30XA080-500 Minimum Load Control Accessory
Installation Instructions
Part No: 00EFN900002700A, 00EFN900002800A, 00EFN900002900A
SAFETY CONSIDERATIONS | INSTALLATION |
Installing, starting up, and servicing
Only trained, qualified installers and service technicians should install, start up, and service this equipment.
When working on
Follow all safety codes. Wear safety glasses and work gloves. Use care in handling equipment.
Be sure power to equipment is shut off before performing maintenance or service to avoid electrocution. Lock out and
GENERAL
This control accessory reduces 30XA chiller capacities be- low the standard lowest capacity step. This capacity reduction provides more precise control of leaving fluid temperature during light load conditions.
The minimum load control solenoid valve limits the amount of gas that can be bypassed from the condenser without impacting oil return.
One accessory package is required for
Table 1 — Accessory Package Usage
30XA UNIT SIZE | ACCESSORY PART NO. | |
00EFN9000002700A | ||
00EFN9000002800A | ||
325, 350 | 00EFN9000002900A | |
400 | 00EFN9000002700A, | |
00EFN9000002800A | ||
| ||
450, 500 | 00EFN9000002800A, | |
00EFN9000002900A | ||
|
Examine the package contents for correct part numbers. If any of the components are damaged, file a claim with the shipping company and notify your Carrier representative.
See Table 2A, 2B, or 2C for package contents. See Fig. 1 for dimensional drawings of tubes included in the kit.
The following material is field supplied:
•5/8 in. OD copper tubing
•5/8 in. OD copper tube elbows and couplings (as required)
•Loctite 554 thread sealing compound
•Parker Super
Install the Solenoid Valve Tube Assembly
1.Remove refrigerant charge from the circuits using an approved refrigerant recovery device before proceeding with this installation. Follow good piping practices.
2.Locate the discharge manifold for minimum load piping on the side of the coil V for each circuit as shown in Fig. 2. Locate the 1/2 in. NPT pipe plugs on the top of the cooler for each circuit. See Fig. 3.
3.Remove the 1/2 in. NPT pipe plugs from the top of the cooler. Use the thread sealing compound and install one 1
4.Remove the trim panel on the discharge manifold for minimum load piping on the side of the coil V. Use a tubing cutter to cut 11/2 in. out from the discharge mani- fold for each circuit. See Fig. 4. Braze a tee in between the gap and, depending on the routing of the hot gas bypass tubing, have the tee’s remaining port facing either left or right.
5.Use
6.When piping is completed, leak test the assembly.
7.Evacuate, dehydrate, and recharge each circuit. Be sure to use the correct type and amount of refrigerant listed in the nameplate data and base unit documentation.
8.Restore power to the unit.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book | 2 | Catalog No. | Printed in U.S.A. | Form | Pg 1 | Replaces: New | |
Tab | 5c |
|
|
|
|
|
|
|
|
|
|
|
|
|
|