INSTALLATION IN 38AKS014-024/INDOOR
FAN COIL (CONSTANT VOLUME)
SPLIT SYSTEM COMBINATION Step 1 — Install Piping (See Fig. 4)
Shut off all power to the unit and remove refrigerant charge using an approved refrigerant recovery device before pro- ceeding with installation. Failure to do so may result for personal injury.
IMPORTANT: Do not bury refrigerant piping underground.
1.In applications where the air handler refrigerant distribu- tor is not equipped with a side outlet connection, it is rec- ommended that a Sporlan
2.Install a
3.Sweat the pilot solenoid valve supplied in the hot gas ac- cessory package directly to the hot gas bypass valve on the 3/8 in. ODF external equalizer port.
4.Install
5.Connect a
6.Connect another
7.Connect a
LEGEND
TXV — Thermostatic Expansion
Valve
*Pilot valve connects directly to bypass valve per sketch A.
Fig. 4 — 38AKS Hot Gas Bypass Piping
3