30

HEAT PUMP HEATING PERFORMANCE

INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ˚F(˚C)
--- 3 ( --- 1 9 . 4 ) 7 (---13.9) 17 (---8.3) 27 (---2.8) 37 (2.8) 47 (8.3) 57 (13.9) 67 (19.4)
EDB CFM
Capacity MBtuh Total
Sys-
tem
KW†
Capacity MBtuh Total
Sys-
tem
KW†
Capacity MBtuh Total
Sys-
tem
KW†
Capacity MBtuh To tal
Sys-
tem
KW†
Capacity MBtuh Total
Sys-
tem
KW†
Capacity MBtuh Total
Sys-
tem
KW†
Capacity MBtuh To tal
Sys-
tem
KW†
Capacity MBtuh Total
Sys-
tem
KW†
Total Integ* To ta l Integ* To t a l Integ* To t a l Integ* Tota l Integ* Total Integ* To ta l Integ* To t a l Integ*
25HCR360C30 Outdoor Section With FC4DN(F,B)060 Indoor Section
65
1750 25.95 23.87 3.95 31.46 28.91 4.10 37.43 34.13 4.27 44.20 39.26 4.46 51.85 47.18 4.69 60.38 60.38 4.89 68.55 68.55 5.15 74.57 74.57 5.35
2000 26.34 24.23 4.00 31.86 29.28 4.13 37.91 34.56 4.28 44.72 39.72 4.46 52.50 47.77 4.67 60.21 60.21 4.83 66.47 66.47 5.01 66.51 66.51 4.99
2250 26.69 24.56 4.05 32.23 29.61 4.17 38.34 34.95 4.32 45.20 40.15 4.49 52.97 48.20 4.64 59.85 59.85 4.82 62.69 62.69 4.88 62.10 62.10 4.85
70
1750 25.46 23.42 4.11 31.03 28.51 4.28 36.99 33.73 4.45 43.69 38.81 4.65 51.22 46.61 4.89 59.75 59.75 5.13 68.30 68.30 5.39 74.72 74.72 5.61
2000 25.85 23.79 4.16 31.44 28.89 4.30 37.45 34.14 4.46 44.22 39.28 4.65 51.82 47.15 4.87 60.00 60.00 5.05 67.83 67.83 5.29 68.80 68.80 5.30
2250 26.22 24.12 4.21 31.81 29.23 4.35 37.85 34.51 4.50 44.65 39.66 4.67 52.37 47.66 4.87 59.78 59.78 5.03 64.71 64.71 5.17 64.66 64.66 5.14
75
1750 24.93 22.93 4.27 30.56 28.09 4.45 36.57 33.34 4.64 43.17 38.34 4.85 50.61 46.05 5.10 59.02 59.02 5.38 67.93 67.93 5.63 75.31 75.31 5.91
2000 25.33 23.30 4.32 30.98 28.47 4.48 37.00 33.74 4.65 43.69 38.80 4.85 51.20 46.59 5.08 59.66 59.66 5.28 67.64 67.64 5.53 71.07 71.07 5.63
2250 25.70 23.64 4.37 31.36 28.82 4.52 37.41 34.11 4.68 44.15 39.21 4.87 51.71 47.06 5.08 59.61 59.61 5.25 65.79 65.79 5.44 66.81 66.81 5.45
Heating Indoor Model Capacity Power Furnace Model
*FC4DN(F,B)060 1.00 1.00
FK4DNB006 0.99 0.99
CSRH*6012A** 0.99 1.02 58CV(A,X)135---22
CAR**6024A** 0.99 1.02 58CV(A,X)155---22
CNRH*6024A** 0.98 1.03 58CV(A,X)155---22
CNRV*6024A** 0.98 1.03 58CV(A,X)155---22
CSRH*6012A** 0.99 1.02 58CV(A,X)155---22

NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.

* The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity.

{The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these values to obtain total system kilowatts.

EDB —EnteringDryBulb