9-2-3. Check Code List (Indoor)

¡ : Go on, ¥ : Flash, l : Go off ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two flashing LED

(Indoor unit detected)

 

Check code indication

Sensor lamp indication

 

 

 

Air conditioner operation

 

TCC-LINK central &

Block indication

 

Representative defective position

 

Explanation of error contents

Automatic

Operation

 

Wired remote controller

Operation

Timer

Ready

Flash

 

 

 

reset

continuation

 

E03

¥

l

l

 

Regular communication error between indoor and

 

No communication from remote controller and network adapter

¡

×

 

 

remote controller

 

(Also no communication from central control system)

 

E04

l

l

¥

 

Indoor/Outdoor serial error

 

There is error on serial communication between indoor and outdoor units

¡

×

 

E08

¥

l

l

 

Duplicated indoor addresses

²

Same address as yours was detected.

¡

×

 

E10

¥

l

l

 

Communication error between indoor MCU

 

MCU communication error between main motor and micro computer

¡

×

 

E18

¥

l

l

 

Regular communication error between

 

Regular communication between indoor master and follower units is impossible,

¡

×

 

 

indoor master and follower units

 

Communication between twin master (main) and follower (sub) units is impossible.

 

F01

¥

¥

l

ALT

Indoor unit, Heat exchanger (TCJ) error

 

Open/short was detected on heat exchanger (TCJ).

¡

×

 

F02

¥

¥

l

ALT

Indoor unit, Heat exchanger (TC) error

 

Open/short was detected on heat exchanger (TC).

¡

×

 

F10

¥

¥

l

ALT

Indoor unit, Room temp. sensor (TA) error

 

Open/short was detected on room temp. sensor (TA).

¡

×

 

F29

¥

¥

l

SIM

Indoor unit, other indoor P.C. board error

 

EEPROM error (Other error may be detected. If no error, automatic address is repeated.

×

×

 

L03

¥

l

¥

SIM

Duplicated setting of indoor group master unit

²

There are multiple master units in a group.

×

×

 

L07

¥

l

¥

SIM

There is group cable in individual indoor unit.

²

When even one group connection indoor unit exists in individual indoor unit.

×

×

 

L08

¥

l

¥

SIM

Unset indoor group address

²

Indoor group address is unset.

×

×

 

L09

¥

l

¥

SIM

Unset indoor capacity

 

Capacity of indoor unit is unset.

×

×

 

L20

¥

¡

¥

SIM

Duplicated central control system address

 

Duplicated setting of central control system address

¡

×

 

L30

¥

¡

¥

SIM

Outside error input to indoor unit (Interlock)

 

Abnormal stop by outside error (CN80) input

×

×

 

P01

l

¥

¥

ALT

Indoor unit, AC fan error

 

An error of indoor AC fan was detected. (Fan motor thermal relay worked.)

×

×

P10

l

¥

¥

ALT

Indoor unit, overflow detection

 

Float switch worked.

×

×

71

P12

l

¥

¥

ALT

Indoor unit, DC fan error

 

Indoor DC fan error (Over-current/Lock, etc.) was detected.

×

×

P19

¥

l

¥

ALT

4-way valve system error

 

In heating operation, an error was detected by temp. down of indoor heat exchanger sensor.

¡

×

P31

¥

l

¥

ALT

Other indoor unit error

 

Follower unit in group cannot operate by warning from [E03/L03/L07/L08] of master unit.

¡

×

²When this warning was detected before group construction/address check finish at power supply was turned on, the mode shifts automatically to AUTO address setup mode.

(Remote controller detected)

Check code indication

Sensor lamp indication

 

 

Air conditioner operation

Wired remote controller

Block indication

 

Representative defective position

Explanation of error contents

Automatic

Operation

 

Operation

Timer

Ready

 

Flash

 

 

reset

continuation

E01

¥

l

l

 

 

No master remote controller, Remote controller

Signal cannot be received from indoor unit. Master remote controller was not set.

 

 

communication (Receive) error

(including 2 remote controllers)

 

 

 

 

 

 

 

 

E02

¥

l

l

 

 

Remote controller communication (Send) error

Signal cannot be sent to indoor unit.

E09

¥

l

l

 

 

Duplicated master remote controller

In 2-remote controller control, both were set as master. (Indoor master unit stops warning

×

 

 

 

and follower unit continues operation.)

 

(Central control devices detected)

 

 

 

 

 

 

 

 

 

 

 

 

Check code indication

Sensor lamp indication

 

 

Air conditioner operation

TCC-LINK central

Block indication

 

Representative defective position

Explanation of error contents

Automatic

Operation

Operation

Timer

Ready

 

Flash

 

 

reset

continuation

 

 

 

 

C05

Is not displayed.

 

Central control system communication (send) error

Signal sending operation of central control system is impossible.

 

(Common use of

 

 

There are multiple same central devices. (AI-NET)

 

 

C06

remote controller, etc.)

Central control system communication (receive) error

Signal receiving operation of central control system is impossible.

C12

 

 

 

 

General-purpose device control interface batched warning

An error on device connected to general-purpose device control interface of exclusive to

 

 

 

 

TCC-LINK/AI-NET

 

 

 

 

 

 

 

 

 

P30

 

By warning unit

 

Group follower unit is defective.

Group follower unit is defective.

(Above-mentioned)

 

(For remote controller, above-mentioned [∗∗∗] details are displayed with unit No.

 

 

 

 

 

NOTE: Even for the same contents of error such as communication error, the display of check code may differ according to detection device.

When remote controller or central controller detects an error, it is not necessarily related to operation of the air conditioner. In this list, the check codes that outdoor unit detects are not described.

Page 71
Image 71
Toshiba RAV-SP1104ATZG-E, RAV-SM1404UT-E Check Code List Indoor, Indoor unit detected, Remote controller detected

RAV-SP1104ATZG-E, RAV-SP1104ATZ-E, RAV-SP1404ATZ-E, RAV-SM804UT-E, RAV-SP1404AT-E specifications

Toshiba has long been a notable player in the air conditioning market, with a range of products designed to deliver effective cooling and heating solutions. Among its recent offerings are the RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models. Each of these models is engineered for efficiency, performance, and user convenience.

The RAV-SP1104AT-E is designed for residential and commercial spaces alike, featuring advanced inverter technology. This model operates efficiently by adjusting compressor speed according to the required cooling load, resulting in reduced energy consumption and optimal performance. With a cooling capacity of 11 kW, it is suitable for medium to large spaces.

The RAV-SM1404UT-E model builds on this efficiency with enhanced features aimed at maximizing comfort. It includes a built-in Wi-Fi capability, allowing users to control the system remotely through a mobile app. This model boasts a high-energy efficiency rating, which translates into lower operating costs and a smaller environmental footprint.

Similarly, the RAV-SM1104UT-E emphasizes versatility and adaptability, adept at handling various climatic conditions. In addition to its robust cooling performance, it supports heating capabilities, making it an excellent choice for year-round use. The unit's quiet operation ensures comfort without the nuisance of disruptive noise, making it ideal for both residential and commercial settings.

The RAV-SP1104ATZ-E and RAV-SP1404ATZ-E models represent the pinnacle of Toshiba's innovation in multi-split systems. Both models utilize advanced refrigerant technology, ensuring rapid cooling and heating while minimizing energy loss. The RAV-SP1104ATZ-E offers a balanced performance with a focus on high efficiency, while the RAV-SP1404ATZ-E provides greater capacity, ideal for larger establishments requiring substantial climate control.

All these units feature Toshiba's cutting-edge technologies, including advanced filtration systems that improve indoor air quality by capturing dust, allergens, and other particulates. The robust design of these models ensures durability and longevity, making them a worthwhile investment for any property owner.

In summary, Toshiba’s RAV-SP1104AT-E, RAV-SM1404UT-E, RAV-SM1104UT-E, RAV-SP1104ATZ-E, and RAV-SP1404ATZ-E models reflect the brand's commitment to innovation and energy efficiency. These air conditioning solutions cater to a variety of needs while ensuring comfort, reduced environmental impact, and user-friendly operation.