Carrier 38BYG, 38BYC AccessoryUsage, LinePower Connections, Start-Up, CompressorCrankcase Heater

Models: 38BYG 38BYC

1 8
Download 8 pages 29.42 Kb
Page 5
Image 5
Table 2—Accessory Usage

Table 2—Accessory Usage

 

REQUIRED FOR

REQUIRED FOR

REQUIRED FOR

ACCESSORY

LOW-AMBIENT

LONG-LINE

BURIED LINE

APPLICATIONS

APPLICATIONS*

APPLICATIONS†

 

 

(BELOW 55°F)

(OVER 50 FT)

(OVER 3 FT)

Crankcase Heater

Yes

Yes

Yes

Evaporator Freeze Thermostat

Yes

No

No

Accumulator

No

No

Yes

Compressor Start-Assist

Yes

Yes

Yes

Capacitor and Relay

 

 

 

MotorMaster® Control,

 

 

 

or

Yes

No

No

Low-Ambient Pressure Switch

 

 

 

Wind Baffle

See low-ambient

No

No

Instructions

 

 

 

Unit Risers

Recommended

No

No

Liquid-Line Solenoid Valve

 

See Long-Line

 

or

No

Application

Yes

Hard-Shutoff TXV

 

Guideline

 

Ball-Bearing Fan Motor

Yes‡

No

No

 

 

 

 

*For tubing line sets between 50 and 175 ft, refer to Application Guideline and Service Manual — Air Conditioners and Heat Pumps.

† For buried line applications, refer to Application Guideline and Service Manual — Air Conditioners and Heat Pumps.

‡ Required for low-ambient controller (full-modulation feature) and MotorMaster® Control only.

DISCONNECT

PER N. E. C. AND/OR LOCAL CODES

FIELD POWER

WIRING

FIELD GROUND

WIRING

CONTACTOR

GROUND

LUG

A91056

Step 13—Start-Up

To prevent compressor damage or personal injury, observe the following:

•Do not overcharge system with refrigerant.

•Do not operate unit in a vacuum or at negative pressure. •Do not disable low-pressure switch.

In scroll compressor applications: •Dome temperatures may be hot.

Fig. 8—Line Power Connections

Use furnace transformer, fan coil transformer, or accessory trans- former for control power, 24v/40va minimum.

NOTE: Use of available 24v accessories may exceed the mini- mum 40va power requirement. Determine total transformer load- ing and increase the transformer capacity or split the load with an accessory transformer as required.

IMPORTANT: Check factory wiring and wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, and so forth.

Step 11—Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit. A crankcase heater is required if refrigerant tubing is longer than 50 ft.

Step 12—Install Electrical Accessories

Refer to the individual instructions packaged with kits or acces- sories when installing.

To prevent personal injury wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following:

•Back-seating service valves are not equipped with Schrader valves. Fully back seat (counterclockwise) valve stem before removing gage-port cap.

•Front-seating service valves are equipped with Schrader valves.

Federal Regulations require that you do not vent refrigerant to atmosphere. Recover during system repair or final unit disposal.

Follow these steps to properly pumpdown a system and avoid negative suction pressure.

1.Fully back seat (open) liquid- and vapor-tube service valves.

2.Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after system is opened to refrigerant flow. Replace caps finger-tight and tighten with wrench an additional 1/12 turn.

3.Close electrical disconnects to energize system.

5

Page 5
Image 5
Carrier 38BYG AccessoryUsage, LinePower Connections, Start-Up, CompressorCrankcase Heater, InstallElectrical Accessories