READ ALL INSTRUCTIONS AND SAFETY INFORMATION
IMPORTANT!
It is extremely important you verify the electrical supply wires are the same voltage as the heater (i.e. 120 volt heater to 120 volt power
supply and 240 volt heater to 240 volt power supply).
If replacing an existing heater, check the labels of the old heater and replace using the same voltage. Hooking a 240 volt heater to a 120 volt power supply will drastically reduce the heater's output. Hooking a 120 volt heater to a 240 volt power supply will destroy the heater. Connecting your heater to an incompatible power supply will void the warranty.
Warranty is void if any material is sprayed on the element or blower.
Installation Instructions
Part One
PLACEMENT: For best results install The Register Plus on an inside wall. Headers and bracing are not
necessary. NOTE: The wall can must be installed in the TOP UP (horizontal) position only. Heater is not approved for ceiling mount.
THERMOSTAT: A thermostat is required. A Cadet Electronic Thermostat is recommended for ultimate control and comfort.
How do I install for new construction? | How do I install in an existing wall? | |||
| Mount Wall Can |
| Cut Hole In Wall | |
STEP 1 | STEP 1 | |||
The RM series REQUIRES A MINIMUM distance | Cut a hole 12 ¾ inches wide by 6 inches high | |||
of 6 inches from adjacent surfaces and 4 ½ inches | next to wall stud. The RM series REQUIRES A | |||
from the floor. However, Cadet RECOMMENDS | MINIMUM distance of 6 inches from adjacent | |||
12 inches from all adjacent surfaces and 12 inches | surfaces and 4 ½ inches from the floor. However, | |||
from the floor (See Figure 5) for longer and cleaner | Cadet RECOMMENDS 12 inches from all adjacent | |||
performance. Heaters must be spaced at least | surfaces and 12 inches from the floor (See | |||
3 feet apart. | Figure 5) for longer and cleaner performance. | |||
Secure the wall can to the studs and/or sill plate | Heaters must be spaced at least 3 feet apart. | |||
|
| |||
with screws through the larger (3/16 inch) holes. |
|
| ||
(See Figures 1 and 2). |
|
| ||
|
| FIGURE 1 |
|
|
|
|
|
| |
|
| Metal legs position wall can |
|
|
|
| at minimum floor clearance. |
|
|
|
|
|
|
|
| FIGURE 2 |
|
| Bend one leg | FIGURE 5 |
| 90 degrees | |
|
| |
| for higher | STEP 2 Route Supply Wires |
| placement | |
| Route supply wire from circuit breaker to wall | |
| and secure | |
| to studs. | thermostat, then to wall can. Remove a knockout |
|
| and attach the supply wire with a strain relief |
|
| connector leaving 10 inches wire lead for later |
| FIGURE 3 | use (See Figure 4). Connect supply ground wire |
| Face of wall can must | to grounding pigtail in wall can. |
| extend ½ inch or 5/8 | STEP 3 Mount Wall Can |
| inch from face of stud | |
| to allow for thickness | FIGURE 6 |
| of sheetrock. Mount | |
| Insert wall can, legs | |
| wall can flush with | |
| first, into opening | |
| finished surface. | |
| and rotate into wall. | |
|
| |
STEP 2 Route Supply Wires |
| |
Route supply wire from circuit breaker to |
| |
thermostat to wall can. Remove a knockout |
| |
and attach the supply wire with a strain relief |
| |
connector leaving 10 inches wire lead for later |
| |
use. Connect supply ground wire to grounding | FIGURE 7 | |
pigtail in wall can (See Figure 4). Proceed to | ||
PART TWO. |
| Keeping front of |
|
| wall can flush with |
SUPPLY | FIGURE 4 | finished surface, |
WIRE |
| secure to wall stud |
|
| with screws through |
| larger (3/16 inch) holes. | |
| (TWIST TO |
|
| REMOVE) | IMPORTANT: Insert two drywall screws into |
| STRAIN RELIEF | the small holes opposite the wall stud into the |
| drywall to rest against backside of sheetrock | |
| CONNECTOR | (keeping wall can flush to wall). |
GROUNDING |
| |
|
| |
WIRE | GROUNDING | Proceed to PART TWO. |
WIRE | PIGTAIL |
|
|
| |
CONNECTOR |
|
|