Table 7 — CADM Troubleshooting
Miswired Module Indication | Recommended Troubleshooting Action |
Green LED is not on, | Determine if both R and C module terminals are |
module does not power up | connected. Verify voltage in present at module’s R and C |
| terminals. |
| NOTE: The CADM requires a constant nominal 24VAC |
| power supply. The wiring to the module’s R and C |
| terminals must be directly from the control transformer. |
| The module cannot receive its power from another device |
| that will interrupt the 24VAC power supply. See Fig. 20, |
| the 38AU Wiring Diagram. |
|
|
Green LED Intermittent, | Determine if R and Y terminals are wired in reverse. Verify |
module powers up only | module’s R and C terminals have a constant source. See |
when compressor runs | “NOTE” above for details on R and C wiring. |
|
|
TRIP LED is on but system | Verify Y terminal is wired properly per the 38AU wiring |
and compressor check OK | diagram (see Fig. 19). Verify voltage at contactor coil falls |
| below 0.5VAC when off. Verify 24VAQC is present across |
| Y and C when thermostat demand signal is present. If not, |
| R and C are reverse wired. |
|
|
TRIP LED and ALERT LED | Verify R and C terminals are supplied with |
flashing together |
|
|
|
ALERT Flash Code 3 | Verify Y terminal is connected to 24VAC at contactor coil. |
(Compressor Short Cycling) | Verify voltage at contactor coil falls below 0.5VAC when |
displayed incorrectly | off. |
|
|
ALERT Flash Code 5 or 6 | Check that compressor T1 and T3 wires are through |
(Open Circuit, Missing Phase) | module’s current sensing holes. Verify Y terminal is |
displayed incorrectly | connected to 24VAC at contactor coil. Verify voltage at |
| contactor coil falls below 0.5VAC when off. |
|
|
Alert Flash Code * | Determine if module’s Y terminal is connected. Verify Y |
(Welded Contactor) | terminal is connected to 24VAC at contactor coil. Verify |
displayed incorrectly | 24VAC is present across Y and C when thermostat |
| demand signal is present. If not, R and C are reverse |
| wired. Verify voltage at contactor coil falls below 0.5VAC |
| when off. |
|
|
Crankcase Heater — The heater prevents refrigerant migration and compressor oil dilution during shutdown when- ever compressor is not operating. The heater is wired to cycle with the compressor; the heater is off when compressor is run- ning, and on when compressor is off.
The crankcase heater will operate as long as the power circuit is energized.
Compressor Protection
COMPRESSOR OVERTEMPERATURE PROTECTION (IP) — A thermostat installed on the compressor motor wind- ing reacts to excessively high winding temperatures and shuts off the compressor.
CRANKCASE HEATER — The heater minimizes absorp- tion of liquid refrigerant by oil in the crankcase during brief or extended shutdown periods. The main disconnect must be on to energize the crankcase heater.
IMPORTANT: Never open any switch or disconnect that energizes the crankcase heater unless unit is being serviced or is to be shut down for a prolonged period. After a pro- longed shutdown on a service job, energize the crankcase heater for 24 hours before starting the compressor.
ADVANCED SCROLL TEMPERATURE PROTECTION (ASTP) — See “Advanced Scroll Temperature Protection (ASTP)” on page 15.
Outdoor Fans — Each fan is supported by a
Lubrication
FAN MOTORS have sealed bearings. No provisions are made for lubrication.
COMPRESSOR has its own oil supply. Loss of oil due to a leak in the system should be the only reason for adding oil after the system has been in operation.
21