Table 7 — 19XR Additional Data for Marine Waterboxes*
HEAT EXCHANGER
FRAME, PASS
ENGLISH SI
Psig Rigging Weight
(lb) Water Volume
(gal) kPa Rigging Weight
(kg) Water Volume
(L)
FRAME 2, 1 AND 2 PASS 150 730 84 1034 331 318
FRAME 2, 2 PASS 150 365 42 1034 166 159
FRAME 3, 1 AND 2 PASS 150 730 84 1034 331 317
FRAME 3, 2 PASS 150 365 42 1034 166 159
FRAME 4, 1 AND 3 PASS 150 1060 123 1034 481 465
FRAME 4, 2 PASS 150 530 61 1034 240 231
FRAME 5, 1 AND 3 PASS 150 1240 139 1034 562 526
FRAME 5, 2 PASS 150 620 69 1034 281 263
FRAME 6, 1 AND 3 PASS 150 1500 162 1034 680 612
FRAME 6, 2 PASS 150 750 81 1034 340 306
FRAME 7, 1 AND 3 PASS 150 2010 326 1034 912 1234
FRAME 7, 2 PASS 150 740 163 1034 336 617
FRAME 8, 1 AND 3 PASS 150 1855 406 1034 841 1537
FRAME 8, 2 PASS 150 585 203 1034 265 768
FRAME 2, 1 AND 3 PASS 300 860 84 2068 390 318
FRAME 2, 2 PASS 300 430 42 2068 195 159
FRAME 3, 1 AND 3 PASS 300 860 84 2068 390 317
FRAME 3, 2 PASS 300 430 42 2068 195 159
FRAME 4, 1 AND 3 PASS 300 1210 123 2068 549 465
FRAME 4, 2 PASS 300 600 61 2068 272 231
FRAME 5, 1 AND 3 PASS 300 1380 139 2068 626 526
FRAME 5, 2 PASS 300 690 69 2068 313 263
FRAME 6, 1 AND 3 PASS 300 1650 162 2068 748 612
FRAME 6, 2 PASS 300 825 81 2068 374 306
FRAME 7, 1 AND 3 PASS 300 3100 326 2068 1406 1234
FRAME 7, 2 PASS 300 2295 163 2068 1041 617
FRAME 8, 1 AND 3 PASS 300 2745 405 2068 1245 1533
FRAME 8, 2 PASS 300 1630 203 2068 739 768
*Add to heat exchanger data for total weights or volumes.
NOTES:
1. Weight adder shown is the same for cooler and condenser of equal frame size.
2. For the total weight of a vessel with a marine waterbox, add these values to the heat
exchanger weights (or volumes).
11