ELECTRICAL DATA
|
|
|
|
|
|
|
| MIN | MIN | MAX | MAX | MAX | |
UNIT SIZE | V/PH | OPER VOLTS* | COMPR | FAN | MCA | WIRE | WIRE | LENGTH | LENGTH | FUSE** | |||
|
|
|
|
| SIZE† | SIZE† | ft.(m)‡ | ft.(m)‡ | or BRK | ||||
|
|
|
|
|
|
|
| ||||||
|
| MAX | MIN | LRA | RLA | FLA |
| 60˚ C | 75˚ C | 60˚ C | 75˚ C | AMPS | |
18 |
|
|
| 41 | 9.8 | 0.5 | 12.7 | 14 | 14 | 124 | 118 | 20 | |
|
|
| (37.80) | (35.97) | |||||||||
|
|
|
|
|
|
|
|
|
|
| |||
24 |
|
|
| 54 | 15.13 | 0.7 | 19.6 | 14 | 14 | 80 | 76 | 30 | |
|
|
| (23.16) | (23.16) | |||||||||
|
|
|
|
|
|
|
|
|
|
| |||
30 |
|
|
| 72.5 | 13.50 | 1.2 | 18.6 | 14 | 14 | 85 | 81 | 30 | |
|
|
| (25.91) | (24.69) | |||||||||
|
|
|
|
|
|
|
|
|
|
| |||
36 | 253 | 197 | 88 | 18.68 | 0.9 | 24.2 | 12 | 12 | 103 | 98 | 40 | ||
(31.39) | (29.87) | ||||||||||||
|
|
|
|
|
|
|
|
|
|
| |||
42 |
|
|
| 104 | 17.90 | 0.9 | 24.0 | 12 | 12 | 104 | 99 | 40 | |
|
|
| (31.70) | (30.18) | |||||||||
|
|
|
|
|
|
|
|
|
|
| |||
48 |
|
|
| 137 | 22.22 | 1.2 | 29.0 | 10 | 10 | 138 | 131 | 50 | |
|
|
| (42.06) | (39.93) | |||||||||
|
|
|
|
|
|
|
|
|
|
| |||
60 |
|
|
| 148 | 28.85 | 1.2 | 37.3 | 8 | 8 | 167 | 159 | 60 | |
|
|
| (50.90) | (48.46) | |||||||||
|
|
|
|
|
|
|
|
|
|
| |||
* Permissible limits of the voltage range at which the unit will operate satisfactorily |
|
|
|
|
|
|
{If wire is applied at ambient greater than 30° C, consult table
trade name ROMEX, shall be that of 60° C conditions, per the NEC (ANSI/NFPA 70) Article
}Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%. **
FLA
NOTE: Control circuit is
A-WEIGHTED SOUND LEVEL (dBA)
| STANDARD | TYPICAL OCTAVE BAND SPECTRUM (dB, without tone adjustment) | |||||||
UNIT SIZE | RATING | ||||||||
|
|
|
|
|
|
| |||
| (dB) | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |
|
|
|
|
|
|
|
|
| |
18 | 71 | 55 | 58 | 64.5 | 65 | 64.5 | 63 | 55.5 | |
24 | 74 | 57.0 | 62.5 | 68.5 | 69.5 | 67.5 | 63.0 | 55.0 | |
30 | 73 | 58.0 | 66.0 | 66.0 | 67.5 | 64.5 | 61.0 | 54.5 | |
36 | 74 | 53.5 | 65.5 | 64.5 | 68.5 | 66.0 | 62.0 | 54.5 | |
42 | 74 | 59.0 | 62.0 | 66.0 | 69.0 | 65.0 | 60.0 | 51.5 | |
48 | 75 | 54.5 | 61.0 | 66.0 | 71.0 | 65.5 | 62.0 | 56.5 | |
60 | 75 | 56.5 | 66.5 | 67.5 | 69.5 | 67.5 | 63.5 | 56.5 |
CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)
UNIT | REQUIRED SUBCOOLING _F (_C) | Heating Piston Size | |
18 | 10 (5.6) | 42 | |
24 | 10 (5.6) | 52 | |
30 | 10 (5.6) | 57 | |
36 | 10 (5.6) | 57 | |
42 | 10 (5.6) | 67 | |
48 | 9 | (5.0) | 67 |
60 | 10 (5.6) | 78 |
25HCR3C