Evacuating

Valve handling precautions

Size

ø

9,52

33 a 42 N•m (3,3 a 4,2 kgf•m)

 

ø

15,87

20 a 25 N•m (2,0 a 2,5 kgf•m)

Service connection

14 a 18 N•m (1,4 a 1,8 kgf•m)

 

 

 

 

Open the valve stem or the handle until it strikes the stopper. It is unnecessary to apply further force.

Securely tighten the cap with a torque wrench.

Cap tightening torque

Electrical connections

Make refrigerant connections before electrical connections.

When disconnecting, disconnect electrical connections before refrigerant connections.

IMPORTANT:

Make ground connection prior to any other electrical connections.

Model

38VYX110

 

38VYX130

 

 

 

Power supply

220240 V

Single phase 50Hz

 

 

 

 

 

Maximum running current

22 A

 

22,8A

 

 

 

 

Installation

25 A (type D

)

fuse rating

 

 

 

 

 

 

Power cable

H07 RN-F (245 IEC 57)

2,5 mm2

 

 

 

 

 

All field electrical connections are the responsibility of the installer.

WARNING:

• Wrong wiring may cause a burn-out to some electrical parts.

• Be sure to use the cord clamps attached to the product.

• Do not damage or scratch the conductive core and inner

insulator of power and inter-connecting cables when peeling

them.

• Be sure to comply with local regulations of the cable from

Terminal block

Terminal block power supply

Power cable

To the indoor unit

Earth

Connecting cable

Power cable and connecting cable

outdoor unit to indoor unit.

(wire size and cabling method etc.)

• Use the power and Inter-connecting cables with specified

thickness, specified type and protective devices required.

1.Connect the connecting cable to the terminal as identified with their respective numbers on the terminal block of indoor and outdoor unit.

L N 10

10

30

 

1

2

3

 

 

 

10

 

Connecting

 

 

40

cable

 

30

Power cable

 

 

 

 

 

 

 

Ground

 

 

 

connector

 

 

(mm)

The indoor - outdoor unit interconnecting wires must be A07 RN-F type (245 IEC 57) or higher, with synthetic rubber insulation with Neoprene coating, according to EN 60335-2-40 codes.

The mains supply connecting cable for 38VYX units, must be H07 RN-F type (245 IEC 57) or higher, with synthetic rubber insulation with Neoprene coating, according to EN 60335-2-40 codes.

Refer to the indoor unit installation manual for sizing of the power supply wires.

2.For inter connecting cable, do not use a wire jointed to another on the way.

Use wires long enough to cover the entire length.

The installation fuse (25A D type ) must be used for the power supply line of this air conditioner.

Incorrect/incomplete wiring might cause an electrical fire or smoke.

Prepare the exclusive power supply for the air conditioner.

Ensure that mains supply connection is made through a switch that disconnects all poles, with contact gap of a least 3 mm.

GB - 10

Page 11
Image 11
Carrier 38VYX130, 38VYX110 Electrical connections, Valve handling precautions, Power cable and connecting cable

38VYX110, 38VYX130 specifications

The Carrier 38VYX130 and 38VYX110 are advanced air conditioning units designed for residential and light commercial applications, offering optimal energy efficiency, reliable performance, and enhanced comfort. These models exemplify Carrier's commitment to delivering high-quality climate control solutions.

One of the standout features of the Carrier 38VYX series is its energy efficiency. Both the 38VYX130 and 38VYX110 boast a high Seasonal Energy Efficiency Ratio (SEER) rating, indicating their ability to provide effective cooling while consuming less energy. This makes them an environmentally friendly option, as well as a cost-effective choice for homeowners and businesses looking to reduce their energy bills.

The 38VYX130 and 38VYX110 utilize inverter technology, which allows the compressor to adjust its speed based on the cooling demand. This not only enhances energy efficiency but also ensures consistent comfort levels by minimizing temperature fluctuations. This feature is particularly beneficial in variable weather conditions, providing a stable indoor climate without excessive energy consumption.

Another significant technological advancement in these models is the use of R-410A refrigerant, which is known for its low environmental impact compared to traditional refrigerants. This aligns with Carrier's commitment to sustainability and reducing the carbon footprint of their products. Additionally, both units are equipped with advanced filtration systems that help improve indoor air quality by capturing dust, allergens, and other airborne particles.

The Carrier 38VYX series is also designed with quiet operation in mind. With sound levels that fall within the low dB range, these units ensure that homeowners can enjoy a comfortable living environment without disruptive noise, whether the system is running during the day or at night.

For ease of installation and maintenance, the 38VYX130 and 38VYX110 come with user-friendly features, including a compact design that allows for flexible placement and service access. Furthermore, Carrier offers a robust warranty and customer support, ensuring peace of mind for users.

In conclusion, the Carrier 38VYX130 and 38VYX110 are exceptional choices for those looking for efficient, reliable, and quiet air conditioning systems. With their advanced technologies and commitment to sustainability, these models are set to provide superior comfort for years to come.