42VMC

Electrical connections

Heat pump

E N G L I S H

Unit

42VMC 009, 012, 014

System

L N NY O W2

￿￿

￿

L N N Y O W2

50Hz~ 230V ￿ ￿

N Y O W2

￿

Unit

42VMC 018, 024

System

￿

R C YO W2 S

￿ ￿ 50Hz~

230V

R C Y O W2 S

￿

￿

L N R C Y O W2 S

￿

 

 

 

 

Minimum connection wire size between

 

 

 

 

 

 

 

indoor and outdoor units (mm2)

 

 

Model

L

N

N

R

C

Y

O

 

W2

S

 

 

 

 

 

 

 

 

 

 

 

42VMC 009

2.5

2.5

1.5

1.5

1.5

 

1.5

 

 

 

 

 

 

 

 

 

 

 

42VMC 012, 014

2.5

2.5

2.5

2.5

2.5

 

2.5

 

 

 

 

 

 

 

 

 

 

 

42VMC 018, 024

1.5

1.5

1.5

1.5

 

1.5

1.5

 

 

 

 

 

 

 

 

 

 

 

Terminal box legend

Earth.

LLive power supply.

N Neutral power supply.

N Neutral connection indoor/outdoor unit. R Live connection indoor/outdoor unit.

C Neutral connection indoor/outdoor unit. Y Compressor interlocking contact.

O Reversing valve control.

W2 Outdoor fan signal.

SDefrost end signal.

10120

10 100

￿Mains supply connecting cable

￿(field wiring).

￿Connecting cable, indoor-outdoor units (field wiring).

￿￿ Indoor unit

￿Outdoor unit

￿Main switch

￿Time-delay fuse or circuit breaker (see outdoor unit installation manual)

GB - 11