X. Low Water Cut Off (LWCO)

WARNING

DO NOT ATTEMPT to cut factory wires to install an aftermarket Low Water Cut Off (LWCO). Only use connections specifically identified for Low Water Cut Off.

In all cases, follow the Low Water Cut Off (LWCO) manufacturer's instructions.

When

A low water cutoff is required to protect a hot water boiler when any connected heat distributor (radiation) is installed below the top of the hot water boiler (i.e. baseboard on the same floor level as the boiler). In addition, some jurisdictions require the use of a LWCO with a hot water boiler.

Where

The universal location for a LWCO on both gas and oil hot water boilers is above the boiler, in either the supply or return piping. The minimum safe water level of a water boiler is at the uppermost top of the boiler; that is, it must be full of water to operate safely.

What Kind

Typically, in residential applications, a probe type LWCO is used instead of a float type, due to their relative costs and the simplicity of piping for a probe LWCO.

How to Pipe

A “tee” is commonly used to connect the probe LWCO to the supply or return piping, as shown below.

LWCO Location

Select the appropriate size tee using the LWCO manufacturer’s instructions. Often, the branch connection must have a minimum diameter to prevent bridging between the probe and the tee. Also, the run of the tee must have a minimum diameter to prevent the end of the probe from touching or being located too close to the inside wall of the run of the tee.

Ideally, manual shutoff valves should be located above the LWCO and the boiler to allow for servicing. This will allow probe removal for inspection without

50

draining the heating system. Many probe LWCO manufacturers recommend an annual inspection of the probe.

How to Wire

LWCO’s are available in either 120 VAC or 24 VAC configurations. The 120 VAC configuration can be universally applied to both gas and oil boilers by wiring it in the line voltage service to the boiler (after the service switch, if so equipped).

The presence of water in a properly installed LWCO will cause the normally open contact of the LWCO to close, thus providing continuity of the 120 VAC service to the boiler.

It is recommended to supply power to the probe LWCO with the same line voltage boiler service as shown below.

Wiring of Typical LWCO

A 24 VAC LWCO is used primarily for gas fired boilers where a 24 volt control circuit exists within the boiler. However, a 24 VAC LWCO can only be used if the boiler manufacturer has provided piping and wiring connections and instructions to allow for this application.

How to Test

Shut off fuel supply. Lower water level until water level is BELOW the LWCO. Generate a boiler demand by turning up thermostat. Boiler should not attempt to operate. Increase the water level by filling the system. The boiler should attempt to operate once the water level is above the LWCO.

Page 50
Image 50
Burnham RSA manual Low Water Cut Off Lwco, Lwco Location, Wiring of Typical Lwco

RSA specifications

Burnham RSA is a prominent figure in the renewable energy sector, specializing in the development and management of renewable energy projects across various scales. The company has established a strong reputation for its commitment to sustainability and innovation, embracing advanced technologies and methodologies to maximize energy efficiency and minimize environmental impact.

At the heart of Burnham RSA's operations lies a diverse portfolio of renewable energy sources, including solar, wind, and biomass. The company's flagship projects often showcase cutting-edge solar photovoltaic (PV) technology, which effectively converts sunlight into electricity. By utilizing high-efficiency solar panels, Burnham RSA can ensure maximum energy generation, even in less-than-ideal weather conditions.

Wind energy is another critical component of Burnham RSA's strategy. The deployment of state-of-the-art wind turbines at strategic locations allows for optimal harnessing of wind energy. These turbines are equipped with advanced control systems that optimize their performance by adjusting their orientation and blade pitch to maximize energy capture based on real-time wind conditions.

In addition to solar and wind, Burnham RSA is actively exploring biomass energy solutions, which involve converting organic materials into usable energy. This approach not only provides a renewable energy source but also contributes to waste reduction, as agricultural and forestry residues can be repurposed to generate power.

Burnham RSA places a strong emphasis on sustainability, ensuring that all projects are designed with environmental considerations at the forefront. The company adheres to rigorous standards for environmental impact assessments and works closely with local communities to promote awareness and education about renewable energy benefits.

Smart grid technology is another area where Burnham RSA excels. By implementing advanced grid management systems and energy storage solutions, the company enhances the reliability and efficiency of renewable energy distribution. These systems allow for better integration of various energy sources, ensuring a stable energy supply even during peak demand periods.

Furthermore, Burnham RSA is committed to continuous innovation, investing in research and development to improve existing technologies and explore new avenues for energy production. This proactive approach not only fosters growth within the company but also contributes positively to the broader renewable energy landscape.

In summary, Burnham RSA stands out in the renewable energy sector through its comprehensive use of solar, wind, and biomass technologies, commitment to sustainability, and focus on innovation. With its advanced systems and community engagement efforts, Burnham RSA is poised to play a significant role in shaping the future of renewable energy.