire is

-.02” w.c. Use a smoke test and adjust air for minimum smoke (not to exceed #1) with a minimum of excess air. Make final check using suitable instrumentation to obtain a CO2 of 11.5 to 12.5% with draft of -.02” w.c. in fire box. These settings will assure a safe and efficient operating condition. If the flame appears stringy instead of a solid flame, try another nozzle of the same type. Flame should be solid and compact. After all adjustments have been made, recheck for a draft of -.02” w.c. over the fire.

4.TURN “OFF” BURNER and remove pressure gauge. Install gauge port plug and tighten. Start burner again.

Carlin Burner

1-4. Refer to “Installation and Operating Instructions for Packaged Heating/Burner Units, Carlin Elite Oil Burner” (Form CCT-569A)for instructions for Bleeding the Pump and Starting the Burner.

5.Turn “off” Burner and remove pressure gauge. Install gauge port plug and tighten. Start burner again.

6.CAD Cell Location and Service. The burner is supplied with a cadmium sulfide flame detector mounted at the factory, mounted on the bottom of the transformer. See “Installation and Operating

Instructions for Packaged Heating/Burner Units, Carlin Elite Oil Burner” (Form CCT-569A). To service cad cell or to replace the plug in portion, swing open the transformer. After service is complete, be sure to fasten down the transformer.

M.FLAME FAILURE

The RSA boiler controls operate the burner automatically. If for unknown reasons the burner ceases to fire and the reset button on the primary control has tripped, the burner has experienced ignition failure. Before pressing the reset button, call your serviceman immediately.

WARNING

Do not attempt to start the burner when excess oil has accumulated, when the unit is full of vapor, or when the combustion chamber is very hot.

N.CHECK FOR CLEAN CUT OFF OF BURNER 1. AIR IN THE OIL LINE between fuel unit and

34

Page 34
Image 34
Burnham RSA Remove GUN Assembly, Verify OIL Burner Settings Before Starting, Open ALL OIL Line Valves, Start OIL Burner

RSA specifications

Burnham RSA is a prominent figure in the renewable energy sector, specializing in the development and management of renewable energy projects across various scales. The company has established a strong reputation for its commitment to sustainability and innovation, embracing advanced technologies and methodologies to maximize energy efficiency and minimize environmental impact.

At the heart of Burnham RSA's operations lies a diverse portfolio of renewable energy sources, including solar, wind, and biomass. The company's flagship projects often showcase cutting-edge solar photovoltaic (PV) technology, which effectively converts sunlight into electricity. By utilizing high-efficiency solar panels, Burnham RSA can ensure maximum energy generation, even in less-than-ideal weather conditions.

Wind energy is another critical component of Burnham RSA's strategy. The deployment of state-of-the-art wind turbines at strategic locations allows for optimal harnessing of wind energy. These turbines are equipped with advanced control systems that optimize their performance by adjusting their orientation and blade pitch to maximize energy capture based on real-time wind conditions.

In addition to solar and wind, Burnham RSA is actively exploring biomass energy solutions, which involve converting organic materials into usable energy. This approach not only provides a renewable energy source but also contributes to waste reduction, as agricultural and forestry residues can be repurposed to generate power.

Burnham RSA places a strong emphasis on sustainability, ensuring that all projects are designed with environmental considerations at the forefront. The company adheres to rigorous standards for environmental impact assessments and works closely with local communities to promote awareness and education about renewable energy benefits.

Smart grid technology is another area where Burnham RSA excels. By implementing advanced grid management systems and energy storage solutions, the company enhances the reliability and efficiency of renewable energy distribution. These systems allow for better integration of various energy sources, ensuring a stable energy supply even during peak demand periods.

Furthermore, Burnham RSA is committed to continuous innovation, investing in research and development to improve existing technologies and explore new avenues for energy production. This proactive approach not only fosters growth within the company but also contributes positively to the broader renewable energy landscape.

In summary, Burnham RSA stands out in the renewable energy sector through its comprehensive use of solar, wind, and biomass technologies, commitment to sustainability, and focus on innovation. With its advanced systems and community engagement efforts, Burnham RSA is poised to play a significant role in shaping the future of renewable energy.