Table 1B — Physical Data — 38AUZ*07-14 Units — 60 Hz SI

UNIT SIZE 38AU

Z*07

 

Z*08

 

Z*12

 

Z*14

NOMINAL CAPACITY (kW)

21.1

 

26.4

 

35.1

 

44

OPERATING WEIGHT (kg)

 

 

 

 

 

 

 

Aluminum-Fin Coils (Standard)

149

 

160

 

190

 

196

REFRIGERANT TYPE*

 

 

R-410A

 

 

Operating Charge, Typical (kg)†

3.8

 

4.6

 

6.3

 

8.2

Shipping Charge (kg)

2.0

 

2.2

 

2.9

 

3.3

COMPRESSOR

 

 

Scroll

 

 

Qty...Model

1...ZP61

 

1...ZP83

 

1...ZP103

 

1...ZP137

Oil Charge (L)

1.7

 

1.8

 

3.3

 

3.3

No. Cylinders

 

 

 

N/A

 

 

Speed (r/s)

 

 

 

58

 

 

CONDENSER FANS

 

2...18

 

 

Qty...r/s

 

 

 

Motor Hp NEMA

 

 

 

1/4

 

 

Diameter (mm)

 

 

 

560

 

 

Nominal Airflow (L/s)

 

2832

 

 

Watts (Total)

 

 

 

610

 

 

CONDENSER COIL (Qty)

 

 

1...NOVATION

 

 

Face Area (sq m total)

1.6

 

1.9

 

2.3

 

3.0

Rows/Fins per Meter (Fins/m)

1...670

 

1...670

 

1...670

 

1...670

Storage Capacity (kg)**

2.5

 

2.7

 

3.4

 

3.9

CONTROLS

 

 

 

 

 

 

 

Pressurestat Settings (kPa)

 

 

 

 

 

 

 

High Cutout

 

4347 ± 70

 

 

Cut-in

 

3482 ±138

 

 

Low Cutout

 

372 ± 21

 

 

Cut-in

 

807 ± 34

 

 

PIPING CONNECTIONS (in. ODS)

1...11/8

 

1...11/8

 

1...13/8

 

1...13/8

Qty...Suction

 

 

 

Qty...Liquid

1...3/8

 

1...1/2

 

1...1/2

 

1...5/8

LEGEND

NEMA — National Electrical Manufacturers Association

ODS — Outside Diameter Sweat (socket)

* Unit is factory-supplied with partial charge only.

† Typical operating charge with 7.62 m of interconnecting piping.

** Storage capacity of condenser coil with coil 80% full of liquid R-410A at 35°C.