If TXV installation is required, remove existing AccuRater® from indoor coil. Refer to Figs. 4 and 5 and install TXV kit as follows:
1.Install suction tube adapter.
2.Install liquid
3.Connect external equalizer tube to fitting on suction tube adapter.
4.Position sensing bulb on horizontal portion of suction tube adapter. Secure using supplied hardware.
5.Insulate bulb after installation. (See Fig. 5.)
6.Leak check all connections.
COIL
SENSING
BULB
EQUALIZER
TUBE
THERMOSTATIC
EXPANSION
VALVE
A88382
Fig. 4—Typical TXV Installation
feeder tubes, there is a
FEEDER TUBE
STUB TUBE
DEFROST
THERMOSTAT
A97517
Fig. 6—Defrost Thermostat Location
Step 9—Make Piping Connections
Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow control devices, including solenoid valves.
10 O'CLOCK
2 O'CLOCK
STRAP |
SUCTION TUBE
8 O'CLOCK
7⁄8 IN. OD & SMALLER
SENSING BULB
4O'CLOCK
LARGER THAN 7⁄8 IN. OD
If ANY refrigerant tubing is buried, provide a 6 in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. may be buried without further special consideration. For lengths longer than 36 in., refer to Application Guideline and Service Manual — Residential Split System Air Conditioners and Heat Pumps.
To prevent damage to unit or service valves observe the following:
•Use a brazing shield.
•Wrap service valves with wet cloth or use a
A81032
Fig. 5—Positioning of Sensing Bulb
Step 7—Check Outdoor AccuRater® Piston
Check outdoor unit piston. Remove retainer on liquid service valve and check piston size with matching number listed on outdoor unit rating plate.
Step 8—Check Defrost Thermostat
Check defrost thermostat to ensure it is properly located and securely attached. There is a liquid header with a brass distributor and feeder tube going into outdoor coil. At the end of 1 of the
Outdoor units may be connected to indoor section using accessory- tubing package or
For buried line applications greater than 36 in., refer to Table 2 and Residential Split System Buried Line Application Guideline. Buried line applications may not exceed 100 ft.
If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.
3